Page 1: ...iSMA B AAC20D User Manual DALI Network Global Control 5 Sp z o o Warsaw Poland www gc5 pl ...

Page 2: ...etwork kit 7 3 1 DALI license and limitation 7 3 2 DALI Network component 8 DALI Network actions Device Discover and New Initialization 9 4 DALI Device 10 4 1 DALI Scenes and Groups 12 5 DALI light control components 13 5 1 DALI Command 13 5 2 DALI On Off 14 5 3 DALI On Off Dimming 1 Switch 14 5 4 DALI On Off Dimming 2 Switch 15 5 5 DALI On Off Preset Value 17 5 6 DALI On Off Recall Scene 18 5 7 D...

Page 3: ...the commands that ballasts need to recognize in order to be considered DALI ballasts The system allows individual ballasts to talk to the user and allows the user to talk back via DALI controllers computers equipped with appropriate software or building management systems BMS Warning Before programming Sedona DALI kit please check if you are using the latest kit version The latest kits are availab...

Page 4: ...ous kits in a zip file To do this use an application from the Tools menu Sedona Installer After successful import of the files upload the files to your device using the Kit Manager Application from the Sedona Tools package Warning Before programming Sedona DALI Network please check if you are using the latest kit version The latest kit is available on GC5 support web site www support gc5 pl Figure...

Page 5: ...rom the Sedona Tools To install selected kit Step 1 Open Work Place expand Sedona Application then Sedona Tools and then choose double click Kit Manager Step 2 In the Kit Manager you can manage your kits on the Sedona device Step 3 Select DALI kit then you can click Next Finish and Restart Device Step 4 Your components install successful Figure 2 Kit Manager installing DALI kit ...

Page 6: ... Work Place expand Sedona Application next Sedona Tools and then choose double click Kit Manager Step 2 In the Kit Manager you can manage your kits on the Sedona device Step 3 Uncheck Dali kit then you can click Next Finish and Close Step 4 Your components uninstall successful Figure 3 Kit Manager removing DALI kit ...

Page 7: ...ces DALI Network kit consists of 11 types of components DALI Command DALI Device DALI Device Folder DALI Logic Folder DALI Network DALI On Off DALI On Off Dimming 1 Switch DALI On Off Dimming 2 Switch DALI On Off Preset Value DALI On Off Recall Scene DALI Scene Setter Figure 4 iSMA DALI kit components 3 1 DALI license and limitation In standard license there are available 64 DALI devices and this ...

Page 8: ...laced under Drivers folder DALI network component has the following slots Status Network status available states OK Network is working properly Disabled Network is disable Slot Enable is in false Fault Cause Fault cause description Power Supply Switches to on off DALI network power supply Figure 5 DALI Network Note As part of the DALI Network component configuration actions performed by the integr...

Page 9: ...ected to DALI port It will also create Discover folder and place there all found devices All devices have unique address assigned by manufacturer slot Address All devices can be moved and groped in to Device Folders folders must be also placed under DALI Network component Discover New Initialization This action has the same functionality like Discover but also is responsible for Short Address Afte...

Page 10: ...area allows the light source s of the device to flash DALI Device component has the following slots Status device current status Fault Cause Fault cause description Description Additional description label Device Type Type of device Short Address In some installations it makes sense to define the address at the planning stage Random Address Hexadecimal address of device connected to the DALI input...

Page 11: ... Level Minimum brightness value this value cannot be undershot when fading down Power On Level Brightness value to which the Dali ballast switches when the power supply is switched on System Failure Level Brightness value to which the Dali ballast switches when a fault is detected in the Dali circuit Fade Time Time in seconds for fading from the current brightness value to the new brightness value...

Page 12: ...ence room or a morning scene in a wellness centre The values of the 16 scenes are stored in the control gear DALI Groups Figure 7 above With DALI device it is possible to define 16 groups in a DALI circuit A group is a meaningful collection of devices Group assignment can be edited in DALI It is possible for one DALI device to belong to several groups This reduces the amount of wiring needed and g...

Page 13: ...mmands Individual in slots are provided for various Sedona DALI commands A transition from false to true will cause the associated Sedona DALI command to be sent to the control gear DALI Device component has the following actions Send This action will send DALI command to DALI devices Figure 9 Sedona DALI Command Sedona DALI command has the following slots Status Component current status Descripti...

Page 14: ...witch Off command to device devices 5 3 DALI On Off Dimming 1 Switch This component has the built in DALI command which allows to switch On and Off or to change DALI device devices lighting level This component was designed to work with single switch one button connect to one digital input The switch is working in two modes short and long press The short press when Switch slot is in true mode for ...

Page 15: ...nent current status Description User description up to 32 characters Address Short DALI device address or DALI group address Address Type You can manage single device group or all DALI devices Switch Component input with will trigger DALI command sending Long Press Time parameter which will define time for long press function In default 500ms Scene No For Last Level Scene number which will store l...

Page 16: ...s of triggering the corresponding inputs therefore it is suitable for connection with other components affecting the same ballast whether by Address Type Single or Group or All The component has the following actions Send Short Press On This action will send On command and to DALI device devices Send Short Press Off This action will send Off command and to DALI device devices Figure 12 iSMA DALI O...

Page 17: ... sending slots so different values for On and Off trigger can be defined The component has the following actions Send Value On This action will send to DALI device devices direct level value assign to On trigger Send Value Off This action will send to DALI device devices direct level value assign to Off trigger Figure 13 iSMA DALI On Off Preset Value The component has the following slots Status Co...

Page 18: ...ts so define different scenes for On and Off trigger can be defined The component has the following actions Send Scene On This action will send to DALI device devices recall scene number assign to On trigger Send Scene Off This action will send to DALI device devices recall scene number assign to Off trigger Figure 14 iSMA DALI On Off Recall Scene The component has the following slots Status Compo...

Page 19: ...ene which value is to be changed to the current level of the luminaire actual level The component has the following actions Save Scene This action sends a command to the DALI device devices to save the actual level for ballast to the scene number indicated by the Scene Number slot Figure 15 iSMA DALI Scene Setter The component has the following slots Status Component current status Description Use...