SfAR-S-6TI User Manual
www.ismacontrolli.com
DMP272en | 3rd Issue rev. 2 | 05/2022
page 21 of 26
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
30054
53
0x35
Temperature 2
Read
in °C·10 for temperature
in Ω for resistance
30055
54
0x36
Temperature 3
Read
30056
55
0x37
Temperature 4
Read
30057
56
0x38
Temperature 5
Read
30058
57
0x39
Temperature 6
Read
30059
58
0x3A
Alarm Temperature 1
Read
Alarm temperature for
alarm output 1
30060
59
0x3B
Alarm Temperature 2
Read
Alarm temperature for
alarm output 2
30061
60
0x3C
Junction Temperature
Read
Module junction
temperature
30062
61
0x3D
Measurement Current Read
Measurement current
40063
62
0x3E
MAX Alarm Level 1
Read/write
If the temperature
exceeds this value the
corresponding alarm flag
is set
40064
63
0x3F
MAX Alarm Level 2
Read/write
40065
64
0x40
MAX Alarm Level 3
Read/write
40066
65
0x41
MAX Alarm Level 4
Read/write
40067
66
0x42
MAX Alarm Level 5
Read/write
40068
67
0x43
MAX Alarm Level 6
Read/write
40069
68
0x44
MIN Alarm Level 1
Read/write
If the temperature is
below this value
corresponding alarm flag
is set
40070
69
0x45
MIN Alarm Level 2
Read/write
40071
70
0x46
MIN Alarm Level 3
Read/write
40072
71
0x47
MIN Alarm Level 4
Read/write
40073
72
0x48
MIN Alarm Level 5
Read/write
40074
73
0x49
MIN Alarm Level 6
Read/write
40075
74
0x4A
Alarm Settings 1
Read/write
Alarm Settings
0 – alarm due to the
current temperature
1 – remember the value of
the alarm, until reset by
the master via Modbus
40076
75
0x4B
Alarm Settings 2
Read/write
40077
76
0x4C
Alarm Settings 3
Read/write
40078
77
0x4D
Alarm Settings 4
Read/write