21
Condensate Drain Kit (
cont.
)
Internal Drain
Installation
Part Number 6140165
The drain kit can be installed as an internal drain on the bot-
tom of the wall sleeve to allow condensate to drain into an
internal drain system inside of the building. Locate the drain
so that it will be on the room side of the wall when the cabinet
wall sleeve is installed.
NOTE: The drain kit must be installed prior to the installation
of the wall sleeve.
1.
Locate an area on the wall sleeve that will be inside
the room when the sleeve is installed. If a subbase
is installed, locate the kit a minimum of 5 ½” from
the front flange of the wall sleeve. This clearance will
provide adequate clearance for the subbase.
2.
Cutout the template shown to the right. Using this
template, locate and drill the drain kit holes as close
to the outside wall as possible.
3.
Using detail figure 14 as a guide, assemble the drain
gasket, drain fitting plate, and indoor drain fitting
together. Install the assembly into the drilled holes
and secure using the two indoor mounting screws
provided. The screws must be inserted INSIDE the
wall sleeve and TOP driven down into the drain fit-
ting plate.
Ensure drain tube is not restricted. Cover the two screw heads
with a good quality outdoor caulking (not supplied) for addi-
tional corrosion protection.
NOTE: If the drain fitting is not connected to an indoor
drainage system immediately after the wall sleeve is installed,
plug the hole with cork (not included) to prevent indoor water
damage in case it rains.
4.
Install a ½” ID tube or hose (not included) on the
drain fitting and interconnect it to the drain system
inside of the building. Ensure that there are no kinks
or traps in tube or hose. Kinks or traps can cause
improper drainage.
5.
Install the two drain block-off plates and outdoor
drain gaskets on the outdoor portion of the wall
sleeve as shown in figure 15. These components can
be installed after the sleeve is secured in the wall
opening just prior to the installation of the condenser
grille and chassis.
DRAIN LOCATION FROM SIDE-
TO-SIDE IS DETERMINED BY
BUILDING DRAIN SYSTEM
DRAIN LOCATION FROM FRONT EDGE OF WALL
SLEEVE SHOULD BE A MIN. OF 5.5 INCHES IF
USING SUBBASE
DETERMINE LOCATION OF
INTERNAL DRAIN.
DRILL MOUNTING HOLES
ACCORDING TO TEMPLATE
Figure 13
Internal Drain Location
ATTACH DRAIN FITTING, GASKET, AND PLATE WITH SCREWS
INSERTED THROUGH WALL SLEEVE
SHEET METAL
SCREWS
GASKET
PLATE
DRAIN FITTING
INSIDE OF WALL SLEEVE
Figure 14
Internal Drain Installation
BLOCK-OFF
PLATE
SHEET METAL
SCREWS
OUTDOOR
GASKET
INSTALL BLOCK-OFF PLATES
AND GASKETS OVER LEFT AND
RIGHT EXTERIOR DRAIN HOLES
Figure 15