1 NVRAM battery assemblies
Figure 3. NVRAM battery location
2. Lift up the locking tab at the bottom of the battery battery assembly.
2
1
1 Locking tab
2 NVRAM battery
Figure 4. Removing an NVRAM battery assembly
3. Remove the battery assembly out of the node, using the handle. The system software detects the removal of the
battery, and generates alerts.
4. Wait at least 30 seconds for all the alerts to generate.
5. Insert a new battery assembly.
The locking tab clicks into place when the battery assembly is fully inserted.
The battery alert is replaced by an INFO alert stating that the new battery is undergoing a rapid test.
6. Wait five minutes for the rapid battery test to conclude.
If the test concludes successfully, the INFO alert stops, the red Service LED turns off, and the node returns to read-
write mode.
Note: If the battery test does not complete successfully, remove the battery assembly and insert another
battery assembly.
7. Verify that the Charge LED is lit indicating that the new battery is charging.
It may take up to seven hours for the battery to fully charge. After the battery is fully charged, a full battery test is
automatically scheduled for the next day. The full battery test runs in the background and takes 60 hours to complete.
NVRAM battery assembly
12
©
2010 Isilon Systems, Inc.
Summary of Contents for IQ S Series
Page 1: ...Isilon IQ S Series Field Replacement Manual August 2010 120 0031 01 Rev C ...
Page 4: ...Chapter 11 Air baffle 39 Removing the air baffle 39 Installing the air baffle 40 ...
Page 8: ......
Page 18: ......
Page 22: ......
Page 26: ......
Page 36: ......
Page 42: ......
Page 44: ......