![iseg HPS 300 W series Operator'S Manual Download Page 29](http://html.mh-extra.com/html/iseg/hps-300-w-series/hps-300-w-series_operators-manual_2092522029.webp)
S p e z i a l e l e k t r o n i k G m b H
iseg Spezialelektronik GmbH
Email: [email protected]
Tel ++ 49 (0) 351 / 26 996 - 0
Bautzner Landstr. 23
http://www.iseg-hv.de
Fax ++ 49 (0) 351 / 26 996 - 21
D - 01454 Radeberg / Rossendorf
21
ModuleStatus (read access)
:READ:MODule:STATus?
Bit15
Bit14
Bit13
Bit12
Bit11
Bit10
Bit9
Bit8
isKILena
isTEMPgd
isSPLYgd
isMODgd
isEVNTact
isSFLPgd
isnoRAMP
isnoSERR
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
res
res
res
isSrvc
res
res
res
isADJ
The status bits as there are IsTemperatureGood, IsSupplyGood, IsModuleGood, IsEventActive, Is-
SafetyLoopGood, IsNoRamp and IsNoSumError indicate the single status for the complete module.
Bit
Name
Bit is 1
Bit is 0
isKILena
IsKillEnable
Module is in state Kill enable
Module is in state Kill disable
isTEMPgd
IsTemperatureGood
Module Temperature < 55 °C
Module temperature > 55°C
High voltage is turned off
isSPLYgd
IsSupplyGood
Power Supply is good
Power Supply is not good
isMODgd
IsModuleGood
Module status is good
Module status bad
isEVNTact
IsEventActive
At least one masked Event is active
No masked Event is active
isSFLPgd
IsSafetyLoopGood
Safety Loop is closed
Safety Loop is open
isnoRAMP
IsNoRamp
All channels stable, no ramp active.
At least one channel is ramping
isnoSERR
IsNoSumError
No sum error
Sum error active
isSrvc
IsServiceNeeded
Hardware failure detected:
consult manufacturer
No Hardware failure detected
isADJ
IsFineAdjustment
Adjustment is on
Adjustment is off
Res