Control Bit
Description, when the Bit is “0”
Description, when the Bit is “1”
Is Kill Enable
Module in state kill disable
Module in state kill enable
Is Temperature Good
if module temperature is higher than 55°C then
all channels are switched off permanently
module temperature is within working range
Is Supply Good
supply voltages are out of range
(range 24V +/-10% and 5V +/-5%)
supply voltages are within range
Is Module Good
module is not good, that means
(Is No Sum Error
AND
(Event Temperature Not Good
OR
Event Supply Not Good
OR
Event Safety Loop Not Good))==0
module is good, that means (Is No Sum Error
AND NOT
(Event Temperature Not Good
OR
Event Supply Not Good
OR
Event Safety Loop Not Good))==1
(see module event status also)
Is Event Active
no Event is active
any Event is active
Is Safety Loop Good
safety loop is broken - V
OUT
has been shut off
safety loop is closed
Is No Ramp
V
OUT
is ramping in at least one channel
no channel is ramping
Is No Sum Error
voltage limit, current limit, trip, voltage bound
or current bound has been exceeded in at least
one of the channels or external INHIBIT error,
reset by reset of the corresponding flag of the
‘Channel Status’
evaluation of the ‘
’ (chapter
9.1 Channel Status (read access))over all
channels to a sum error flag
“
I s V o l t a g e L i m i t
”&”
I s C u r r e n t L i m i t
”&”
I s
Cu r r e n t T r ip
”&”
I s E x t e r n a l I n h ib i t
”&”
I s
V o l t a g e B o u n d s
”&”
I s Cu r r e n t
B o u nd s
”=0 no errors
Is Hardware Voltage Limit
Good
hardware voltage limit not in proper range
hardware voltage limit in proper range
Is Fine Adjustment
Fine adjustment is off
Fine adjustment is on (default)