CAUTION 

If mounting the air conditioner to the enclosure door, confirm with the enclosure manufacturer that the 
door’s hinges will support the air conditioner’s added weight (see equipment specifications).  Insure 
that when the door is fully open that the enclosure will not topple over due to the off-center load.

 

 
Unit Specifications 
 

The following table provides electrical and refrigeration specifications for the HC201 Series Air 
Conditioners. 
 

 

HC201 Series 

 
 

Nominal Capacity Rating: 20,000 BTUH 

 

Standard Maximum Ambient: 131°F 

 

 

Model 

Operating 

Voltage 

Range 

 
 
 

(Volts) 

Inrush 

Current  

(Start 

Up 

Current) 

 

(Amps)

 

Loading 

Current 

(Running 

Current) 

 
 

(Amps) 

SCCR  

(Short 

Circuit 

Current 

Rating) 

 

(Amps) 

Recommended 

Circuit 

Protection 

 
 
 

(Amps) 

KVA 

Rating 

 
 
 

(K-

Watts) 

Refrigerant 

Type 

Refrigerant 

Amount 

 
 
 
 

(ounces) 

Low/High 

Unit  

Pressures 

 
 
 

(psi) 

Noise 

Level 

 
 
 
 

(dBA) 

Weight 

(Unit/Ship 

 
 
 
 

(lbs) 

ISC 

HC201236 

207-253 

51.50 

13.7 

*2 

25 Amp Class 

CC, CCMR Time 

Delay * 

3.1 

R407f 

42 

140 / 397 

n/a 

205/226 

ISC 

HC201486 

440-480 

24.68 

6.56 

160K 

12 Amp Class 

CC, CCMR Time 

Delay * 

3.1 

R407f 

42 

140 / 397 

n/a 

320/342 

 

* Time-delay Fuses with the following electrical characteristics are recommended.  Fast-acting fuses 
are not recommended. 

 

 

% of Ampere Rating 

Opening Time 

110 % 

15min Minimum 

125 % 

1hr Maximum 

200 % 

12sec Minimum 
4min Maximum 

 

*2

  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / 

enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.

 

 
 
 

 

Summary of Contents for HC201 Series

Page 1: ...User Technical Manual HC201 Series Rev 1 0...

Page 2: ...roprietary information comprising ISC Inc s trade secrets Please maintain the confidentiality of all proprietary information during and after the term of the use agreement Also please refrain from usi...

Page 3: ...onditioner 4 Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller...

Page 4: ...nt ISC air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect your equipment upon receipt...

Page 5: ...ry compressors without damaging the compressor If air conditioner is to be shipped or transported at any time pack in original packaging and strap to pallet to prevent damage Air conditioner must be k...

Page 6: ...In the event of excess water vapor where the enclosure door has been left open there is an overflow hole on the bottom of every unit Please contact ISC Inc if you encounter excess water coming from y...

Page 7: ...where the cold air can circulate across the width of the enclosure to cool it all the way across Once proper mounting placement is determined turn the enclosure equipment off if possible to prevent d...

Page 8: ...ltage Range Volts Inrush Current Start Up Current Amps Loading Current Running Current Amps SCCR Short Circuit Current Rating Amps Recommended Circuit Protection Amps KVA Rating K Watts Refrigerant Ty...

Page 9: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 0 9 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 10: ...um constant low current in the compressor motor during the non cooling state This option provides internal heat to the compressor to protect it from stalls and hard starts during long periods of compr...

Page 11: ...0 Watt 150 Watt 200 Watt 250 Watt 300 Watt 400 Watt 550 Watt 650 Watt 950 Watt Default Settings 55 F Heat Set Point 3 F Differential At the default settings the heater output turns on at 52 F and oper...

Page 12: ...t any specific location of your enclosure Ethernet IP Controller Output This option provides the ability to communicate with the ISC Air Conditioner controller via the Ethernet IP protocol You can mon...

Page 13: ...delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault may have...

Page 14: ...display its value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without...

Page 15: ...start up delay No Output 2 HA2 Condenser High Temperature Alarm P2 145 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Output 2 CA Evaporator Coil Alarm L...

Page 16: ...ray bottle is recommended to enhance air filter efficiency Replacement filters are readily available from ISC Customer Service DO NOT operate the air conditioner without the air filter Such operation...

Page 17: ...HC201 32008 1 Compressor HC201 31040 1 Compressor Thermal Overload Internal Gasket Installation Kit 71405 HC20 Evaporator Fan 41062 2 1 Condenser Fan 41060 2 1 Filter Media 44013 1 Capacitor HC201 54...

Page 18: ...n position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insufficient...

Page 19: ...se meter 3 Check for faulty evaporator fan 3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compressor the...

Page 20: ...ontroller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer to Ala...

Page 21: ...Dimensions 230 VAC Models Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed agains...

Page 22: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 0 22 P a g e 480 VAC Models...

Page 23: ...s com SP ENG 211 100 11 Rev 1 0 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics applies to all voltages optional accessories wiring not provided in this...

Page 24: ...lacement of its own product This Warranty does not cover Labor or reimbursement of labor for evaluation removal installation repair or cost of any warranted part except at the ISC factory in Dallas Te...

Page 25: ...nd contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available If suitable packing is not available arrange...

Reviews: