background image

                                                                                                      

 

 

4421 Tradition Trail ● Plano, Texas 75093 ● 972-964-2700 ● 800-836-7472  

URL:  

www.iscenclosurecooling.com

 ● Email:  

[email protected]

 

SP-ENG-211-100-11 Rev 1.0         

|

 

P a g e

                   

 

Run the air conditioner for 15 minutes; during this time the condenser fan will turn on after the 
condenser coil warms up. 

Note: Ambient Temperature must be at least 75°F.

 

 

Turn the unit off if the equipment makes any unexpected or hard mechanical noises or 
vibrations and refer to the troubleshooting guide in this manual. 

 

The supply cold air should be at least 10°F colder than the return air entering the unit.  If it is 
not, refer to the troubleshooting guide in this manual; 

 

When you are satisfied that the unit is operating properly, turn unit off, disconnect the power 
and mount the unit on the enclosure in accordance with the Mounting the Air Conditioner 
section in this manual. 

 
Mounting the Air Conditioner 
 

Using the template supplied, determine where the air conditioner is to be mounted and assure that all 
required cuts and holes will not interfere with or damage the enclosure or its contents.  Assure that 
there is a 3” clearance between walls / obstructions and the air conditioner for the condenser supply 
air and return air flow so that it is not restricted.  Restricted condenser air flow will affect the air 
conditioner’s performance.  Mount the air conditioner high on the enclosure in order to cool the hot air 
in the top of the enclosure.  Position the unit where the cold air can circulate across the width of the 
enclosure to cool it all the way across.  
 
Once proper mounting placement is determined, turn the enclosure equipment off, if possible, to 
prevent damage.  Drill and cut the holes as indicated on the mounting template.  Install insulation 
gasket as required to insure an air tight closed loop seal.  Be cautious not to let any cutting debris fall 
into the enclosure.  Attach the hanging bolts as indicated on the template to hold the unit onto the 
enclosure and then use the mounting screws that are provided. 
 
Hang the air conditioner on the hanging bolts and from inside the enclosure use the fasteners supplied 
to attach the air conditioner to the enclosure.  Insure that these fasteners are tight in order to prevent 
the unit from falling off the enclosure.   These fasteners should be checked periodically to insure that 
they have not become loose due to vibration. 
 
Ensure that the power supplied is compatible with the air conditioner’s power requirements.  Properly 
attach the unit’s power cord to a circuit that meets the equipment requirements and provide a circuit 
protection device based on the Unit Specifications section of this manual. 

 

After mounting the air conditioner, replace/close the enclosure door and start air conditioner; test for 
air leaks to assure a proper closed air loop seal and run test the unit to assure proper operation after 
mounting.  If any cold air leaks are found, check for proper mounting and apply silicone-free Lexel seal 
if leaks persist.  Assure that the air conditioner’s condenser inlet air filter is installed properly and 
cleaned regularly. 

 
 
 

Summary of Contents for HC201 Series

Page 1: ...User Technical Manual HC201 Series Rev 1 0...

Page 2: ...roprietary information comprising ISC Inc s trade secrets Please maintain the confidentiality of all proprietary information during and after the term of the use agreement Also please refrain from usi...

Page 3: ...onditioner 4 Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller...

Page 4: ...nt ISC air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect your equipment upon receipt...

Page 5: ...ry compressors without damaging the compressor If air conditioner is to be shipped or transported at any time pack in original packaging and strap to pallet to prevent damage Air conditioner must be k...

Page 6: ...In the event of excess water vapor where the enclosure door has been left open there is an overflow hole on the bottom of every unit Please contact ISC Inc if you encounter excess water coming from y...

Page 7: ...where the cold air can circulate across the width of the enclosure to cool it all the way across Once proper mounting placement is determined turn the enclosure equipment off if possible to prevent d...

Page 8: ...ltage Range Volts Inrush Current Start Up Current Amps Loading Current Running Current Amps SCCR Short Circuit Current Rating Amps Recommended Circuit Protection Amps KVA Rating K Watts Refrigerant Ty...

Page 9: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 0 9 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 10: ...um constant low current in the compressor motor during the non cooling state This option provides internal heat to the compressor to protect it from stalls and hard starts during long periods of compr...

Page 11: ...0 Watt 150 Watt 200 Watt 250 Watt 300 Watt 400 Watt 550 Watt 650 Watt 950 Watt Default Settings 55 F Heat Set Point 3 F Differential At the default settings the heater output turns on at 52 F and oper...

Page 12: ...t any specific location of your enclosure Ethernet IP Controller Output This option provides the ability to communicate with the ISC Air Conditioner controller via the Ethernet IP protocol You can mon...

Page 13: ...delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault may have...

Page 14: ...display its value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without...

Page 15: ...start up delay No Output 2 HA2 Condenser High Temperature Alarm P2 145 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Output 2 CA Evaporator Coil Alarm L...

Page 16: ...ray bottle is recommended to enhance air filter efficiency Replacement filters are readily available from ISC Customer Service DO NOT operate the air conditioner without the air filter Such operation...

Page 17: ...HC201 32008 1 Compressor HC201 31040 1 Compressor Thermal Overload Internal Gasket Installation Kit 71405 HC20 Evaporator Fan 41062 2 1 Condenser Fan 41060 2 1 Filter Media 44013 1 Capacitor HC201 54...

Page 18: ...n position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insufficient...

Page 19: ...se meter 3 Check for faulty evaporator fan 3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compressor the...

Page 20: ...ontroller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer to Ala...

Page 21: ...Dimensions 230 VAC Models Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed agains...

Page 22: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 0 22 P a g e 480 VAC Models...

Page 23: ...s com SP ENG 211 100 11 Rev 1 0 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics applies to all voltages optional accessories wiring not provided in this...

Page 24: ...lacement of its own product This Warranty does not cover Labor or reimbursement of labor for evaluation removal installation repair or cost of any warranted part except at the ISC factory in Dallas Te...

Page 25: ...nd contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available If suitable packing is not available arrange...

Reviews: