2.  INSTALLATION 

2.1 CHOOSING A LOCATION

 ON YOUR ENCLOSURE 

When  choosing  a  mounting  location  for  your  unit,  be  sure  to  keep  air  flows  of  both  the 

interior and exterior heatsinks and fans in mind.  Adequate clearance between the fans/heatsinks 

and nearby surfaces is required for unrestricted air flows which will ensure optimal performance 

and long, trouble free operation.  The general rule is to allow a minimum of two inches between 

the fans or heatsinks and any surface.  Refer to figure 1.1 for an air flow diagram.   

Other  considerations  in  deciding  on  a  mounting  location  include;  allowing  access  to 

thermostat (this will be inside the enclosure) if frequent adjustments are to be made; allowing 

access to the hot side heat sinks (this will be on the outside of the enclosure) for cleaning if the 

unit will be used in a harsh, dirty environment.    

2.2 ORIENTATION 

Your AC unit can be mounted either vertically on the front, rear or side of your enclosure or 

horizontally on the top of your enclosure.  See Figure 2.1 and 2.2. 

Vertically mounted 500 Btu units are always mounted with the exposed heatsink fins at the 

bottom  and  the  fans  at  the  top.  (Fig.  2.1)  Vertical  installations  often  require  the  use  of  a 

Condensate Drip Pan (part # DP-V) depending on a number of factors including internal enclosure 

temperatures  and  ambient  temperatures,  humidity  levels,  quality  of  enclosure  seals,  and 

frequency of enclosure opening.  

We strongly recommend the use of a drip pan to protect the 

electronics from dripping condensate.  

(Fig. 2.1)

 

Mounting the unit with the fins pointing to either side or straight up will cause condensate 

to drip in an uncontrolled manner, possibly damaging electronic equipment within the enclosure.  

If one of these orientations is the only possible configuration, contact the Engineering Dept. at ISC 

for a custom solution.   

Horizontally  mounted 

5

00  Btu  units

 

always  require  a  drip  pan  (part  #  DP-14

2H

)  to 

prevent dripping condensate from damaging electronic equipment.

  (Fig. 2.2)   

In either orientation, issues regarding access should be considered and minimum clearances 

must be maintained as outlined in Section 2.1 of this manual.  

 

 