OPERATION 

3.1  THERMOSTAT SET POINTS AND HEATING/COOLING UNITS 

SETTING THE THERMOSTAT 

 

Your  ISC  air  conditioner  is  equipped  with  an  adjustable  thermostat.  The  set  point  you 

choose should be based on the desired internal temperature of the enclosure.  The air conditioner 

will run until the set point temperature is achieved within the enclosure and then the hot side fans 

and the thermoelectric cooling modules will shut down.  The cold side fan will continue to run, 

circulating the air to maintain a uniform temperature within the enclosure. 
HEATING AND COOLING UNITS 

 

If you purchased an HC unit (heating and cooling), the heater operation is controlled by a 

fixed-point thermostat.  This thermostat is set to turn the heaters on when the temperature within 
the enclosure falls to approximately 45

°

 F and turn the heaters off when the temperature rises to 

approximately 55

°

 F.   

 

The  cooling  operation  is  controlled  by  the  adjustable  thermostat.  To  avoid  having  the 

heating and cooling on at the same time, do not set the cooling thermostat below 70

°

 F. 

 

3.2  MAINTENANCE 

MAINTENANCE 
          ISC  Thermoelectric  Air  Conditioners  are  virtually  maintenance-free.  The  only  time 

maintenance is required is when a unit is installed in an extremely dirty environment.  In these 

cases, the hot side heat sinks (outside the enclosure) should be inspected regularly for a build-up 

of dust or dirt.  If a build-up is present on the heat sink fins, it can be easily removed as follows: 

 

1.

 

Disconnect the power from the unit.   

2.

 

Dry  dust/dirt  can  be  removed  using  compressed  air  to  blow  out  the  heat  sinks.  Do  not 

direct any high-pressure air at the fans.   

3.

 

NEMA 4X models of our air conditioners are designed to allow for water wash down of the 

hot side of the unit, which is outside of the enclosure 

(never the cold side which is inside 

the enclosure).

 

 A pressure washer can be used to carefully clean the hot side heat sink 

fins.  Never  direct  high-pressure  water  at  the  fans  or  the  joint  formed  by  the  mounting 

flange, gasket and enclosure.  Never allow the cold side of your unit to get wet.  Always 

check your serial label before proceeding with a water wash down. 

 

Keeping the hot side heat sink fins free from any insulating build-up of dirt or dust will ensure 

long, trouble-free operation of your air conditioner. 

 

   

NEVER  EXPOSE  THE  COLD  SIDE  OF  ANY  AIR  CONDITIONER  (INSIDE  THE  ENCLOSURE)  TO 

WATER.

 

 

If you have any questions about any aspect of your ISC air conditioner, don’t hesitate to call us at 

the numbers listed below.

 