iSC2F User’s Manual
UM-iSC2F-2-EN.docx
Pages 2 of 12
1.2
Operating Modes
1.3
Configuring the Device
The ISC2F can be configured using the Mode DIP switch located on the right side off
the enclosure. Use the DIP switch to change the operating mode of the ISC2F.
The configuration settings are as follows:
Switch
ON
OFF
1
RS232 to fiber
RS485/422 to fiber
2
RS232-to-RS485/422
conversion enabled
RS232-to-RS485/422
conversion disabled
3
Full-duplex
Half-duplex (RS485
only)
4
120
Ω
terminations
enabled
No 120
Ω
termination
5
Fiber repeater
enabled
Fiber repeater
disabled
6
1200 – 2400 baud
n/a
7
4800 – 9600 baud
n/a
8
14400 – 19200 baud
n/a
9
28800 – 38400 baud
n/a
10
57600 – 115200
baud
n/a