iSC2F User’s Manual
UM-iSC2F-2-EN.docx
Pages 4 of 12
Baud Rate (bps)
DIP6
DIP7
DIP8
DIP9
DIP10
1200 – 2400
ON
OFF
OFF
OFF
OFF
4800 – 9600
OFF
ON
OFF
OFF
OFF
14400 – 19200
OFF
OFF
ON
OFF
OFF
28800 – 38400
OFF
OFF
OFF
ON
OFF
57600 – 115200
OFF
OFF
OFF
OFF
ON
Fiber Repeater Mode
When a distance that is more than 5 km (3.1 mi) has to be supported, iSC2F must be used in
Fiber Repeater mode. This mode supports extended distance between serial devices.
1.
RS232 device
2.
iSC2F
3.
RS485 Device/ Network
Position
State
Notes
1
OFF
RS232 to fiber
2
OFF
RS232-to-RS485/422 conversion
3
OFF
Full-duplex
4
OFF
No 120 Ohm termination
5
ON
Fiber repeater
6
OFF
1200 – 2400 baud
7
OFF
4800 – 9600 baud
8
OFF
14400 – 19200 baud
9
OFF
28800 – 38400 baud
10
OFF
57600 – 115200 baud
The repeat function will optically re-transmit any data received on the optical receiver, in
addition to any connected serial devices. As a result, any data transmitted from the master,
will be re-transmitted optically to the slave. In this case, the distance between master and
slave can be extended over the 5 km (3.1 mi).
This topology can be used for RS232, RS485 or RS422. In all cases, all repeater devices should
have the repeat function—DIP position 5 ON.