100/1000Base-X SFP Port
Indicator
Green for port Link/Act.
Fault contact
Relay
Relay output to carry capacity of 1 A at 24 VDC.
Power
Redundant power input modular
Dual DC inputs 10-48VDC, Dual DC 36-72VDC, and Dual AC/DC power inputs. 85-264VAC / 88-
370VDC.
Power consumption
18 Watts
Overload current protection
Present
Installation Category
Present
Physical Characteristic
Enclosure
DIN Rail made from galvanized steel
Dimension (W x D x H)
5 x 6.44 x 6.07 inch
Environmental
Storage Temperature
-40oC to 85oC (-40oF to 18 5oF)
Operating Temperature
-40oC to 85oC (-40oF to 18 5oF)
Operating Humidity
5% to 95% Non-condensing
Regulatory approvals
Electric utility
IEC 61850-3 Ed. 2 (2013), IEEE 1613
EMI
FCC Part 15, CISPR (EN550 22) class A, EN5 015 5 (EN50121-3-2 , EN5 5011, EN50121-4)
EMC
EN610 00-4-2 (ESD)
EN610 00-4-3 (RS),
EN610 00-4-4 (EFT), EN610 00-4-5 ( Surge), EN610 00-4-6 (CS),
EN610 00-4-8,
EN610 00-4-11
Mechanical
IEC 60255-21-1 (Vibration, 2g, 10-150Hz)
IEC 60255-21-2 (Shock 30g, Bump 20G)
IEC 60255-21-3 (Seismic, 2g, 7.5mm)
Shock
IEC60068-2-27
Free Fall
IEC60068-2-32
Vibration
IEC60068-2-6
Safety
EN60950-1
Warranty
Warranty