4.2.5 Checking status (CHK)
Checking status setting interface
Power up again after power off in fault mode, the UPS enters checking status (CHK). Judge if keep bypass output and
forbid turning on the UPS according to the fault information. It is not allowed to turn on the UPS until failure is solved and
manually close CHK.
Press and hold the menu settings button
more than 2 seconds to enter the setting interface. Press inquiry button
or
more than half a second and less than 2 seconds to select the function options. After selecting CHK setting interface,
CHK will flash.
Press the menu settings button
more than half a second and less than 2 seconds to enter the CHK setting interface,
at this moment CHK is illuminated, and ON under the CHK flashes. Press inquiry button
or
more than half a
second and less than 2 seconds and select OFF, at this moment OFF flashes.
After selecting OFF, press the menu settings button
more than half a second and less than 2 seconds, CHK Enable is
confirmed, at this moment OFF uner the CHK is illuminated and stop flashing.
Press and hold the menu settings button
more than 2 seconds to exit the setting interface and return to the home
screen displaying UPS output information.
Power up again after power off, the UPS enter normal mode.
Note:
The menu setting interface will not have CHK option until failure, there is no CHK option when the UPS is
normal.