4.2.2 Configure the end of discharge point
(
EOd
)
end of discharge poin setting interface
Press and hold the menu settings button
more than 2 seconds to enter the setting interface. Press inquiry button
or
more than half a second and less than 2 seconds to select the function options. After selecting the EOd setting
interface, EOd will flash.
Press the menu settings button
more than half a second and less than 2 seconds to enter the EOd setting interface,
at this moment EOd is illuminated, and the value under the EOd flashes. Press inquiry button
or
more than half a
second and less than 2 seconds to select the Eod value needed. There are dEF, 9.8V, 9.9V, 10V, 10.2V and 10.5V
available for options. EOd is dEF by default (Eod varies with load). The configured settings can be saved in real time.
After selecting the vaule, press the menu settings button
more than half a second and less than 2 seconds, EOd
setup is confirmed, at this moment the selected value is illuminated and stop flashing.
Press and hold the menu settings button
more than 2 seconds to exit the setting interface and return to the home
screen.
Note:
The low voltage alarm point of each battery is (Eod + 1V) (Battery low voltage shutdown point +
1V)×Numbers of battery.