For standard model UPS, each UPS has inbuilt battery group; for long time model UPS, it needs to equip separated
external battery group.
Verify all connection after parallel installation is completed. Operate the parallel UPS after confirming correct.
In the condition of each single UPS running, set the physical address (ID) of each UPS, and ensure that each ID is
different.
In the condition of each single UPS running, set the output voltage (OPU) of each UPS, and ensure that each OPU is
same.
Verify if the parallel cables of all UPS are connected firmly, perform startup and finish parallel installation.