SECTION IV
Maintenance
Page 4.5
BP+2.9X
11/95
4.5 Fuses
There are four (4) fuses adjacent to the UPS CONTROL switch inside the
front door. If one of these fuses is blown, the control logic will not become energized
at startup. Once the UPS is started, it will operate even though one or more of the
fuses is blown.
In case a fuse blows, replace it with a fuse of the same make and size.
These are the only fuses available to the user unless he or she has had
authorized factory training.
4.6 Battery Maintenance
4.6.1
Safety Precautions
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
When replacing batteries, use the same number and the following type of
batteries: sealed lead acid.
All batteries in a cabinet should be from the same
manufacturer and of the same part number.
CAUTION:
Do not dispose of battery or batteries in a fire. The battery
may explode.
CAUTION:
Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic.
CAUTION:
A battery can present a risk of electrical shock and high short circuit
current. The following precautions should be observed when working
on batteries:
1.
Remove watches, rings or other metal objects.
2.
Use tools with insulated handles.