SECTION III
Operation
Page 3.29
BP+2.9X
11/95
3.6 UPS Operating Procedures (continued)
3.6.3
UPS Maintenance Menu (continued)
3.6.3.2
Inverter Maintenance Menu (continued)
8. Press
to return to the Inverter
Maintenance Menu.
3.6.3.3
SBS Maintenance Menu
1. Press to advance to the SBS
Maintenance Menu.
Bypass/Shutdown Procedure
2. Press
to obtain this screen. Press ^
to begin the Bypass/Shutdown Procedure.
Retransfers are disabled by this procedure.
To Skip Bypass/Shutdown procedure
and go directly to Manual Transfer to Bypass
(Step 12) press instead of
.
3. Press
to continue the Bypass
Shutdown procedure.
Warning:
Bypass/Shutdown procedure may
not be exited without performing all
steps in the order shown.
4. When this message appears, close the
BYPASS CIRCUIT BREAKER.
Inverter
Maintenance
Menu
SBS
Maintenance
Menu
Bypass/Shutdown UPS
UP=Bypass
Confirm
Yes=UP No=DN
Menu
Close
Bypass
Breaker