switching point
with release position
programmed parameters:
SP.1:
100.0°C
rP.1:
40.0°C
An increasing temperature up to SP.1 (e.g. 100°C), switches the output according to the
adjusted switching function (no or nc). This state remains also for higher temperatures.
For decreasing temperatures the switching state changes with the temperature value at
rP.1 (e.g. 40°C). If SP.1 will be changed, rP.1 remains the same.
The minimum range between SP1 and rSP.1 is 1% of the maximum temperature.
switching point with hysteresis
programmed parameters:
SP.1:
50.0°C
HYS.1:
3
0.0°C
An increasing temperature up to SP.1 (e.g. 50°C) switches the output according to the ad-
justed switching function (no or nc). This state remains also for higher temperatures.
For decreasing temperatures the switching state changes after passing the hysteresis (e.g.
30°C). If SP.1 will be changed, the hysteresis HYS1 remains the same, that means the re-
lease position is (SP.1 – 20°C).
temperature [°C]
switching point
release position
switching point
temperature [°C]
s
w
it
c
hi
ng poi
nt
s
w
it
c
hi
ng poi
nt
hysteresis HYS1
100
MANUAL • Subject to alteration! Version:
June 2017
ipf electronic gmbh • Rosmarter Allee 14 • 58762 Altena
│
Tel +49 2351 9365-0 • Fax +49 2351 9365-19
│
[email protected] • www.ipf-electronic.com
9