operating modes 

RUN-Mode 

Normal operating mode 
At power on the unit is in the RUN-mode. It carries out its measurement and evaluation 
functions and provides output signals according to the set parameters. 
The display shows the current system temperature. The red LEDs indicate the switching 
state of the outputs. 

display mode 

Display and adjustment of the switch-points, release positions and of the hysteresis. 
When the 

Enter/Set

 button is pressed briefly, the main menu opens. The internal sens-

ing, processing and output functions of the unit continue as if in RUN-mode.  The pa-
rameter values can be read and adjusted. 
Pressing the arrow key „downwards“ briefly, scrolls through the adjustable parameters. 
Pressing the 

Enter/Set

 button briefly, shows the adjusted parameter value. 

Pressing the arrow key „downwards“ or „upwards“ briefly, changes the parameter value 
step by step. Pressing the arrow key continuous changes the value fast. 
Pressing the 

Enter/Set

 button safes the adjusted value, the display blinks three times. 

The unit now operates with the „new adjusted“ value. 

Returning to the RUN-Mode: Press the 

ESC 

button. 

Enhanced menu / programmimg mode 

Setting of the parameter values and programming the main functions. 
The unit changes to the programming mode if „EF“ is set in the main menu and the 

En-

ter/

Set button is pressed for at least 5sec

.

 

The internal sensing, processing and output functions of the unit continue as if in RUN-
mode. 

Pressing the arrow key „downwards“briefly, scrolls through the adjustable parameters. 
Pressing the 

Enter/Set

 button briefly, indicates the adjusted parameter value 

Pressing the arrow key „downwards“ or „upwards“ briefly, changes the parameter value 
step by step. Pressing the arrow key continuous changes the value fast. 
Pressing the 

Enter/Set

 button safes the adjusted value, the Display blinks three times. 

The unit now operates with the „new adjusted“ value. 

Returning to the RUN-Mode: Press the 

ESC 

button several times. 

MANUAL • Subject to alteration! Version: 

June 2017

 

ipf electronic gmbh • Rosmarter Allee 14 • 58762 Altena 

 Tel +49 2351 9365-0 • Fax +49 2351 9365-19 

 [email protected] • www.ipf-electronic.com 

11

Summary of Contents for YT353120

Page 1: ...temperature monitor MANUAL Subject to alteration Version June 2017 ipf electronic gmbh Rosmarter Allee 14 58762 Altena Tel 49 2351 9365 0 Fax 49 2351 9365 19 info ipf electronic com www ipf electroni...

Page 2: ...oint page 10 window function with hysteresis page 10 operating modes page 11 programming page 12 list of parameters page 12 mounting and electrical connection page 15 connection of the PT100 sensors p...

Page 3: ...cal data can lead to personal injury and or damage to property In all applications check compliance of the product materials Never use these devices in applications where the safety of a per son depen...

Page 4: ...on of menu and parameters setting and saving of parameters Enter Set Enter Set 5 arrow key up setting the parameter values increasing the value fast keep the button pressed 6 arrow key down setting th...

Page 5: ...u the indication will be shown on the display program button Enter Set symbol Enter Set Enter Set Selection of menus and submenus as well as confirming and saving of parameter values Short pressing in...

Page 6: ...ock If the device is in the RUN Mode and you press the arrow keys at the same time for at least 5 seconds the keyboard lock will be activated The display shows sLOC blinking 3 times Now the adjusted s...

Page 7: ...2 level MANUAL Subject to alteration Version June 2017 ipf electronic gmbh Rosmarter Allee 14 58762 Altena Tel 49 2351 9365 0 Fax 49 2351 9365 19 info ipf electronic com www ipf electronic com 7...

Page 8: ...tween the switching outputs SP 1 and rSP 1 is 1 of the temperature range stated by the system The smallest adjustable hysteresis is 1 of the temperature range stated by the system All examples are eff...

Page 9: ...ameters SP 1 50 0 C HYS 1 30 0 C An increasing temperature up to SP 1 e g 50 C switches the output according to the ad justed switching function no or nc This state remains also for higher temperature...

Page 10: ...s rP 1 will remain the same windowfunction with hysteresis programmed parameters SP 1 50 0 C HYS 1 30 0 C If the temperature hits the adjusted window between SP 1 HYS 1 and SP 1 50 C the output switch...

Page 11: ...e adjusted value the display blinks three times The unit now operates with the new adjusted value Returning to the RUN Mode Press the ESC button Enhanced menu programmimg mode Setting of the parameter...

Page 12: ...e with the arrow keys Confirm the setted value with the Enter Set button 1X rP1 HYS1 Press the Enter Set button The current value for the release point S1 respectively the hysteresis will be displayed...

Page 13: ...if in Ou 1 a switching function is set off delay timer function S1 Ou 2 Configuration Output 2 4 switching functions the error signal or 4 analog functions SP HY switch point hysteresis SP rP switch p...

Page 14: ...a switching function is set on delay timer function S2 dr 2 ds 2 is active if in Ou 2 a switching function is set off delay timer function S2 HI saving the max temperature value of the system The hig...

Page 15: ...no AY000060 After mounting the sensor mechanically the control panel can be rotated by 350 to align it for the machine operator The unit must be connected by a suitably qualified electrician The natio...

Page 16: ...K030F25 with the temperature monitor For PT100 sensors with a fixed cable use a M12 connector e g VK003028 Depending on the version the connection pins must be bridged as you see below 2 wire 3 wire 4...

Page 17: ...nal check wiring check load ERR sensor defect internal error S1 and S2 are switched off analog output error signal contact manufacturer AO If current output is selected analog output open If voltage o...

Page 18: ...4mA adjustable start and end point burden max RL W Ub 8V 20mA error recognition analog output in case of line break current or short circuit voltage from 1V rise time 5msec 10 90 of PN damping 0 to 20...

Page 19: ...y optical interface connection USB software AD000011 accessory mounting clip M12 socket Revised version 01 02 2010 internal software 4 13 cycle counter for SP1 Revised version 10 02 2016 analog output...

Reviews: