factory settings
OU 1
SP.rP
OU 2
4 - 20
SP 1
130°C
rP 1
-17.3°C
SP 2
215°C
rP 2
-17.3°C
technical data
temperature range [°C]
see list of articles
temperature detection
resistance thermometer PT100 (2-, 3-, or 4-wire)
operating voltage
12 to 32V DC, reverse polarity protection
voltage drop
< 2V
current consumption
< 60mA
switching outputs
2 x pnp-switching, no/nc 1A short-circuit protection
time delay
0 to 20sec, adjustable
switch-point adjustment range
1 to 100% of the accumulated value
release position
0 to 99% of the accumulated value
switching frequency
max. 125Hz
repeatability
< ±0,1% of accumulated value
current output
0/4 to 20mA, 20 ... 0/4mA
,
adjustable start and end point
burden
max. RL [W]=(Ub-8V) / 20mA
error recognition
analog output in case of line break
(current) or short-circuit (voltage, from 1V)
rise time
5msec (10% ... 90% of PN)
damping
0 to 20sec, adjustable
linearity deviation
max. ±0.25% of PN
system temperature display
4 x 7 segment LED-Display
switching function display
2x LED red
operating temperature
-20°C to +80°C
connection of the PT100
M12-cable socket, 4-pin, with rotatable coupler
housing material
PA6.6, polyester
system of protection
IP65 to EN 60529
electrical connection
M12 connector 4-pin
optical interface
9600 Baud, via optical adapter at USB-Port
MANUAL • Subject to alteration! Version:
June 2017
ipf electronic gmbh • Rosmarter Allee 14 • 58762 Altena
│
Tel +49 2351 9365-0 • Fax +49 2351 9365-19
│
[email protected] • www.ipf-electronic.com