IP Enclosures IP-ACIRM100 User Manual Download Page 14

Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 14/20

 

UMA-CDZ-IP-ACIRM100-00

 

dP3

  

Third probe display

- no available 

.

dP4

  

Fourth probe display

- no available 

 

 
4.2.11 DIGITAL INPUT (ENABLED WITH P3P = N) 

 
The free voltage digital input is programmable in different configurations by the “i1F” 
parameter. 
 

Door switch input (i1f = dor) 
 

It signals the door status and the corresponding relay output status through the 

odc

 

parameter:  

no

= normal (any change);, 

Fan= 

fan OFF; 

CPr

= Compressor OFF, 

F_C

= Compressor and 

fan OFF. 
Since the door is opened, after the delay time set through parameter 

did

, the door alarm is 

enabled, the display shows the message 

dA

 and the regulation restarts is 

rtr = yES

. The 

alarm stops as soon as the external digital input is disabled again. With the door open, the 
high and low temperature alarms are disabled. 
 

Digital inputs polarity 
 

The digital input polarity depends on the 

i1P

 parameter. 

i1P=CL

: the input is activated by closing the contact. 

i1P=OP

: the input is activated by opening the contact 

 
 

4.2.12 GENERIC ALARM (i1F = EAL) 
 

As soon as the alarm input is activated (for example enclosure temperature higher than 
ALU value) the unit will wait for 

did

 time delay before signalling the 

EAL

 alarm message. 

The outputs status doesn’t change. The alarm stops just after the alarm input is de-
activated. 
 

4.3.13 SERIOUS ALARM MODE (i1F = bAL) 
 

When the alarm input is activated (for example enclosure temperature higher than ALU 
value), the unit will wait for 

did

 delay before signalling the 

CA 

alarm message. The relay 

outputs are switched OFF. The alarm will stop as soon as the alarm input is de-activated. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for IP-ACIRM100

Page 1: ...00 00 USER S MANUAL PART 2 ROOF MOUNT AIR CONDITIONER FOR ELECTRICAL ENCLOSURE INDOOR APPLICATION IP ACIRM100 Document UMA CDZ IP ACIRM100 00 Date Name Description Original user s manual for air condi...

Page 2: ...closure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary we...

Page 3: ...ES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 1000 1060 A35 A50 W 760 790 Absorbed electric power EN14511 A35 A35 W 780 810 A35 A50 W 890 930 Rated current A 5 1 6 2 Moto...

Page 4: ...Electrical enclosure must be sized according to air conditioner dimensions and weight Electrical enclosure must have at least IP54 protection degree Internal and external components of electrical encl...

Page 5: ...hole on the enclosure as is shown in the drilling template VIEW FROM EXTERNAL OF ELECTRICAL ENCLOSURE Deburr all sharp edges to avoid accidental injuries 2 Apply the gasket included in fixing kit on t...

Page 6: ...ipes in order to ensure proper drainage in case of occlusion of a drain pipe Air conditioner produces condensate because the moist air inside of the enclosure meets cold heat exchanger evaporator and...

Page 7: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 7 20 UMA CDZ IP ACIRM100 00 3 ELECTRICAL CONNECTION 3 1 WIRING DIAGRAM...

Page 8: ...andard Before the installation make sure that the cabinet is disconnected from the electrical supply Wire male plug included with an adequate cable as is shown by following picture Cable section must...

Page 9: ...larm output is activated according to alarm parameters for example in case of enclosure temperature higher than ALU value digital input not activated See PARAMETERS at 4 2 DIGITAL THERMOSTAT INSTRUCTI...

Page 10: ...lled only on the roof of electrical enclosure After finishing assembly of the conditioner wait approx 30 min before starting it the oil must collect in the compressor to ensure lubrication and cooling...

Page 11: ...ions for parameter changing To display target set point in programming mode it selects a parameter or confirm an operation DEF To start a manual defrost To see the max stored temperature in programmin...

Page 12: ...SET key or wait for 5 seconds to display the probe value again 4 2 5 HOW TO CHANGE THE SETPOINT 1 Push the SET key for more than 2 seconds to change the Set point value 2 The value of the set point w...

Page 13: ...defrost cycles 0 120h Determines the time interval between the beginning of two defrost cycles MdF Maximum length for defrost 0 255min 0 no defrost When P2P n not evaporator probe timed defrost it set...

Page 14: ...as the external digital input is disabled again With the door open the high and low temperature alarms are disabled Digital inputs polarity The digital input polarity depends on the i1P parameter i1P...

Page 15: ...Ht heating cL Pr1 rES Resolution in integer dE dec point dE Pr1 IdF Interval between defrost cycles 1 120 hours 8 Pr1 MdF Maximum length for defrost 0 255 min 0 Pr1 ALU MAXIMUM temperature alarm Set...

Page 16: ...ESCRIPTION CODE 1 Evaporator fan VCENT190D230V 2 Compressor COMPRSC12G 3 Condenser fan VCENT220D230U C1 Evaporator fan capacitor CON2UFS2M8F C3 Condenser fan capacitor CON2UFS2M8F 4 Regulating thermos...

Page 17: ...oling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This w...

Page 18: ...UE LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 4...

Page 19: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 19 20 UMA CDZ IP ACIRM100 00 SAA CERTIFICATE...

Page 20: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 20 20 UMA CDZ IP ACIRM100 00 NOTES...

Reviews: