IP Enclosures IP-ACIRM100 User Manual Download Page 13

Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 13/20

 

UMA-CDZ-IP-ACIRM100-00

 

4.2.8  HOW TO UNLOCK THE KEYBOARD 
 

Keep pressed together for more than 3s the 

 + 

 keys, till the 

Pon

 message will be 

displayed. 

 
4.2.9  THE ON/OFF FUNCTION 
 

With 

onF = oFF

, pushing the 

ON/OFF

 key, the instrument is switched off. The 

OFF

 message is displayed. In this configuration, the regulation is disabled. 

To switch the instrument on, push again the 

ON/OFF

 key. 

WARNING:

 Loads connected to the normally closed contacts of the relays are always 

supplied and under voltage, even if the instrument is in standby mode. 
 
 

4.2.10 PARAMETERS 
 
Regulation 
 
Hy   Differentia

l: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. 

Compressor 
Cut IN is Set Point + differential (Hy). Compressor Cut OUT is when the 
temperature reaches the set point. 

Ot

  

Thermostat probe calibration

: (-12.0÷12.0°C; -120÷120°F) allows to adjust 

possible offset of the thermostat probe. 

AC

  

Anti-short cycle delay

: (0÷50 min) minimum interval between the compressor stop 

and the following restart. 

CH

  

Type of action

: CL = cooling; Ht = heating. 

rES

  

Resolution (for °C):

 (in = 1°C; dE = 0.1 °C) allows decimal point display. 

dLy Display delay: (0 ÷20.0m; risul. 10s) when the temperature increases, the 
display is updated of 1 °C/1°F after this time. 

IdF

  

Interval between defrost cycles

: (0÷120h) Determines the time interval between 

the beginning of two defrost cycles. 

MdF   (Maximum) length for defrost

: (0÷255min) (0=no defrost) When P2P = n, (not 

evaporator probe: timed defrost) it sets the defrost duration, when P2P = y (defrost 
end based on temperature) it sets the maximum length for defrost. 

ALU

  

MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this temperature 

is reached the alarm is enabled, after the “ALd” delay time. 

ALL

  

Minimum temperature alarm

: (-50.0 ÷ SET°C; -58÷230°F when this temperature is 

reached the alarm is enabled, after the “ALd” delay time. 

i1P

  

Digital input polarity

: oP: the digital input is activated by opening the contact; CL: 

the digital input is activated by closing the contact. 

i1F

  

Digital input configuration

: EAL = external alarm: “EA” message is displayed;  

bAL = serious alarm “CA” message is displayed. PAL = pressure switch alarm, “CA” 
message is displayed; dor = door switch function; dEF = activation of a defrost 
cycle; AUS =to switch on the second relay if oA1 = AUS; Htr = kind of action 
inversion (cooling –heating); FAn = not set it; ES = Energy saving. 

did 

(0 ÷ 255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between 
the 
detection of the external alarm condition and its signalling. 
with i1F= dor: door open signalling delay 
with i1F = PAL: time for pressure switch function: time interval to calculate the 
number of the pressure switch activation. 

PbC

  

Type of probe

: it allows to set the kind of probe used by the instrument: PbC = 

PBC probe, ntc = NTC probe. 

Summary of Contents for IP-ACIRM100

Page 1: ...00 00 USER S MANUAL PART 2 ROOF MOUNT AIR CONDITIONER FOR ELECTRICAL ENCLOSURE INDOOR APPLICATION IP ACIRM100 Document UMA CDZ IP ACIRM100 00 Date Name Description Original user s manual for air condi...

Page 2: ...closure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary we...

Page 3: ...ES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 1000 1060 A35 A50 W 760 790 Absorbed electric power EN14511 A35 A35 W 780 810 A35 A50 W 890 930 Rated current A 5 1 6 2 Moto...

Page 4: ...Electrical enclosure must be sized according to air conditioner dimensions and weight Electrical enclosure must have at least IP54 protection degree Internal and external components of electrical encl...

Page 5: ...hole on the enclosure as is shown in the drilling template VIEW FROM EXTERNAL OF ELECTRICAL ENCLOSURE Deburr all sharp edges to avoid accidental injuries 2 Apply the gasket included in fixing kit on t...

Page 6: ...ipes in order to ensure proper drainage in case of occlusion of a drain pipe Air conditioner produces condensate because the moist air inside of the enclosure meets cold heat exchanger evaporator and...

Page 7: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 7 20 UMA CDZ IP ACIRM100 00 3 ELECTRICAL CONNECTION 3 1 WIRING DIAGRAM...

Page 8: ...andard Before the installation make sure that the cabinet is disconnected from the electrical supply Wire male plug included with an adequate cable as is shown by following picture Cable section must...

Page 9: ...larm output is activated according to alarm parameters for example in case of enclosure temperature higher than ALU value digital input not activated See PARAMETERS at 4 2 DIGITAL THERMOSTAT INSTRUCTI...

Page 10: ...lled only on the roof of electrical enclosure After finishing assembly of the conditioner wait approx 30 min before starting it the oil must collect in the compressor to ensure lubrication and cooling...

Page 11: ...ions for parameter changing To display target set point in programming mode it selects a parameter or confirm an operation DEF To start a manual defrost To see the max stored temperature in programmin...

Page 12: ...SET key or wait for 5 seconds to display the probe value again 4 2 5 HOW TO CHANGE THE SETPOINT 1 Push the SET key for more than 2 seconds to change the Set point value 2 The value of the set point w...

Page 13: ...defrost cycles 0 120h Determines the time interval between the beginning of two defrost cycles MdF Maximum length for defrost 0 255min 0 no defrost When P2P n not evaporator probe timed defrost it set...

Page 14: ...as the external digital input is disabled again With the door open the high and low temperature alarms are disabled Digital inputs polarity The digital input polarity depends on the i1P parameter i1P...

Page 15: ...Ht heating cL Pr1 rES Resolution in integer dE dec point dE Pr1 IdF Interval between defrost cycles 1 120 hours 8 Pr1 MdF Maximum length for defrost 0 255 min 0 Pr1 ALU MAXIMUM temperature alarm Set...

Page 16: ...ESCRIPTION CODE 1 Evaporator fan VCENT190D230V 2 Compressor COMPRSC12G 3 Condenser fan VCENT220D230U C1 Evaporator fan capacitor CON2UFS2M8F C3 Condenser fan capacitor CON2UFS2M8F 4 Regulating thermos...

Page 17: ...oling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This w...

Page 18: ...UE LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 4...

Page 19: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 19 20 UMA CDZ IP ACIRM100 00 SAA CERTIFICATE...

Page 20: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 20 20 UMA CDZ IP ACIRM100 00 NOTES...

Reviews: