TEST, CHECK AND STARTUP:
10. Repeat the same step for zone 2 and zone
3. LED status should be the same with the
exception that ZD2 light for the zone 2
thermostat cooling test and ZD3 LED will light
for the zone 3 thermostat test.
11. The same test can be done for a heating call
from each zone.
12. Once testing is confirmed, place zone
thermostats in their proper mode of operation.
ZP3-HPS-ESP SPECIFICATIONS:
Enclosure:
Aluminum
Panel Dimensions:
Height: 8.0”
Width: 6.0”
Depth 2.25”
PC Board Mounting:
Individual Snap Track mounted to enclosure base
Operating Temperature Rating:
-40° F to 150° F
Operating Humidity:
5% to 90% RH non-condensing
Wiring:
18-gauge wire for all equipment and component
connections.
Time Delays:
3 minutes off between heating and cooling calls.
3 minutes off on high or low limit
20 minute time share
Purge ON = 1 minute
Thermostats:
Single or multi-stage heat pump
Programmable or non-programmable
Auto or manual changeover
Sensors:
iO-ZP3-DAS Discharge Air Sensor
NTC Type 3, 10K @ 77° F, +/- 3% @ 77° F
Ω
iO-ZP3-OT Outdoor Sensor
NTC Type 3, 10K @ 77° F, +/- 3% @ 77° F
Ω
FIELD WIRING TERMINALS:
Zone Thermostats:
C
24Vac (Common)
R
24Vac (Hot)
W
Auxiliary or Emergency Heat
Y1
First Stage Compressor
Y2
Second Stage Compressor
G
Fan
O/B Reversing Valve
HVAC Equipment:
R
24Vac Equipment Hot
W
Auxiliary or Emergency Heat
Y1
First Stage Compressor
Y2
Second Stage Compressor
G
Fan
O/B Reversing Valve
High / Low Limit
DA
Land to ZPA-DTS
DA Land to ZPA-DTS
Outdoor Temperature Sensor
OT
Land to ZPA-OTS
OT
Land to ZPA-OTS
Panel Power:
C
24Vac (Common)
R
24Vac (Hot)
Damper Outputs
PC
Power Close
C
Common
PO
Power Open
Pressure Sensor:
2
Land to ZPA-SPS
3
Land to ZPA-SPS
7