Communication Protocol
116
10.7.3 RTU mode, write 5000(1388H) into address 0008H, slave node address 02.
The request command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
Node address
02H
Command 06H
High byte of data address
00H
Low byte of data address
08H
High byte of write content
13H
Low byte of write content
88H
Low byte of CRC
05H
High byte of CRC
6DH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
The reply command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
Node address
02H
Command 06H
High byte of data address
00H
Low byte of data address
08H
High byte of write content
13H
Low byte of write content
88H
Low byte of CRC
05H
High byte of CRC
6DH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)