List of Function Parameters
98
Function
Code
Name
Description
Factory
Setting
Modify
Serial
No.
PB.00
Motor overload
protection
0: Disabled
1: Normal motor
2: Variable frequency motor
2
134
PB.01
Motor overload
protection current
20.0%~120.0%
100.0%
O
135
PB.02
Threshold of trip-free 70.0~110.0%
80.0%
O
136
PB.03
Decrease rate of
trip-free
0.00Hz~P0.04
0.00Hz
O
137
PB.04
Over-voltage stall
protection
0: Disabled
1: Enabled
0
O
138
PB.05
Over-voltage stall
protection point
110~150%
Depend
on model
O
139
PB.06
Auto current limiting
threshold
50~200%
G:160%
P:120%
O
140
PB.07
Frequency decrease
rate when current
limiting
0.00~100.00Hz/s
10.00
Hz/s
O
141
PC Group: Serial Communication
PC.00
Local address
0~247
1
O
142
PC.01
Baud rate selection
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
4
O
143
PC.02
Data format
0: RTU, 1 start bit, 8 data bits, no parity
check, 1 stop bit.
1: RTU, 1 start bit, 8 data bits, even parity
check, 1 stop bit.
2: RTU, 1 start bit, 8 data bits, odd parity
check, 1 stop bit.
3: RTU, 1 start bit, 8 data bits, no parity
check, 2 stop bits.
4: RTU, 1 start bit, 8 data bits, even parity
check, 2 stop bits.
5: RTU, 1 start bit, 8 data bits, odd parity
check, 2 stop bits.
6: ASCII, 1 start bit, 7 data bits, no parity
check, 1 stop bit.
7: ASCII, 1 start bit, 7 data bits, even parity
check, 1 stop bit.
0
O
144
Summary of Contents for CHE100-004G-2
Page 7: ......
Page 11: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverters 15kw and below...
Page 20: ...Installation 13 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Page 22: ...Wiring 15 4 1 Connection of Peripheral Devices Figure 4 1 Connection of peripheral devices...