List of Function Parameters
97
Function
Code
Name
Description
Factory
Setting
Modify
Serial
No.
P9.00
PID preset source
selection
0: Keypad
1: AI1
2: AI2
3: Communication
4: Multi-step
0
O
115
P9.01
Keypad PID preset 0.0%~100.0%
0.0%
O
116
P9.02
PID feedback source
selection
0: AI1
1: AI2
2: AI1+AI2
3: Communication
0
O
117
P9.03
PID output
characteristics
0: Positive
1: Negative
0
O
118
P9.04
Proportional gain
(Kp)
0.00~100.00
1.00
O
119
P9.05
Integral time (Ti)
0.01~10.00s
0.10s
O
120
P9.06
Differential time (Td) 0.00~10.00s
0.00s
O
121
P9.07
Sampling cycle (T)
0.01~100.00s
0.10s
O
122
P9.08
Bias limit
0.0~100.0%
0.0%
O
123
P9.09
Feedback lost
detecting value
0.0~100.0%
0.0%
O
124
P9.10
Feedback lost
detecting time
0.0~3600.0s
1.0s
O
125
PA Group: Multi-step Speed Control
PA.00
Multi-step speed 0
-100.0~100.0%
0.0%
O
126
PA.01
Multi-step speed 1
-100.0~100.0%
0.0%
O
127
PA.02
Multi-step speed 2
-100.0~100.0%
0.0%
O
128
PA.03
Multi-step speed 3
-100.0~100.0%
0.0%
O
129
PA.04
Multi-step speed 4
-100.0~100.0%
0.0%
O
130
PA.05
Multi-step speed 5
-100.0~100.0%
0.0%
O
131
PA.06
Multi-step speed 6
-100.0~100.0%
0.0%
O
132
PA.07
Multi-step speed 7
-100.0~100.0%
0.0%
O
133
PB Group: Protection Function
Summary of Contents for CHE100-004G-2
Page 7: ......
Page 11: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverters 15kw and below...
Page 20: ...Installation 13 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...
Page 22: ...Wiring 15 4 1 Connection of Peripheral Devices Figure 4 1 Connection of peripheral devices...