INVT CHE100-004G-2 Operation Manuals Download Page 116

Communication Protocol 

 

109

Node addr. 

Command

Data addr. 

Read No. 

CRC 

0x01 0x03 

0x00

0x02 

0x00 0x01 0x25 0xCA 

The table below shows the reply frame from slave node address 1 

Node addr. 

Command 

Bytes No.

Data  

CRC 

0x01 0x03 0x02 

0x00 0x00 0xB8

0x44 

ASCII mode 

In ASCII mode, the frame head is “0x3A”, and default frame tail is “0x0D” or “0x0A”. The 
frame tail can also be configured by users. Except frame head and tail, other bytes will be 
sent as two ASCII characters, first sending higher nibble and then lower nibble. The data 
have 7/8 bits. “A”~“F” corresponds to the ASCII code of respective capital letter. LRC 
check is used. LRC is calculated by adding all the successive bytes of the message 
except the head and tail, discarding any carriers, and then two’s complementing the 
result. 
Example of Modbus data frame in ASCII mode:   
The command frame of writing 0x0003 into address “0x1000” of slave node address 1 is 
shown in the table below: 
LRC checksum = the complement of (01+06+10+00+0x00+0x03) = 0xE5 

 

Frame 

head 

Node addr. 

Command 

Data addr. 

Code  0 

1 0 6 

ASCII 3A 30 31 30 36 

31 

30 

30 

30 

Data to write 

LRC 

Frame tail 

0 0 0  3  E 5 

CR 

LF 

30 30 30  33  45 35 

0D 

0A 

10.4 Protocol function 

Different respond delay can be set through drive’s parameters to adapt to different needs. 
For RTU mode, the respond delay should be no less than 3.5 bytes interval, and for 
ASCII mode, no less than 1ms. 
The main function of Modbus is to read and write parameters. The Modbus protocol 
supports the following commands: 

0x03 

Read inverter’s function parameter and status parameters 

0x06 

Write single function parameter or command parameter to inverter 

All drive’s function parameters, control and status parameters are mapped to Modbus 
R/W data address.   
The data addresses of each function parameters please refer the sixth column of chapter 
9.  
 

Summary of Contents for CHE100-004G-2

Page 1: ...ion Manual z Thank you very much for your buying CHE series sensorless vector control inverter z Before use please read this manual thoroughly to ensure proper usage Keep this manual at an easily acce...

Page 2: ...warning any un safety operation In some cases even the contents of CAUTION still can cause serious accident Please follow these important precautions in any situation NOTE indicate the necessary oper...

Page 3: ...ons of AC input reactor AC output reactor and DC reactor 21 4 4 3 Specification of braking resistor 22 4 5 Wiring Main Circuits 23 4 5 1 Wiring at input side of main circuit 23 4 5 2 Wiring at inverte...

Page 4: ...als 52 6 7 P6 Group Output Terminals 57 6 8 P7 Group Display Interface 59 6 9 P8 Group Enhanced Function 64 6 10 P9 Group PID Control 68 6 11 PA Group Multi step Speed Control 71 6 12 PB Group Protect...

Page 5: ...l plate cover 13 Figure 3 8 Open inverter cabinet 13 Figure 4 1 Connection of peripheral devices 15 Figure 4 2 Main circuit terminals 0 4 0 75kW 1AC 220V 16 Figure 4 3 Main circuit terminals 1 5 2 2kW...

Page 6: ...mode2 56 Figure 6 14 Relationship between AI and corresponding setting 57 Figure 6 15 Relationship between AO and corresponding setting 59 Figure 6 16 Skip frequency diagram 65 Figure 6 17 Traverse op...

Page 7: ......

Page 8: ...h 150 of rated current 10s with 180 of rated current Starting Torque 150 of rated torque at 0 5Hz SVC Speed Adjusting Range 1 100 SVC Speed Accuracy 0 5 of maximum speed SVC Carrier Frequency 0 5kHz 1...

Page 9: ...4 2 7 0 1 5 B CHE100 2R2G S2 2 2 23 0 10 2 2 B 3AC 220V 15 CHE100 0R7G 2 0 75 5 0 4 5 0 75 A CHE100 1R5G 2 1 5 7 7 7 1 5 B CHE100 2R2G 2 2 2 11 0 10 2 2 B CHE100 004G 2 4 0 17 0 16 3 7 C CHE100 5R5G 2...

Page 10: ...7G 045P 4 37 45 76 90 75 90 37 45 F CHE100 045G 055P 4 45 55 90 105 90 110 45 55 F CHE100 055G 075P 4 55 75 105 140 110 150 55 75 F CHE100 075G 090P 4 75 90 140 160 150 176 75 90 G CHE100 090G 110P 4...

Page 11: ...Introduction 4 1 4 Parts Description Figure 1 2 Parts of inverters 15kw and below...

Page 12: ...Introduction 5 Figure 1 3 Parts of inverters 18 5kw and above 1 5 External Dimension Figure 1 4 Dimension 0 4 0 75kW 1AC 220V...

Page 13: ...Introduction 6 Figure1 5 Dimension 0 75 15kW Figure 1 6 Dimension 18 5 110kW Figure 1 7 Dimension 132 315kW...

Page 14: ...6 140 85 115 4 0 75 2 2 B 110 4 170 2 180 120 140 5 4 5 5 C 147 5 237 5 250 160 175 5 7 5 15 D 206 305 5 320 220 180 6 0 18 5 30 E 176 454 5 467 290 215 6 5 37 55 F 230 564 5 577 375 270 7 0 75 110 G...

Page 15: ...or of the Inverter to ensure there are no scratches or other damage caused by the transportation 2 Ensure there is operation manual and warranty card in the packing box 3 Inspect the nameplate and ens...

Page 16: ...s voltage Power Terminals R S T Motor Connection Terminals U V W When power off should not install the inverter until 5 minutes after which can ensure the device discharge completely The section area...

Page 17: ...to the following figure Figure 3 1 Relationship between output current and altitude 3 1 4 Impact and Vibration It is not allowed that the inverter falls down or suffers from fierce impact or the inver...

Page 18: ...Installation 11 3 2 Installation Space Figure 3 2 Safe space Figure 3 3 Installation of multiple inverters Notice Add the air deflector when apply the up down installation...

Page 19: ...Installation 12 3 3 Dimension of External Keypad Figure 3 4 Dimension of small keypad Figure 3 5 Dimension of big keypad 3 4 Disassembly Figure 3 6 Disassembly of plastic cover...

Page 20: ...Installation 13 Figure 3 7 Disassembly of metal plate cover Figure 3 8 Open inverter cabinet...

Page 21: ...00V class Ground resistance should be 10 or less 660V class Ground resistance should be 5 or less Otherwise it might cause electric shock or fire Connect input terminals R S T and output terminals U V...

Page 22: ...Wiring 15 4 1 Connection of Peripheral Devices Figure 4 1 Connection of peripheral devices...

Page 23: ...t terminals 1 5 2 2kW R S T U V W PB POWER MOTOR Figure 4 4 Main circuit terminals 4 0 5 5kW R S T U V W PB POWER MOTOR Figure 4 5 Main circuit terminals 7 5 15kW R S T U V W POWER P1 MOTOR Figure 4 6...

Page 24: ...485 485 10V AO COM Y 24V ROA ROB ROC AI1 GND AI2 S1 S2 S3 S4 Figure 4 10 Control circuit terminals 1 5 2 2kW 485 485 AO AI1 GND AI2 10V S1 S2 S3 S4 COM Y 24V ROA ROB ROC Figure 4 11 Control terminals...

Page 25: ...which is used to improve power factor For inverters above 110KW it is recommended to install DC reactor between P1 and 2 Inverters below 15KW have built in braking unit If need braking only need to in...

Page 26: ...0R7G S2 16 2 5 10 CHE100 1R5G S2 20 4 16 CHE100 2R2G S2 32 6 20 3 3A AC C 2 22 20 0V V 1 15 5 CHE100 0R4G 2 16 2 5 10 CHE100 0R7G 2 16 2 5 10 CHE100 1R5G 2 20 4 16 CHE100 2R2G 2 32 6 20 CHE100 004G 2...

Page 27: ...100 022G 030P 4 100 16 80 CHE100 030G 037P 4 125 25 95 CHE100 037G 045P 4 160 25 120 CHE100 045G 055P 4 200 35 135 CHE100 055G 075P 4 200 35 170 CHE100 075G 090P 4 250 70 230 CHE100 090G 110P 4 315 70...

Page 28: ...28 60 0 045 80 0 4 CHE100 030G 037P 4 80 0 19 80 0 032 80 0 4 CHE100 037G 045P 4 90 0 19 90 0 03 110 0 25 CHE100 045G 055P 4 120 0 13 120 0 023 110 0 25 CHE100 055G 075P 4 150 0 11 150 0 019 110 0 25...

Page 29: ...1 19 1100W 1 CHE100 015G 2 1 13 6 1500W 1 CHE100 018G 2 1 12 1800W 1 CHE100 022G 2 1 9 2200W 1 CHE100 030G 2 DBU 055 2 1 6 8 3000W 1 CHE100 037G 2 2 11 2000W 2 CHE100 045G 2 DBU 055 2 2 9 2400W 2 3AC...

Page 30: ...t should be less than 5m 4 Wire between braking unit and braking resistor should be less than 10m 5 Braking unit can be used for braking continuously for 5 minutes When braking unit is working tempera...

Page 31: ...18 5kW to 90kW have built in DC reactor which can improve the power factor 4 5 2 2 Braking unit and braking resistor Inverter of 15KW and below have built in braking unit In order to dissipate the re...

Page 32: ...output reactor should be installed 4 5 3 2 Output EMC filter EMC filter should be installed to minimize the leak current caused by the cable and minimize the radio noise caused by the cables between t...

Page 33: ...is in regenerative status In this case the DC buses of these two inverters can be connected in parallel so that the regenerated energy can be supplied to motors in driving status whenever it needs Det...

Page 34: ...nalog input 0 10V 0 20mA switched by J16 Input impedance 10k voltage input 250 current input GND Common ground terminal of analog signal and 10V GND must isolated from COM 10V Supply 10V to inverter C...

Page 35: ...wer should greater than 1 4W Its resistance is recommended to be 5 10k Notice The terminal will use the internal circuit to adjust the input signal To the first two work mode the relative internal vol...

Page 36: ...t it can produce certain electromagnetic interference noise And the same time inverter should be designed with certain anti jamming ability to ensure the smooth working in certain electromagnetic envi...

Page 37: ...re fire wires one of which is the neutral wire and one of which is the ground wire It is strictly prohibitive to use the same line to be both the neutral wire and the ground wire Device categorization...

Page 38: ...h is the current passing through the common ground wire can not only flow into inverter system but also other devices It also can make leakage current circuit breaker relay or other devices malfunctio...

Page 39: ...tion 5 1 1 Keypad schematic diagram Figure 5 1 Keypad schematic diagram 5 1 2 Key function description Button Symbol Name Function Description Programming Key Entry or escape of first level menu Enter...

Page 40: ...tus restricted by P7 04 can be used to stop the inverter When fault alarm can be used to reset the inverter without any restriction Shortcut Multifunction Key Determined by Function Code P7 03 0 Jog o...

Page 41: ...es such as reference frequency output frequency and so on 5 2 Operation Process 5 2 1 Parameter setting Three levels of menu are z Function code group first level z Function code second level z Functi...

Page 42: ...less Vector Control mode is chosen motor nameplate parameters must be input correctly as the autotuning is based on it The performance of vector control depends on the parameters of motor strongly so...

Page 43: ...can be chosen through Function Code P7 06 Running status display selection and P7 07 Stop status display selection according to binary bits the detailed description of each bit please refer the funct...

Page 44: ...ss the SHIFT to scroll through the parameters in right order Press DATA ENT QUICK JOG to scroll through the parameters in left order 5 3 5 Fault CHE series inverter offers a variety of fault informati...

Page 45: ...racy torque control such as wired drawing In torque control mode the speed of motor is determined by load the rate of ACC DEC has nothing to do with the value of P0 08 and P0 09 or P8 00 and P8 01 Not...

Page 46: ...not save UP DOWN value when power off 2 Invalid 3 Valid during running clear when stop 0 3 0 0 User can adjust the reference frequency by UP DOWN The value of UP DOWN can be saved when power off 1 Use...

Page 47: ...11 z 100 of AI is corresponding to maximum frequency P0 04 4 Multi step speed The reference frequency is determined by PA group The selection of steps is determined by combination of multi step speed...

Page 48: ...ld not be greater than upper frequency limit P0 05 z If frequency reference is lower than P0 06 the action of inverter is determined by P1 12 Please refer to description of P1 12 Function Code Name De...

Page 49: ...eleration time can be selected by combination of multifunctional ON OFF input terminals determined by P5 Group The factory setting of acceleration and deceleration time is as follow z 5 5kW and below...

Page 50: ...actory setting is optimal in most cases Modification of this parameter is not recommended z If the carrier frequency exceeds the factory setting the inverter must be derated because the higher carrier...

Page 51: ...ing is finished and return to the stop status e During the autotuning press the STOP RST will stop the autotuning Notice Only keypad can control the autotuning P0 12 will restore to 0 automatically wh...

Page 52: ...urrent firstly and then start the motor at the starting frequency Please refer to description of P1 03 and P1 04 It is suitable for the motor which have small inertia load and may reverse rotation whe...

Page 53: ...effect the inverter blocks the output immediately The motor coasts to stop by its mechanical inertia Function Code Name Description Setting Range Factory Setting P1 06 Starting frequency of DC brakin...

Page 54: ...actory Setting P1 11 FWD REV enable option when power on 0 Disabled 1 Enabled 0 1 0 Notice This function only takes effect if run command source is terminal control If P1 11 is set to be 0 when power...

Page 55: ...otor rated voltage 0 2000V 0 2000V Depend on model P2 05 Motor rated current 0 8 2000 0A 0 8 2000 0 Depend on model Notice In order to achieve superior performance please set these parameters accordin...

Page 56: ...1 00s P3 05 ASR switching point 2 P3 02 P0 04 P3 02 P0 04 10 00Hz P3 00 P3 05 are only valid for vector control and torque control and invalid for V F control Through P3 00 P3 05 user can set the prop...

Page 57: ...e adjustment please refer to description of P9 group Function Code Name Description Setting Range Factory Setting P3 06 Slip compensation rate of VC 50 0 200 0 50 0 200 0 100 The parameter is used to...

Page 58: ...e otherwise the motor would be over heat or the inverter would be tripped by over current or over load If P4 01 is set to be 0 the inverter will boost the output torque according to the load automatic...

Page 59: ...e multifunctional terminal 0 25 0 The meaning of each setting is shown in following table Setting value Function Description 0 Invalid Please set unused terminals to be invalid to avoid malfunction 1...

Page 60: ...d by the combination of these two terminals Terminal ACC DEC time Corresponding Parameter OFF Acceleration Time 0 P0 08 P0 09 ON Acceleration Time 1 P8 00 P8 01 16 Pause PID PID adjustment will be pau...

Page 61: ...F ON OFF 3 ON ON OFF 4 OFF OFF ON 5 ON OFF ON 6 OFF ON ON 7 ON ON ON Function Code Name Description Setting Range Factory Setting P5 04 ON OFF filter times 1 10 1 10 5 This parameter is used to set fi...

Page 62: ...6 11 2 wire control mode 2 2 3 wire control mode 1 SB1 Start button SB2 Stop button NC K Run direction button Terminal SIn is the multifunctional input terminal of S1 S4 The terminal function should b...

Page 63: ...1 lower limit 0 00V 10 00V 0 00 10 00 0 00V P5 08 AI1 lower limit corresponding setting 100 0 100 0 100 0 100 0 0 0 P5 09 AI1 upper limit 0 00V 10 00V 0 00 10 00 10 00V P5 10 AI1 upper limit correspon...

Page 64: ...0 10 00 10 00V P5 15 AI2 upper limit corresponding setting 100 0 100 0 100 0 100 0 100 0 P5 16 AI2 filter time constant 0 00s 10 00s 0 00 10 00 0 10s Please refer to description of AI1 When AI2 is set...

Page 65: ...nctional analog output 0 10 0 Current 0 20mA or voltage 0 10V output can be selected by Jumper J15 AO functions are indicated in the following table Setting Value Function Range 0 Running frequency 0...

Page 66: ...onship between AO and corresponding setting 6 8 P7 Group Display Interface Function Code Name Description Setting Range Factory Setting P7 00 User password 0 65535 0 65535 0 The password protection fu...

Page 67: ...g direction of inverter will reverse It is only valid if P0 03 is set to be 0 2 Clear UP DOWN setting Press QUICK JOG the UP DOWN setting will be cleared Function Code Name Description Setting Range F...

Page 68: ...unning status If Bit is 0 the parameter will not be displayed If Bit is 1 the parameter will be displayed Press SHIFT to scroll through these parameters in right order Press DATA ENT QUICK JOG to scro...

Page 69: ...PID preset Output terminal status Input terminal status DC bus voltage Reference frequency BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8 Reserved Reserved Reserved Reserved Reserved Reserved Reserved...

Page 70: ...ription of chapter 7 Function Code Name Description Setting Range Factory Setting P7 15 Output frequency at current fault Output frequency at current fault P7 16 Output current at current fault Output...

Page 71: ...P0 04 5 00Hz P8 03 Jog acceleration time 0 1 3600 0s 0 1 3600 0 Depend on model P8 04 Jog deceleration time 0 1 3600 0s 0 1 3600 0 Depend on model The meaning and factory setting of P8 03 and P8 04 i...

Page 72: ...ter frequency 0 0 50 0 0 0 50 0 0 0 P8 09 Rise time of traverse 0 1 3600 0s 0 1 3600 0 5 0s P8 10 Fall time of traverse 0 1 3600 0s 0 1 3600 0 5 0s Traverse operation is widely used in textile and che...

Page 73: ...es 0 3 0 3 0 P8 12 Reset interval 0 1 100 0s 0 1 100 0 1 0s Auto reset function can reset the fault in preset times and interval When P8 11 is set to be 0 it means auto reset is disabled and the prote...

Page 74: ...ram Function Code Name Description Setting Range Factory Setting P8 16 Brake threshold voltage 115 0 140 0 115 0 140 0 Depend on model When the DC bus voltage is greater than the value of P8 16 the in...

Page 75: ...ording to proportional gain integral and differential time Please refer to following figure Figure 6 20 PID control diagram Function Code Name Description Setting Range Factory Setting P9 00 PID prese...

Page 76: ...imize the responsiveness by adjusting these parameters while driving an actual load Use the following procedure to activate PID control and then adjust it while monitoring the response 1 Enabled PID c...

Page 77: ...If the oscillation cycle is short and oscillation occurs with a cycle approximately the same as the differential time setting it means that the differential operation is strong The oscillation will b...

Page 78: ...cy and stability Figure 6 25 Relationship between bias limit and output frequency Function Code Name Description Setting Range Factory Setting P9 09 Feedback lost detecting value 0 0 100 0 0 0 100 0 0...

Page 79: ...00 0 100 0 100 0 0 0 PA 07 Multi step speed 7 100 0 100 0 100 0 100 0 0 0 Notice 100 of multi step speed x corresponds to the maximum frequency P0 04 If the value of multi step speed x is negative the...

Page 80: ...e poorer the cooling effect Based on this reason if output frequency is lower than 30Hz inverter will reduce the motor overload protection threshold to prevent normal motor from overheat 2 As the cool...

Page 81: ...use over voltage fault If PB 03 is too small the feedback energy of motor will be too small to achieve voltage compensation effect So please set PB 03 according to load inertia and the actual load Fun...

Page 82: ...nertia or step change of load PB 06 is a percentage of the inverter s rated current PB 07 defines the decrease rate of output frequency when this function is active If PB 06 is too small overload faul...

Page 83: ...er and slave must be the same Function Code Name Description Setting Range Factory Setting PC 02 Data format 0 17 0 17 0 This parameter defines the data format used in serial communication protocol 0...

Page 84: ...less than 3 5 characters interval in ASCII mode 1ms Function Code Name Description Setting Range Factory Setting PC 04 Communication timeout delay 0 0 Disabled 0 1 100 0s 0 100 0 0 0s When the value i...

Page 85: ...n Setting Range Factory Setting PD 00 Low frequency threshold of restraining oscillation 0 500 0 500 5 PD 01 High frequency threshold of restraining oscillation 0 500 0 500 100 This function is valid...

Page 86: ...current For details please refer to description of PD 00 PD 03 Function Code Name Description Setting Range Factory Setting PD 05 PWM mode 0 PWM mode 1 1 PWM mode 2 2 PWM mode 3 0 2 0 The features of...

Page 87: ...rse Notice When running at torque control mode the acceleration time has nothing to do with P0 08 The 100 of torque setting is corresponding to 100 of P3 07 Torque limit For example if torque setting...

Page 88: ...e Fault Type Reason Solution OUT1 IGBT Ph U fault OUT2 IGBT Ph V fault OUT3 IGBT Ph W fault 1 Acc Dec time is too short 2 IGBT module fault 3 Malfunction caused by interference 4 Grounding is not prop...

Page 89: ...dden change of load 1 Select variable frequency motor 2 Check and adjust V F curve 3 Check and adjust PB 01 4 Check the load OL2 Inverter overload 1 Load is too heavy or Acc Dec time is too short 2 Im...

Page 90: ...2 Check motor s wiring EEP EEPROM fault 1 R W fault of control parameters Press STOP RESET to reset Ask for support PIDE PID feedback fault 1 PID feedback disconnected 2 PID feedback source disappears...

Page 91: ...maged ask for support 7 2 4 Inverter displays normally when power on but switch at the input side trips when running z Inspect whether the output side of inverter is short circuit If yes ask for suppo...

Page 92: ...te 3 no abnormal color and smell Inverter 1 vibration 2 cooling and heating 3 noise 1 point thermometer 2 comprehensive observation 3 listening 1 smooth operation without vibration 2 fan is working in...

Page 93: ...y The drive should be powered for 5 hours without load 8 2 7 Before performing insulation tests all main circuit input output terminals should be short circuited with conductors Then proceed insulatio...

Page 94: ...ates that this parameter can be modified all the time indicates that this parameter cannot be modified during the inverter is running indicates that this parameter is read only Factory Setting indicat...

Page 95: ...stop 0 O 2 P0 03 Frequency A command source 0 Keypad 1 AI1 2 AI2 3 AI1 AI2 4 Multi Step speed 5 PID 6 Communication 0 O 3 P0 04 Maximum frequency 10 00 400 00Hz 50 00Hz 4 P0 05 Upper frequency limit P...

Page 96: ...0s 0 0s O 17 P1 03 DC Braking current before start 0 0 150 0 0 0 O 18 P1 04 DC Braking time before start 0 0 50 0s 0 0s O 19 P1 05 Stop mode 0 Deceleration to stop 1 Coast to stop 0 O 20 P1 06 Starti...

Page 97: ...epend on model l O 35 P2 08 Motor leakage inductance 0 1 6553 5mH Depend on model O 36 P2 09 Motor mutual inductance 0 1 6553 5mH Depend on model O 37 P2 10 Current without load 0 01 655 35A Depend on...

Page 98: ...roup Input Terminals P5 00 S1 terminal function 1 53 P5 01 S2 terminal function 4 54 P5 02 S3 terminal function 7 55 P5 03 S4 terminal function 0 Invalid 1 Forward 2 Reverse 3 3 wire control 4 JOG for...

Page 99: ...it corresponding setting 100 0 100 0 100 0 O 63 P5 11 AI1 filter time constant 0 00s 10 00s 0 10s O 64 P5 12 AI2 lower limit 0 00V 10 00V 0 00V O 65 P5 13 AI2 lower limit corresponding setting 100 0 1...

Page 100: ...V 10 00V 10 00V O 76 P7 Group Display Interface P7 00 User password 0 65535 0 O 77 P7 01 LCD language selection 0 Chinese 1 English 0 O 78 P7 02 Parameter copy 0 Invalid 1 Upload from inverter 2 Downl...

Page 101: ...ck BIT10 Input terminal status BIT11 Output terminal status BIT12 AI1 BIT13 AI2 BIT14 Step No of multi step BIT15 Reserved 0XFF O 83 P7 07 Stop status display selection 0 0X1FF BIT0 Reference frequenc...

Page 102: ...tant speed running OV3 10 DC bus Under voltage UV 11 Motor overload OL1 12 Inverter overload OL2 13 Input phase failure SPI 14 Output phase failure SPO 15 Rectify overheat OH1 16 IGBT overheat OH2 17...

Page 103: ...odel O 101 P8 05 Skip frequency 0 00 P0 04 0 00Hz O 102 P8 06 Skip frequency bandwidth 0 00 P0 04 0 00Hz 103 P8 07 Traverse amplitude 0 0 100 0 0 0 O 104 P8 08 Jitter frequency 0 0 50 0 0 0 O 105 P8 0...

Page 104: ...fferential time Td 0 00 10 00s 0 00s O 121 P9 07 Sampling cycle T 0 01 100 00s 0 10s O 122 P9 08 Bias limit 0 0 100 0 0 0 O 123 P9 09 Feedback lost detecting value 0 0 100 0 0 0 O 124 P9 10 Feedback l...

Page 105: ...20 O 140 PB 07 Frequency decrease rate when current limiting 0 00 100 00Hz s 10 00 Hz s O 141 PC Group Serial Communication PC 00 Local address 0 247 1 O 142 PC 01 Baud rate selection 0 1200BPS 1 2400...

Page 106: ...ASCII 1 start bit 8 data bits even parity check 2 stop bits 17 ASCII 1 start bit 8 data bits odd parity check 2 stop bits PC 03 Communication delay time 0 200ms 5 O 145 PC 04 Communication timeout del...

Page 107: ...O 155 PD 07 Keypad torque setting 100 0 100 0 0 O 156 PD 08 Upper frequency limit selection 0 Keypad P0 05 1 AI1 2 AI2 3 Multi step setting 4 Communication 0 O 157 PD 09 Auto current limiting selecti...

Page 108: ...4 08 V F voltage 3 0 0 100 0 motor rated voltage 100 0 P4 09 V F Slip compensation limit 0 00 200 0 0 0 O P4 10 Auto energy saving selection 0 Disabled 1 Enabled 0 Parameters display on LCD keypad Fun...

Page 109: ...DC braking current STOP BRAK CURR P1 09 DC braking time STOP BRAK TIME P1 10 Dead time of FWD REV FWD REV DEADTIME P1 11 FWD REV enable when power on FWD REV ENABLE P1 12 Reserved RESERVED P2 00 G P...

Page 110: ...erminal function S1 FUNCTION P5 01 S2 terminal function S2 FUNCTION P5 02 S3 terminal function S3 FUNCTION P5 03 S4 terminal function S4 FUNCTION P5 04 ON OFF filter times Sx FILTER TIMES P5 05 FWD RE...

Page 111: ...tion KEYPAD DISPLAY P7 06 Running status display selection RUNNING DISPLAY P7 07 Stop status display selection STOP DISPLAY P7 08 Rectifier module temperature RECTIFIER TEMP P7 09 IGBT module temperat...

Page 112: ...13 FDT level FDT LEVEL P8 14 FDT lag FDT LAG P8 15 Frequency arrive detecting range FAR RANGE P8 16 Brake threshold voltage BRAK VOLT P8 17 Coefficient of rotation speed SPEED RATIO P9 00 PID preset...

Page 113: ...stall protection OVER VOLT STALL PB 05 Over voltage stall protection point OV PROTECT POINT PB 06 Auto current limiting threshold CURR LIMIT POINT PB 07 Frequency decrease rate when current limiting...

Page 114: ...scillation RES OSC ENABLE PD 05 PWM mode PWM MODE PD 06 Torque setting source TORQ SOURCE PD 07 Keypad torque setting KEYPAD TORQ SET PD 08 Upper frequency limit selection UP FREQ SOURCE PD 09 Auto cu...

Page 115: ...master signal line will help to enhance the immunity to interference 10 3 Protocol Format Modbus protocol supports both RTU and ASCII mode The frame format is illustrated as follows Modbus adopts Big...

Page 116: ...SCII mode The command frame of writing 0x0003 into address 0x1000 of slave node address 1 is shown in the table below LRC checksum the complement of 01 06 10 00 0x00 0x03 0xE5 Frame head Node addr Com...

Page 117: ...ing is the percentage of the relative value 100 00 100 00 If it is set as frequency source the value is the percentage of the maximum frequency P0 04 If it is set as PID preset value or feedback value...

Page 118: ...d protocol data unit for simplicity Also MSB stands for the most significant byte and LSB stands for the least significant byte for the same reason The description below is data format in RTU mode The...

Page 119: ...dress Some of the operation addresses are invalid or not allowed to access 03H Illegal value When there are invalid data in the message framed received by slave Note This error code does not indicate...

Page 120: ...5 bytes interval otherwise the message will be discarded 10 5 2 Be cautious to modify the parameters of PC group through communication otherwise may cause the communication interrupted 10 5 3 In the...

Page 121: ...High byte of data number 00H Low byte of data number 02H Low byte of CRC 85H High byte of CRC CAH END T1 T2 T3 T4 transmission time of 3 5 bytes The reply is START T1 T2 T3 T4 transmission time of 3 5...

Page 122: ...ress 0 0 Low byte of start address 4 0 High byte of data number 0 0 Low byte of data number 2 LRC CHK Hi F LRC CHK Lo 6 END Lo CR END Hi LF The reply is START 0 Node address 1 0 Command 3 0 Returned b...

Page 123: ...8H High byte of write content 13H Low byte of write content 88H Low byte of CRC 05H High byte of CRC 6DH END T1 T2 T3 T4 transmission time of 3 5 bytes The reply command is START T1 T2 T3 T4 transmiss...

Page 124: ...f data address 0 0 Low byte of data address 8 1 High byte of write content 3 8 Low byte of write content 8 LRC CHK Hi 5 LRC CHK Lo 5 END Lo CR END Hi LF The reply command is START 0 Node address 2 0 C...

Reviews: