34
Table 8-2 Indicator status
Indicator light
Function
State
Significance
Indicator 1
System Operating
Indicator
Green always
shines/fades
Abnormal monitoring
system
Green scintillation
Normal monitoring system
Indicator 2
Inverter indicator
Green is always bright
Inverter Normal work
Green scintillation
Inverter Soft start
Indicator turn off
Inverter does not work
Indicator 3
Alarm light
Red flashing
Inverter alarm
Indicator turn off
Inverter no alarm
※
ndicator lamp 1, indicator lamp 2, indicator lamp 3, refers to the working status indicator lamp, the
order is from top to bottom.
8.2 Alarm Buzzer
Table 8-3 Buzzer Warning Mode
Short-lived single-beep
alert
When pressing any function operation key, issue this alarm sound
Whisper every 1 second
When an alarm occurs in the inverters, the alarm sounds are
emitted
8.3 Communication Settings
Communication parameters can set device address (modbus address) and RS485 baud rate
to communicate with the host computer. The communication mode between equipment
and BMS can be chosen: no communication, CAN, serial port. The communication between
the equipment and the host computer supports RS485 serial communication and network
communication. The settings are as follows:
RS485 Serial Communication
The Modbus address of the device ranges from 1 to 247, and each device has a unique
address.
The default baud rate of serial communication is 9600 bps.
Network communication
IP address default 192.168.1.250
Subnet mask default 255.255.255.0
Gateway default 192.168.1.1
CAN port communication
The default baud rate of CAN port communication is 250 kbps.
8.4 Software Introduction
8.4.1 Homepage introduction
The main interface mainly displays machine model, network address, time, menu bar, battery