2-8
for the timer to start counting-the voltage may not reach the equalization voltage setting.
To manually stop the equalization process, press the reset pushbutton and the status LED
will stop, if the equalization process was shorter than one hour, the controller will
continue with a bulk charge cycle and then hold the battery at the bulk setting for one
hour (the absorption voltage) before returning to the float setting. Once a manual
equalization has been triggered, the period to the next automatic equalization will be
restarted.
In the Manual Equalization Mode (Switch number 7 OFF), equalization will occur only
when manually started with the push button. The equalization status LED indicator will
begin to equalization enabled. The equalization process will continue until the batteries
have been held at or above the set Equalize Voltage for set Equalize Time of accumulated
time. During the equalization process, the battery voltage will be limited to the set
Equalize Voltage setting. Once the battery voltage has been at or above the set Equalize
Voltage for a cumulative period of set Equalize Time, the SunStar will return to the float
stage of the charge process. To stop the equalization process, press the reset push button,
the status LED will stop. If the equalization process was shorter than one hour, the
controller will continue with a bulk charge cycle and hold the battery at bulk setting for
one hour (the absorption stage) before returning to the float setting.
DIP switch number 8-User define battery select
Switch 8
Charge Control algorithm
ON
User define (VR1, VR2)
OFF
Dip Switch 4~6 selection
The battery voltage setting range of VR2 BULK Voltage potentiometer is 13.0V~15.0V
The battery voltage setting range of VR1 FLOAT Voltage potentiometer is 12.5V~14.5V
※
The above setting voltage value is in the condition of 12V system. The voltage will be
twice of above values in the 24V system and it will be four times of above values in the
48V system.
The latest LCD Meter display will show the voltage setting value of VR2 and VR1 and the
user can adjust those values directly.
2.4.3 Load Control DIP Switch Setting
The Load Control functions that can be adjusted with the DIP switches follow: