OPERATING IN KEYPAD MODE
Set P-12 = 1(this allows the Optidrive to be
controlled from the keypad):
Enable the drive by closing digital input
1. The display will show StoP.
Press the START key. The display shows
H 0.0.
Press to increase speed
The drive will run forward, increasing
speed until is released.
CAUTION:
the rate of acceleration is
controlled by the setting of P-03, check
this before starting.
Either Press
to decrease speed
The drive will decrease speed until
τ
is
released. The rate of deceleration is
limited by the setting in P-04
Or Press the STOP key. The drive will
decelerate to rest at the rate set in P-04.
The display will finally show StoP at
which point the drive is disabled
To preset a target speed prior to enable
press the stop key whilst the drive is
stopped. The display will show the target
speed, use the and
to adjust as
required then press the Stop key to return
the display to StoP. Pressing the START
key will start the drive accelerating to the
target speed.
The operation of the keypad can be duplicated
using remote pushbuttons connected to the
control terminals, see Application Note AN21.
In this mode, if P30 is set to Auto-0..4, then
the drive will run as soon as the drive enable
is applied (terminal 1 & 2 is closed).
TO SAVE CHANGES
to Parameter settings,
switch the power supply off and wait for the
drive to power down (screen blank) before
switching on.
NOTE that this assumes P-38 = 0 (default). If
P-38 = 1, changes are not saved.
STANDARDS CONFORMITY
The Optidrive E conforms with the following standards
1) CE marked for low voltage directive
2) UL508C Power conversion equipment
3) IEC 664-1 Insulation coordination for equipment within low voltage systems
4) EN61800-3 Adjustable Speed electrical power drive systems – Part 3 (EMC)
5) EN 61000-6 / -2, -3, -4 Generic Immunity / Emissions standards (EMC)
Earth
N
Isolator
Contactor,
mcb or
Fuses
Screened motor
cable connects to
motor frame earth
L
U V W
Optidrive E1 size 2
Help card
Cable
management
tie-wrap
L N
U V W
Each drive star
connected to system
earth point
To
other
drives
E
OPERATION – GETTING STARTED
PSC MOTOR WIRING
CONTROL TERMINAL BLOCK -
Default Status
+10V O/
P
D
igi
ta
l I
/P
1
D
igi
ta
l I
/P
2
D
igi
ta
l I
/P
3
+10V O/
P
Analog
I/
P
0V
Analog
O/
P
0V
Re
la
y co
nt
ac
t
R
ela
y c
omm
on
C
lo
se
d:
Enable;
Open:
D
is
able
500
Ω
min.
0-10V
analog
O/P
Relay ratings
30V dc, 5A
240V ac, 5A
0-10V
4
-20mA
1 2 3 4 5 6 7 8 9 10 11
An
alog
I/
P
-
C
los
ed
: A;
Open :
V
lo
sed:
Pre
set
1;
Open:
A
nalog I
/P
WARNING
The STOP function does not remove potentially lethal high voltages. ISOLATE the drive and
wait 10 minutes before starting any work on it
Parameter P-01 can be set to operate the motor at up to 3,000 rpm, hence use this parameter
with care
If it is desired to operate the drive at any frequency/speed above the rated speed (P-09/ P-10)
of the motor, consult the manufacturers of the motor and the driven machine about suitability
for over-speed operation
The fan (if fitted) to the heatsink of the Optidrive starts automatically when the heatsink
temperature reaches approximately 40ºC. When the heatsink is at room temperature the fan
will be stopped.
MECHANICAL INSTALLATION
Optidrives can be installed side-by-side with their heatsink
flanges touching. This gives adequate ventilation space between
them. If the Optidrive is to be installed above another drive or
any other heat-producing device, the minimum vertical spacing
is 100mm. The enclosure should either be force-ventilated or
large enough to allow natural cooling (allow 0.1 m
3
per kW of
drive rating).
GROUNDING (EARTHING)
The ground terminal of each Optidrive should be individually
connected DIRECTLY to the site earth (ground) busbar (through
the filter if installed) as shown. Optidrive ground connections
should not loop from one drive to another, or to, or from any
other equipment. Ground loop impedance must conform to local
industrial safety regulations. To meet UL regulations, UL
approved ring crimp terminals should be used for all earth wiring
connections.
EASY START-UP
When delivered, the Optidrive is in the default state,
meaning that it is set to operate in terminal mode and
all parameters (P-xx) have the default values as
shown overleaf.
Connect a control switch between the control
terminals 1 and 2.
Connect a potentiometer (500
Ω
min to 10 k
Ω
max)
between terminals 5 and 7, and wiper to terminal 6.
Set the control switch between pins 1 and 2 open
so that the drive is ‘disabled’.
With the potentiometer set to zero, switch on the
supply to the drive. The display will show StoP.
Close the control switch, terminals 1-2. The drive is
now ‘enabled’ and the output frequency/speed are
controlled by the potentiometer. The display shows
zero speed in Hz (H 0.0) with the potentiometer
turned to minimum.
Turn the potentiometer to maximum. The motor will
accelerate to 50Hz (the default value of P-01) under
the control of the accelerating ramp time P-03. The
display shows H 50.0 (50Hz) at max speed.
To display motor current (A), briefly press the
Navigate key
⇔
.
Press
⇔
again to return to speed display.
To stop the motor, either turn the potentiometer back
to zero or disable the drive by opening the control
switch (terminals 1-2).
If the enable/disable switch is opened the drive will
decelerate to stop at which time the display will show
StoP. If the potentiometer is turned to zero and the
enable/disable is closed the display will show 0.0Hz, if
left like this for 20 seconds the drive will go into
standby mode, display shows Stndby, waiting for a
speed reference.
User Guide
All rights reserved. No part of this User Guide may be reproduced
or transmitted in any form or by any means, electrical or
mechanical including photocopying, recording or by any
information storage or retrieval system without permission in
writing from the publisher.
Copyright Invertek Drives Ltd
©
2005
The manufacturer accepts no liability for any consequences
resulting from inappropriate, negligent or incorrect installation, or
adjustment of the optional operating parameters of the drive or
from mismatching of the drive to the motor.
The contents of this User Guide are believed to be correct at the
time of printing. In the interests of a commitment to a policy of
continuous improvement, the manufacturer reserves the right to
change the specification of the product or its performance or the
contents of the User Guide without notice.
SAFETY
This variable speed drive product (Optidrive) is intended for
professional incorporation into complete equipment or systems. If
installed incorrectly it may present a safety hazard. The Optidrive
uses high voltages and currents, carries a high level of stored
electrical energy, and is used to control mechanical plant that may
cause injury. Close attention is required to system design and
electrical installation to avoid hazards in either normal operation
or in the event of equipment malfunction.
System design, installation, commissioning and maintenance
must be carried out only by personnel who have the necessary
training and experience. They must read carefully this safety
information and the instructions in this Guide and follow all
information regarding transport, storage, installation and use of
the Optidrive, including the specified environmental limitations.
Please read the
IMPORTANT SAFETY INFORMATION
below, and
all
Warning
and
Caution
boxes elsewhere.
SAFETY NOTICES
WARNING
is given where there is a hazard that could lead to injury
or death of personnel
CAUTION
is given where there is a hazard that could lead to
damage to equipment
CAUTION
Carefully inspect the Optidrive before
installation to ensure it is undamaged
Store the Optidrive in its box until
required. Storage should be clean and
dry Temp. Range –40
o
C to +60
o
C
Install the Optidrive on a flat, vertical,
flame-resistant vibration-free mounting
within a suitable enclosure, according to
EN60529 if specific Ingress Protection
ratings are required. Installation required
in a pollution degree 2 environment.
Flammable material should not be
placed close to the drive
The entry of conductive or flammable
foreign bodies should be prevented
Max. ambient temperature 50
o
C, min. –
5
o
C. Refer to table on reverse side.
Relative humidity must be less than 95%
(non-condensing).
The Optidrive is suitable for use on a
circuit capable of delivering not more
than 5KA (50Hp) / 10KA (51-200HP)
symmetrical amperes, 480V maximum
.
WARNING
Optidrives should be installed only by qualified electrical persons and in accordance with
local and national regulations and codes of practice. The Optidrive has an Ingress Protection
rating of IP20. For higher IP ratings, use a suitable enclosure.
Electric shock hazard!
Disconnect and ISOLATE the Optidrive before attempting any work on
it. High voltages are present at the terminals and within the drive for up to 10 minutes after
disconnection of the electrical supply
Where supply to the drive is through a plug and socket connector, do not disconnect until 10
minutes have elapsed after turning off the supply
Ensure correct earthing connections
The earth cable must be sufficient to carry the maximum supply fault current which normally
will be limited by the fuses or MCB
SAFETY NOTICES
It is the responsibility of the installer to
ensure that the equipment or system into
which the product is incorporated complies
with the EMC legislation of the country of
use. Within the European Union, equipment
into which this product is incorporated must
comply with 89/336/EEC,Electromagnetic
Compatibility
.
WARRANTY
All Invertek Drives Ltd (IDL) products carry a
2-year warranty, valid from the date of
manufacture.
Complete Warranty Terms and Conditions
are available upon request from your IDL
Authorised Distributor.
WARNING
The level of integrity offered by
the Optidrive control functions – for
example stop/start, forward/reverse and
maximum speed, is not sufficient for use
in safety-critical applications without
independent channels of protection. All
applications where malfunction could
cause injury or loss of life must
be subject
to a risk assessment and further
protection provided where needed. Within
the European Union, all machinery in
which this product is used must comply
with Directive 89/392/EEC, Safety of
Machinery. In particular, the electrical
equipment should comply with EN60204-1.
OPTIDRIVE E1
Invertek Drives Ltd Tel: +44 (0) 1938 556868
Offa’s Dyke Business Park Fax: +44 (0) 1938 556869
Welshpool
Powys
email:
SY21 8JF
Internet:
www.invertek.co.uk
UK
Iss2.01
ELECTRICAL INSTALLATION
Connect drive according to diagram (above), ensuring that
motor terminal box connections are correct (see diagram,
below).
Refer to the
ELECTRICAL DATA
overleaf for the sizes of
cabling and wiring.
It is recommended that the power cabling should be 3-core or
4-core PVC-insulated screened cable, laid in accordance with
local industrial regulations and codes of practice.
CAUTION
Ensure that the supply voltage, frequency and no. of phases (1 or 3 phase) correspond to
the rating of the Optidrive as delivered.
An isolator should be installed between the power supply and the drive.
Never connect the mains power supply to the Output terminals U,V,W.
Protect the drive by using slow-blowing HRC fuses or MCB located in the mains supply of
the drive
Do not install any type of automatic switchgear between the drive and the motor
Wherever control cabling is close to power cabling, maintain a minimum separation of 100
mm and arrange crossings at 90
o
Ensure that screening or armouring of power cables is effected in accordance with the
connections diagram below
Ensure that all terminals are tightened to the appropriate torque (see table)
L
W
D
ENCLOSURE
W
D
H
HOLE
POSITIONS
FOR
MOUNTING
A
B
B
C
D
C
OPERATION – USING THE KEYPAD
MANAGING THE KEYPAD
When the drive is delivered from the factory, only the Standard
Parameter Set (see overleaf) is accessible.
To access the Standard Parameter Set
, press the Navigate key
⇔
for
>1 sec.
•
Scroll through P-01 to P-14 (and roll over to P-01) by pressing
or
•
To display the
parameter value
, press
⇔
•
To
edit
the parameter value, press or
•
To
return
to the parameter number, press
⇔
•
To
store
a value and / or
exit
from edit mode, press
⇔
for >1 sec
or press no button for >20 sec.
To
access the Extended Parameter Set
, set P-14 = 101 and press
⇔
NOTE
To restrict unauthorised access, make P-37 = any value from 0
to 9999.
•
When in the Extended Parameter Set (except P-00), the display
will revert to normal if no button is pressed for >20 sec.
Refer to the
Digital Inputs
table overleaf
for details of
the digital input
functions 1 to 3
If screened
cabling is used
for the control
wiring, connect
the cable
screen to 0V of
drive, terminals
7 or 9.
IMPORTANT SAFETY INFORMATION
Safety of machinery, and safety-critical applications
Optidrive hardware and software are designed and tested to a high standard and failures are
unlikely.
Electromagnetic Compatibility (EMC)
Optidrive is designed to high standards of EMC. EMC data is provided in a separate EMC
Data Sheet, available on request. Under extreme conditions, the product might cause or
suffer disturbance due to electromagnetic interaction with other equipment. It is the
responsibility of the installer to ensure that the equipment or system into which the product
is incorporated complies with the EMC legislation of the country of use. Within the European
Union, equipment into which this product is incorporated must comply with 89/336/EEC,
Electromagnetic Compatibility.
When installed as recommended in this User Guide, the radiated emissions levels of all
Optidrives are less than those defined in the Generic radiated emissions standard EN61000-
6-4. When fitted with an optional internal filter, the conducted emission levels are less than
those defined in the Generic radiated emissions standard EN61000-6-3 (class B) for
screened cable lengths of < 1m and with EN61000-6-4 (class A) for screened cable lengths of
< 5m.
SIMPLE PARAMETER ADJUSTMENTS
The factory-set default parameter values may give
satisfactory performance, however certain adjustments
may be beneficial.
Maximum and Minimum
Speeds
P-01 & P-02
Set P-01 to the maximum speed and P-02 to the
minimum speed for your application. These limits are
mirrored for negative speeds. If a non-zero minimum
speed is set in P-02, the motor will ramp (P-03) to this
minimum speed as soon as the drive is enabled.
Acceleration and Deceleration
P-03 & P04
Ramps which are too short will cause the drive to deliver
currents in excess of full load current and may result in
it tripping out or the motor stalling
Stop Mode
P-05
Select method of stopping required when drive is
disabled. Ramp to stop (P-05 = 0) decelerates the motor
at the rate set by deceleration ramp time P-04.
Freewheel/ Coast to stop (P-05=1) disables the drive
output immediately, allowing the motor to decelerate
naturally due to friction or under the control of a
mechanical brake
Torque/Speed Characteristic
P-06
Certain loads such as fans and centrifugal pumps need
very little torque at low speed. Set P-06=1 to reduce
power loss at low speeds for this load type.
Rated Current, Rated Frequency and Rated Speed
P-08,
P-09, P-10.
Parameters P-08 and P-09 should to be set to
correspond with the rated current and frequency shown
on the motor rating plate.
Parameter P-10 is optional. If this parameter is set to
zero (default state), speed will be displayed in Hz; if
speed indication is required in rpm, enter the motor
rated speed (speed at full load) from the motor rating
plate.
Voltage Boost
P-11
Any load which is ‘sticky’ to start will benefit from a
voltage boost on starting. P-11 permits a boost of up to
25% of full motor voltage to be applied.
NOTE: Use of this parameter increases motor heating at
low speeds
Terminal or Keypad Control
P-12
Terminal control (P-12=0) is used when the drive needs
to be controlled from some remote point, such as a
control panel interface or machine system.
Keypad control (P12=1 or 2) is used for local, manual
control and commissioning
Extended Parameter Set
P15 to P-40 and P-00
The Extended Parameter Set is intended for use by
specialist drives engineers and technicians and will not
generally be required for simple applications.
TO RESTORE ALL
DEFAULT VALUES
,
stop the drive and
when display shows
StoP, press and
hold the ,
and
STOP keys
simultaneously for 1
second. The display
will show P-dEF.
Access code P-37
will revert to 101 but
the hours-run meter
P-39 is not affected.
Press STOP to
resume normal
operation.
NAVIGATE
DISPLAY
START
RESET/ STOP
UP
DOWN
H 5 0 . 0
No connection