Optidrive HVAC User Guide V2.00
www.invertekdrives.com
47
11
Te
ch
n
ical
Da
ta
11.
Technical Data
11.1.
Environmental
A
mbient temperature range Operational
: -10 … 50
C (refer to section 11.5.1 on page 50 for derating information)
Storage
: -40
C … 60
C
Max altitude for rated operation
: 1000m (refer to section 11.5.2 on page 50 for derating information)
Relative Humidity
: < 95% (no condensation permitted)
11.2.
Input Voltage Ranges
Depending upon model and power rating, the drives are designed for direct connection to the following supplies:
Model Number
Supply Voltage
Phases
Frequency
ODV-2-x2xxx-1xxxx
200 – 240 Volts + 10% / -15%
1
50 – 60Hz
ODV-2-x2xxx-3xxxx
3
ODV-2-x4xxx-3xxxx
380 – 480 Volts +10% / - 15%
3
All Optidrive HVAC units have phase imbalance monitoring. A phase imbalance of > 3% will result in the drive tripping. For input supplies
which have supply imbalance greater than 3% (typically the Indian sub- continent & parts of Asia Pacific including China) Invertek Drives
recommends the installation of input line reactors. Alternatively, the drives can be operated as a single phase supply drive with 50% de-
rating.
11.3.
Output Power and Current ratings
The following tables provide the output current rating information for the various Optidrive HVAC models. Invertek Drives always recommend
that selection of the correct Optidrive is based upon the motor full load
current
at the incoming supply voltage.
200 – 240 Volts (+ / - 10%) 1 Phase Input, 3 Phase Output
kW
HP
Nominal
Input
Current
Fuse
Or
MCB
Supply
Cable
Size
Nominal
Output
Current
Motor
Cable
Size
Maximum
Motor
Cable
Length
A
Non UL
UL
mm
AWG / kcmil
A
mm
AWG / kcmil
m
feet
0.75
1
8.5
16
15
2.5
14
4.3
1.5
14
100
330
1.5
2
15.2
20
20
4
12
7
1.5
14
100
330
2.2
3
19.5
25
25
4
10
10.5
1.5
14
100
330
Note
The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable
length limit may be increased by 50%. When using the Invertek Drives recommended output choke, the maximum cable length may be
increased by 100%
The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the
motor terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the
motor. Invertek Drives recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life
For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses
200 – 240 Volts (+ / - 10%) 3 Phase Input, 3 Phase Output
kW
HP
Nominal
Input
Current
Fuse
Or
MCB
Supply
Cable
Size
Nominal
Output
Current
Motor
Cable
Size
Maximum
Motor
Cable
Length
A
Non UL
UL
mm
AWG / kcmil
A
mm
AWG / kcmil
m
feet
0.75
1
5.1
10
10
1.5
14
4.3
1.5
14
50
165
1.5
2
8.3
16
15
2.5
14
7
1.5
14
50
165
2.2
3
12.6
16
17.5
2.5
12
10.5
1.5
14
100
330
4
5
21.6
32
30
6
10
18
2.5
10
100
330
5.5
7.5
29.1
40
40
10
8
24
4
10
100
330
7.5
10
36.4
50
50
16
8
30
6
8
100
330
11
15
55.8
80
70
25
4
46
10
6
100
330
15
20
70.2
100
90
35
3
61
16
4
100
330
18.5
25
82.9
125
110
50
2
72
25
3
100
330
22
30
103.6
160
150
70
1
90
35
2
100
330
30
40
126.7
160
175
70
2/0
110
50
1/0
100
330
37
50
172.7
250
225
120
4/0
150
70
3/0
100
330
45
60
183.3
250
250
120
4/0
180
95
4/0
100
330
55
75
205.7
300
300
185
300
202
120
250
100
330
75
120
255.5
400
350
2 x 95
400
248
150
350
100
330