Optidrive ODE-2 User Guide Revision 3.20
26
www.invertekdrives.com
9
Te
ch
n
ical
Da
ta
9.
Technical Data
9.1.
Environmental
Operational ambient temperature range
Open Drives
:
-10 … 50°C (frost and condensation free)
Enclosed Drives
:
-10 ... 40°C (frost and condensation free)
Storage ambient temperature range
:
-40 … 60°C
Maximum altitude
:
2000m. Derate above 1000m : 1% / 100m
Maximum humidity
:
95%, non-condensing
NOTE
For UL compliance: the average ambient temperature over a 24 hour period for 200-240V, 2.2kW and 3HP, IP20 drives is 45°C.
9.2.
Rating Tables
110 - 115 Volt (+ / - 10%) 1 Phase Input, 3 Phase 230V Output
Frame
Size
kW
HP
Nominal
Fuse
Supply
Nominal
Motor
Maximum
Recommended
Input
Or
Cable
Output
Cable
Motor
Brake
Current
MCB (Type B)
Size
Current
Size
Cable
Resistance
Non UL
UL
mm
AWG / kcmil
mm
AWG / kcmil
Length
Ω
1
0.37
0.5
11.0
16
15
2.5
14
2.3
1.5
14
50
N/A
1
0.75
1
19.0
25
25
4
10
4.3
1.5
14
50
N/A
2
1.1
1.5
25.0
32
35
6
8
5.8
1.5
14
100
50
200 - 240 Volt (+ / - 10%) 1 Phase Input, 3 Phase Output
Fram
e
Size
kW
HP
Nominal
Fuse
Supply
Nominal
Output
Current
Motor
Maximum
Recommended
Input
Or
Cable
Cable
Motor
Brake
Current
MCB (Type B)
Size
Size
Cable
Resistance
Non UL
UL
mm
AWG / kcmil
mm
AWG / kcmil
Length
Ω
1
0.37
0.5
6.4
10
10
1.5
14
2.3
1.5
14
50
N/A
1
0.75
1
8.5
16
10
1.5
14
4.3
1.5
14
50
N/A
1
1.5
2
13.9
25
20
2.5
12
7
1.5
14
50
N/A
2
1.5
2
15.2
25
20
2.5
12
7
1.5
14
100
100
2
2.2
3
19.5
25
25
4
10
10.5
1.5
14
100
50
3
4
5
30.5
40
40
4
8
16
2.5
12
100
50
200 - 240 Volt (+ / - 10%) 3 Phase Input, 3 Phase Output
Frame
Size
kW
HP
Nominal
Fuse
Supply
Nominal
Motor
Maximum
Recommended
Input
Or
Cable
Output
Cable
Motor
Brake
Current
MCB (Type B)
Size
Current
Size
Cable
Resistance
Non UL UL (A)
mm
AWG / kcmil
mm
AWG / kcmil
Length
Ω
1
0.37
0.5
3.0
6
6
1.5
14
2.3
1.5
14
50
N/A
1
0.75
1
4.5
6
6
1.5
14
4.3
1.5
14
50
N/A
1
1.5
2
7.3
10
10
1.5
14
7
1.5
14
50
N/A
2
1.5
2
7.3
10
10
1.5
14
7
1.5
14
100
100
2
2.2
3
11.0
16
15
2.5
12
10.5
1.5
14
100
50
3
4
5
18.8
20
20
4
10
18
2.5
10
100
50
380 - 480 Volt (+ / - 10%) 3 Phase Input, 3 Phase Output
Frame
Size
kW
(400V)
HP
(460V)
Nominal
Input
Current
Fuse
Supply
Nominal
Motor
Maximum
Recommended
Or
Cable
Output
Cable
Motor
Brake
MCB (Type B)
Size
Current
Size
Cable
Resistance
Non
UL
UL (A)
mm
AWG / kcmil
mm
AWG / kcmil
Length
Ω
1
0.75
1
2.4
6
6
1.5
14
2.2
1.5
14
25
-
1
1.5
2
5.1
6
10
1.5
14
4.1
1.5
14
25
-
2
1.5
2
5.1
6
10
1.5
14
4.1
1.5
14
50
200
2
2.2
3
7.5
10
10
1.5
14
5.8
1.5
14
50
200
2
4
5
11.2
16
15
2.5
12
9.5
1.5
14
50
100
3
5.5
7.5
19.0
20
20
4
10
14
1.5
12
100
100
3
7.5
10
21.0
25
25
4
10
18
2.5
10
100
50
3
11
15
28.0
32
35
10
8
24
4
10
100
50
Note
: For UL compliance, Motor Cable to be 75°C Copper, fuse current ratings in brackets (), UL Class T must be used.