background image

Optidrive ODE-2 User Guide Revision 3.20 

 

www.invertekdrives.com 

15

 

 

4

 
Pow

er

 W

iri

n

4.9.

 

Using the REV/0/FWD Selector Switch (Switched Version Only) 

By adjusting the parameter settings the Optidrive can be configured for multiple applications and not just for Forward or Reverse. 
This could typically be for Hand/Off/Auto applications (also known and Local/Remote) for HVAC and pumping industries. 
 

 

 

 

 

 

Switch Position

 

Parameters to Set 

Notes

 

P-12 

P-15 

Run Reverse 

STOP 

Run Forward 

Factory Default Configuration 
Run Forward or Reverse with speed controlled from the 
Local POT 

STOP 

STOP 

Run Forward 

5,7 

Run forward with speed controlled form the local POT 
Run Reverse -  disabled 

Preset Speed 1 

STOP 

Run Forward 

Run Forward with speed controlled from the Local POT  
Preset Speed 1 provides a ‘Jog’ Speed set in P-20 

Run Reverse 

STOP 

Run Forward 

6, 8 

Run Forward or Reverse with speed controlled from the 
Local POT 

Run in Auto 

STOP 

Run in Hand 

Run in Hand – Speed controlled from the Local POT 
Run in Auto 0 Speed controlled using Analog input 2 e.g. 
from PLC with 4-20mA signal.  

Run in Speed Control 

STOP 

Run in PI Control 

In Speed Control the speed is controlled from the Local 
POT  
In PI Control, Local POT controls PI set point 

Run in Preset Speed 

Control 

STOP 

Run in PI Control 

0, 2, 4,5, 

8..12 

In Preset Speed Control, P-20 sets the Preset Speed 
In PI Control, POT can control the PI set point  
(P-44=1) 

Run in Hand 

STOP 

Run in Auto 

Hand – speed controlled from the Local POT  
Auto – Speed Reference from Modbus 

Run in Hand 

STOP 

Run in Auto 

Hand – Speed reference from Preset Speed 1 (P-20) 
Auto – Speed Reference from Modbus 

NOTE 

To be able to adjust parameter P-15, extended menu access must be set in P-14 (default value is 101) 

4.10.

 

Control Terminal Connections 

Default Connections 

Control 

Terminal 

Signal 

Description 

 

+24V User Output, 

+24V, 100mA. 

Digital Input 1 

Positive logic 
“Logic 1” input voltage range: 8V … 30V DC 
“Logic 0” input voltage range: 0V … 4V DC 

Digital Input 2 

Digital Input 3 / 

Analog Input 2 

Digital: 8 to 30V 
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA 

+10V User Output 

+10V, 10mA, 1kΩ minimum 

Analog Input 1 / 

Digital Input 4 

Analog: 0 to 10V, 0 to 20mA or 4 to 20mA 
Digital:  8 to 30V 

0V 

User ground connected terminal 9 

Analog Output / 

Digital Output 

Analog: 0 to 10V,  
Digital:  0 to 24V  

20mA maximum 

0V 

User ground connected terminal 7 

10 

Relay Common 

 

11 

Relay NO Contact 

Contact 250Vac, 6A / 30Vdc, 5A 

 

 

Summary of Contents for Optidrive ODE-2-11005-1H01 Series

Page 1: ...ptidrive ODE 2 User Guide Revision 3 20 www invertekdrives com 1 1 Introduction User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 11kW 0 5 15HP 110 480V Installation and Operating Instructions...

Page 2: ...13 Motor Nameplate Details Enter the motor rated voltage in P 07 Enter the motor rated current in P 08 Enter the motor rated frequency in P 09 Keypad operation can be found on page 16 Control Termina...

Page 3: ...nter the motor rated current in P 08 Enter the motor rated frequency in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse...

Page 4: ...cy in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse Ratings given on page 26 Recommended cable sizes shown on page 26...

Page 5: ...factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted For shielded motor cable lengths greater than 100m and...

Page 6: ...ctions 13 4 6 Motor Thermal overload Protection 14 4 7 Control Terminal Wiring 14 4 8 Connection Diagram 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4 10 Control Terminal Conne...

Page 7: ...ses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the drive control cables whilst power...

Page 8: ...50 1KB4 ODE 2 22150 1K04 1 5 ODE 2 22020 1HB4 ODE 2 22020 1H04 2 7 2 ODE 2 22220 1KB4 ODE 2 22220 1K04 2 2 ODE 2 22030 1HB4 ODE 2 22030 1H04 3 10 5 2 N A ODE 2 32040 1K04 2 4 0 N A ODE 2 32050 1H04 2...

Page 9: ...97 5 5 0 22 10 0 39 1 0 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 110 4 33 63 2 48 5 5 0 22 10 0 39 1 7 3 8 3 261 10 28 246 9 69 247 9 72 6 0 24 175 6 89 131 5 16 80 3 15 5 5 0 22 1...

Page 10: ...All Frame Sizes Control Terminals 0 5 Nm 4 5 lb in Power Terminals 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmen...

Page 11: ...For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched mo...

Page 12: ...tor ground must be connected to one of the ground terminals on the drive Ground Fault Monitoring As with all inverters a leakage current to earth can exist The Optidrive is designed to produce the min...

Page 13: ...t power supply faults Part numbers are shown in the table Supply Frame Size AC Input Inductor 230 Volt 1 Phase 1 OPT 2 L1016 20 2 OPT 2 L1025 20 3 N A 400 Volt 3 Phase 2 OPT 2 L3006 20 2 OPT 2 L3010 2...

Page 14: ...s of different voltages e g 24 Volt DC and 110 Volt AC should not be routed in the same cable Maximum control terminal tightening torque is 0 5Nm Control Cable entry conductor size 0 05 2 5mm2 30 12 A...

Page 15: ...un in PI Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Pres...

Page 16: ...turned to minimum 5 Turn the potentiometer to maximum The motor will accelerate to 50Hz the default value of P 01 under the control of the accelerating ramp time P 03 The display shows 50Hz at max sp...

Page 17: ...the motor P 10 Motor Rated Speed 0 30000 0 Rpm This parameter can optionally be set to the rated nameplate rpm of the motor When set to the default value of zero all speed related parameters are displ...

Page 18: ...1 0 0 Hz Rpm P 21 Preset Frequency Speed 2 P 02 P 01 0 0 Hz Rpm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected...

Page 19: ...ut Software Protection Enables the internal brake chopper without software protection An external thermal protection device should be fitted P 35 Analog Input 1 Scaling 0 0 500 0 100 0 Scales the anal...

Page 20: ...erence between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops suffi...

Page 21: ...y This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain operat...

Page 22: ...e or similar to digital input 3 7 Open Stop disable Closed Fwd Run enable Open Stop disable Closed Rev Run enable External trip input Open Trip Closed Run Analog input 1 reference Closing digital inpu...

Page 23: ...ton Open Keypad speed ref 24V Preset speed 1 3 1 Open Stop disable Closed Run enable Closed remote UP push button External trip input Open Trip Closed Run Closed remote DOWN push button Connect extern...

Page 24: ...trip input Open Trip Closed Run PI feedback analog input Connect external motor thermistor PTC type or similar to digital input 3 4 Normally Open NO Momentary close to run Normally Closed NC Momentary...

Page 25: ...2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Checksum...

Page 26: ...0 75 1 8 5 16 10 1 5 14 4 3 1 5 14 50 N A 1 1 5 2 13 9 25 20 2 5 12 7 1 5 14 50 N A 2 1 5 2 15 2 25 20 2 5 12 7 1 5 14 100 100 2 2 2 3 19 5 25 25 4 10 10 5 1 5 14 100 50 3 4 5 30 5 40 40 4 8 16 2 5 12...

Page 27: ...recommends the installation of input line reactors Frequency 50 60Hz 5 Variation Short Circuit Capacity Voltage Rating Min kW HP Max kW HP Maximum supply short circuit current 115V 0 37 0 5 1 1 1 5 5...

Page 28: ...vertek standard braking resistor is being used P 34 MUST be 1 Increase the deceleration time P 04 or 2nd deceleration time P 24 Reduce the load inertia For Other Brake Resistors Ensure the resistance...

Reviews: