Optidrive ODE-2 User Guide Revision 3.20
22
www.invertekdrives.com
7
A
n
al
og and
Di
gi
ta
l I
n
p
u
t
Co
n
fi
gu
ra
ti
on
s
7.
Analog and Digital Input Configurations
7.1.
Terminal Mode (P-12 = 0)
P-15
Digital input 1 (T2)
Digital input 2 (T3)
Digital input 3 (T4)
Analog input (T6)
Comments
0
Open: Stop (disable)
Closed: Run (enable)
Open : Forward run
Closed : Reverse run
Open : Analog speed ref
Closed : Preset speed 1
Analog input 1 reference
1
Open: Stop (disable)
Closed: Run (enable)
Open: Analog speed ref
Closed : Preset speed 1/2
Open: Preset speed 1
Closed : Preset speed 2
Analog input 1 reference
2
Open: Stop (disable)
Closed: Run (enable)
Digital Input 2
Digital Input 3
Preset Speed
Open: Preset speeds 1-4
Closed : Max Speed(P-01)
4 Preset speeds selectable.
Analog input used as digital
input Closed status: 8V < Vin
< 30V
Open
Open
Preset Speed 1
Closed
Open
Preset Speed 2
Open
Closed
Preset Speed 3
Closed
Closed
Preset Speed 4
3
Open: Stop (disable)
Closed: Run (enable)
Open : Analog speed ref
Closed : Preset speed 1
External trip input :
Open: Trip,
Closed: Run
Analog input 1 reference
Connect external motor
thermistor PTC type or
similar to digital input 3
4
Open: Stop (disable)
Closed: Run (enable)
Open : Analog input 1
Closed : Analog input 2
Analog input 2 reference Analog input 1 reference
Switches between analog
inputs 1 and 2
5
Open: Fwd Stop
Closed: Fwd Run
Open: Reverse Stop
Closed: Reverse Run
Open : Analog speed ref
Closed : Preset speed 1
Analog input 1 reference
Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)
6
Open: Stop (disable)
Closed: Run (enable)
Open : Forward
Closed : Reverse
External trip input :
Open: Trip,
Closed: Run
Analog input 1 reference
Connect external motor
thermistor PTC type or
similar to digital input 3
7
Open: Stop (disable)
Closed: Fwd Run (enable)
Open: Stop (disable)
Closed: Rev Run (enable)
External trip input :
Open: Trip,
Closed: Run
Analog input 1 reference
Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)
8
Open: Stop (disable)
Closed: Run (enable)
Open : Forward
Closed : Reverse
Digital Input 3
Analog Input 1
Preset Speed
Open
Open
Preset Speed 1
Closed
Open
Preset Speed 2
Open
Closed
Preset Speed 3
Closed
Closed
Preset Speed 4
9
Open: Stop (disable)
Closed: Forward Run
(enable)
Open: Stop (disable)
Closed: Reverse Run
(enable)
Digital Input 3
Analog Input 1
Preset Speed
Closing digital inputs 1 and 2
together carries out a fast
stop (P-24)
Open
Open
Preset Speed 1
Closed
Open
Preset Speed 2
Open
Closed
Preset Speed 3
Closed
Closed
Preset Speed 4
10
Normally Open (NO)
Momentary close to run
Normally Closed (NC)
Momentary open to stop
Open : Analog speed ref
Closed:Preset speed 1
Analog input 1 reference
11
Normally Open (NO)
Momentary close to run
Normally Closed (NC)
Momentary open to stop
Normally Open (NO)
Momentary close to rev
Analog input 1 reference
Closing digital inputs 1 and 3
together carries out a fast
stop (P-24)
12
Open: Stop (disable)
Closed: Run (enable)
Open: Fast Stop (disable)
Closed: Run (enable)
Open : Analog speed ref
Closed : Preset speed 1
Analog input 1 reference
NOTE
Negative Preset Speeds will be inverted if Run Reverse selected
Typical Applications
Terminal Mode P-12=0, P-15=0
Terminal Mode P-12=0, P-15 = 1
Terminal Mode P-12=0, P-15=2
+24 Volt
+24 Volt
+24 Volt
Run (Enable)
Run (Enable)
Run (Enable)
For / Rev
Analog / Preset
Preset Speeds 1 – 4
Select
Analog / Preset
Preset1 / Preset2
+ 10 Volts
+ 10 Volts
Reference
Reference
Preset / Max
0 Volts
0 Volts
Analog speed input with 1 preset speed and
fwd/rev switch
Analog speed input with 2 preset speeds
4 preset speeds and max speed select switch.
Effectively giving 5 preset speeds