P8-12 

Bypass Mode on Fire 

Parameter configures the drive to switch to bypass mode automatically should an input to the drive be configured for Fire Mode 
operation and that input becomes active. When enabled the drive standard relays 1 and 2 are dedicated to bypass control and 
cannot be assigned other functions. 
0 = Disabled 
1 = Enabled
 

P8-13 

Bypass Contactor Changeover Time 

30 

Parameter active when Bypass function is enabled. Parameter P8-05 sets a time delay or changeover time between the switching 
of the drive relays controlling the bypass circuitry. 

 

Care must be taken when setting P8-13 to ensure that drive and DOL contactors are not switched in circuit simultaneously. 
Both Mechanical and Electrical interlocking of drive and DOL contactors to regional standards are recommended in configuring 
the Bypass function 

P8-14 

Pump Staging Function Select 

Parameter enables the pump staging (cascade) function on the drive 
0 : Disabled 
1 : Single VFD with DOL Cascade (max 4 DOL pumps) 
2 : Multiple Drive Cascade (Optiflow) Master Drive (Only valid when drive set to Optibus master address, P5-01 = 1) 
3 : Multiple Drive Cascade with Jockey Pump (Optiflow) Master Drive (Only valid when drive set to Optibus master address, P5- 
01 = 1)
 In this instance, the Master drive (with address P5-01 =1) will remain active and will not be switched off to support the 
pump rotation ordinarily used for the purpose of sharing operating hours across all pumps. 
4 : Multiple Drive Cascade Mode 2 (Optiflow) Master Drive (Only valid when drive set to Optibus master address, P5-01 = 1) This 
mode is similar to mode 2 but the settling time works differently which can prevent multiple motors starting simultaneously when 
waking up from PID Standby mode 

P8-15 

Number of Assist Pumps 

1 

4 

1 

- 

Parameter valid when P8-14 is set to 1 or 2 to enable Pump Staging Function. P8-15 set the number of assist pumps (P8-14 = 1) or 
network slave drives (P8-14 = 2) that are available in the Pump Staging application. Setting the value to 0 disables Pump Staging. 

P8-16 

Pump Duty Switch Over Time 

1000 

Hours 

In order to balance run time (duty) on each pump in the Pump staging application and to ensure periodic operation of each pump P8-
16 can be set with a time limit for pump switch over. When set to a value other than 0 (disabled) the operation of each staging pump 
will be cycled to ensure the difference in duty between each pump  does not exceed the time set in P8-16 

P8-17 

Assist Pump Start Speed  

P8-18 

P1-01 

49.0 

Hz / RPM 

This parameter defines the speed at which an “Assist” Pump is started when using the Pump Cascade or Optiflow feature. When the 
drive output increases beyond this threshold the next Staging pump is switch on. The Pump staging settle time must then expire 
before additional staging pumps can be brought on or off line. Priority for Staging pump switch on is always given to the pump with 
lowest run time accumulated. 

P8-18 

Assist Pump Stop Speed  

0 

P8-17 

30.0 

Hz / RPM 

This parameter defines the speed at which an “Assist” Pump is stopped when using the Pump Cascade or Optiflow feature. When the 
drive output decreases below this threshold one of the Staging pumps currently operating is switch off. The Pump staging settle time 
must then expire before additional staging pumps can be brought on or off line. Priority for Staging pump switch off is always given to 
the pump with highest run time accumulated. 

P8-19 

Pump Settling Time 

2 

600 

60 

Secs 

Parameter sets a time delay for pump staging whereby, following switch in or switch out of a staging pump, further pumps are not 
permitted to be switched in or out until this time period has elapsed. This parameter should be set to allow adequate settle time 
between staging pump transitions. 

P8-20 

Pump Master Clock Reset 

0 

1 

0 

- 

Master drive in pump staging monitors and maintains duty run times for all available staging pumps. All clocks are available to view in 
P0-20. P8-20 provides the master reset to all run time clocks used for Pump Staging Function (all clocks set to 0). 

 

 

 

Summary of Contents for eco OPTIDRIVE

Page 1: ...Optidrive Eco Advanced User Guide Revision 1 00 Optidrive Eco Parameter Set Overview 1 AC Variable Speed Drive 0 75kW 250kW 1HP 350HP 200 480 Volt 1 3 Phase Advanced User Guide Revision 1 00...

Page 2: ...e time of release This user guide must be read in conjunction with the Optidrive Eco User Guide included with each product and in particular all relevant safety information and warnings The informatio...

Page 3: ...5 Parameter Group 0 Monitoring Parameters Read Only 25 1 6 P6 28 Value Selection 29 2 Diagnostic and Fault Messages 30 3 Immunity Tests 31 3 1 Electrostatic Discharge ESD 31 3 2 Electrical Fast Trans...

Page 4: ...c Read Write Group 2 P2 01 to P2 40 Extended Parameters Extended Read Write Group 3 P3 01 to P3 18 PID Controller Extended Read Write Group 4 P4 01 to P4 14 Motor Control Extended Read Write Group 5 P...

Page 5: ...d nameplate voltage of the motor Volts The factory default setting of this parameter is drive model dependent as follows All kW HP models intended for 200 240 volt operation e g ODV 3 x2xxx xxF1x xN F...

Page 6: ...from the fieldbus option module interface 5 Slave Mode The drive acts as a Slave to a connected Optidrive operating in Master Mode 6 BACnet MSTP Control Control via BACnet bus connected to the RJ45 s...

Page 7: ...requency reference applied to the drive is within the band the Optidrive output frequency will remain at the upper or lower limit of the band P2 11 Analog Output 1 Terminal 8 Function Select 0 12 8 Di...

Page 8: ...ve and no fault exists 2 At Target Frequency Speed Logic 1 when the output frequency matches the setpoint frequency Hysterisis is applied defined by P6 04 3 Output Frequency 0 0 Hz Logic 1 when the dr...

Page 9: ...rror Limit Logic 1 when the PID Error exceeds the adjustable threshold 15 High or Low load detected Logic 1 when the output current falls outside of the load monitoring profile See P8 06 to P8 08 P2 1...

Page 10: ...e signal level falls below 3mA 4 to 20mA Signal In the event that the signal falls below 3mA the Optidrive will ramp operate at Preset Speed 4 20 to 4mA Signal the Optidrive will trip and show the fau...

Page 11: ...Speed 4 P2 04 4 Minimum Speed Terminal Start Following a stop and restart the drive will always initially run at the minimum speed P1 02 The drive starting is controlled from the digital inputs based...

Page 12: ...applied to the Analog Input 1 P3 10 PID Feedback Signal Source Select 0 5 0 0 Analog Input 2 1 Analog Input 1 2 Motor Current The feedback value is scaled such that 100 0 P1 08 3 DC bus voltage The fe...

Page 13: ...gain value for the speed controller when operating in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 Higher values provide better output frequency regulation and response Too high a va...

Page 14: ...put 1 status bit 1 indicates digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heatsink Temperature 0 to 100 0 to 100 C 5 User Register 1 6 User Register 2 7 P0 80...

Page 15: ...s option to be used P9 38 must be set to 1 and the PID User setpoint must not be utilised within any Function Block Code 2 User register 3 The value received by the drive in PDI 3 is transferred to Us...

Page 16: ...d into the drive to operate When set to 0 the Function Block Program will be disabled P6 11 Speed Holding Time on Enable 0 250 0 s Defines a time period for which the drive will run at Preset Speed 7...

Page 17: ...A higher value may cause a significant distortion in the motor current which may cause an aggressive rough motor behaviour P7 10 System Inertia Constant 0 600 10 System Load Inertia to Motor Inertia...

Page 18: ...arameter enables the Load Profile Monitoring Function load current monitoring which can be used to detect belt failure in belt driven fan applications or Dry Pump Pump Blockage or broken impeller in P...

Page 19: ...mber of assist pumps P8 14 1 or network slave drives P8 14 2 that are available in the Pump Staging application Setting the value to 0 disables Pump Staging P8 16 Pump Duty Switch Over Time 0 1000 0 H...

Page 20: ...ng on their state Parameters defined as logic sources have the following range of possible settings No Drive LED Display Drive OLED Display Function 0 Off Safe Function permanently disabled or where a...

Page 21: ...n Forward or Run Reverse commands are applied from external sources e g Fieldbus control signals or a Function Block Program Logic 1 Drive operation is allowed Logic 0 Drive stops using deceleration r...

Page 22: ...d restart P9 18 Speed Reference Select Bit 0 Logic Source P9 19 Speed Reference Select Bit 1 Logic Source P9 20 Speed Reference Select Bit 2 Logic Source Note The active speed setpoint source can be s...

Page 23: ...n Module Drive Tripped Relay 5 Cascade Option Module Drive Running 1 Relay Output 1 Function set by User Defined Source P9 42 Clean Trigger Input Edge Trigger 0 25 0 This parameter defines the source...

Page 24: ...for various internal protection and monitoring functions P0 17 Stator Resistance Rs Ohms Displays the measured motor stator resistance providing an auto tune has been successfully completed P0 19 Casc...

Page 25: ...ay shows user resettable time reset with P6 22 Second display shows none resettable time This is used for scheduled maintenance information P0 36 DC Bus Voltage Log 256ms Volts Diagnostic log for DC b...

Page 26: ...alue in use for output relay settings that use hysteresis defined by P6 04 P0 62 Fire Mode Total Acitvation Counter Specifies the total number of times that Fire Mode has been activated on the drive P...

Page 27: ...ltage Volts Displays the supply voltage measured between L2 and L3 terminals for indication to the user P0 76 L3 L1 Input Voltage Volts Displays the supply voltage measured between L3 and L1 terminals...

Page 28: ...a 123 Function Block Program Cycle Time R Data 32 User analog output 1 RW Data 124 Function Block Program ID R Data 33 User analog output 2 RW Data Reserved R 34 Reserved RW Data 130 kWh meter user re...

Page 29: ...s trip P LOSS 14 Input phase loss trip SC F05 54 BACnet comms loss trip h O I 15 Instantaneous over current on drive output SC F06 55 Reserved th Flt 16 Faulty thermistor on heatsink SC F07 56 Reserve...

Page 30: ...e as defined in EN 61000 4 4 2004 Test points Test Method Level Control Terminals Capacitive clamp 1kV at 5kHz Motor Power Terminals Capacitive clamp 2kV at 5kHz 1 PH Supply Power Terminals Coupling D...

Page 31: ...Time Four individual deceleration ramps 0 600 seconds 0 01s resolution Frame 2 3 0 6000 seconds 0 1s resolution Frame 4 above 4 1 3 Overload Capacity Overload Capacity 110 of rated current for 60 seco...

Page 32: ...5 Maximum non condensing 4 3 4 Vibration Levels Bump Test Testing in each of three mutually perpendicular axes in turn Reference standard IEC 60068 2 29 Severity 18g 6ms half sine No of bumps 600 100...

Page 33: ...Current P1 08 The accumulator value reduces towards zero The time required depends on the actual load current as explained further below Motor Current 100 P1 08 The accumulator value remains static M...

Reviews: