Invertek Drives eco OPTIDRIVE Advanced User'S Manual Download Page 18

1.3.8.

 

Parameter Group 8 – Application Specific Parameters 

Par. 

Name 

Minimum 

Maximum 

Default 

Units 

P8-01 

Stir Interval Duration 

60000 

This parameter can be used to set a pre-defined period of inactivity, whereby if the drive remains in standby mode for a period of time 
exceeding the limit, stir function is activated, and the drive will operate at preset speed 7 (P2-07) for the time set in P8-02. This allows 
the pump to stir, preventing sediment from settling and avoiding a blockage. 

P8-02 

Pump Stir Activation Time 

6000 

10 

Set the time period that the stir function will be active once triggered (excludes time for deceleration to stop) 

P8-03 

Pump Clean Function Select 

This parameter configures the drive conditions that will cause activation of the automatic pump clean function. When activated, the 
pump clean will operate the pump at preset speed 5 (P2-05) for the time period set in P8-04, followed by Preset Speed 6 (P2- 06) 
(Providing P2-06 <> 0) for the time set in P8-04, before resuming normal operation. During the cleaning cycle, the ramp time set in P8-
05 is used for both acceleration and deceleration, and overrides P1-03 and P1-04. 
Where possible, P2-05 and P2-06 may be set to negative values, to allow the pump to be reversed. For best results, it is recommended 
to use as high a speed as possible, and to adjust P8-05 to allow a short acceleration time whilst avoiding over current trips. 
0 : Disabled 
1 : Active on start-up only.
 The pump cleaning function operates every time the pump is started. 
2 : Active on start-up and over-torque detection. The pump cleaning function operates every time the pump is started, and also in the 
event that the drive detects a possible pump blockage during normal operation. This requires the Load Profile Monitoring function to 
be active and commissioned for correct operation, see parameter P8-06. 
3 : Active on over-torque detection only. The pump cleaning function operates only when a possible pump blockage is detected 
during normal operation. This requires the Load Profile Monitoring function to be active and commissioned for correct operation, see 
parameter P8-06. Note: The pump clean function can also be activated by digital input configured in group 9 parameters 

P8-04 

Pump Cleaning Time 

600 

Sets the time period for the operation of the pump cleaning cycle. When bi-directional pump cleaning is selected, the time interval is 
used twice, once in each direction. 

P8-05 

Clean Function Ramp Time 

0.0 

6000 

30 

Independent ramp rate used only for the pump automatic cleaning function (see P8-03) when the motor is Accelerated as part of 
the cleaning cycle. 

P8-06 

Load Monitor Enable 

This parameter enables the Load Profile Monitoring Function (load current monitoring), which can be used to detect belt failure in belt 
driven fan applications, or Dry Pump, Pump Blockage or broken impeller in Pump applications. 
0: Disabled 
1: Low Load Detection Enabled 
(Belt Failure / Dry Pump / Broken Impeller) 
2: High Load Detection Enabled (Pump Blockage) 
3: Low and High Load Detection 
4: Low and High Load Detection
, warning only - bit 7 of the status word goes high in the event of a high or low load being detected 
but the drive will not trip 

 

 

Adjustment of parameter P8-06 (<>0) will cause the drive to automatically run the motor through its programmed frequency 
range upon the next drive enable (input enable). Ensure the application is in a suitable condition to allow the motor to run 
safely through its frequency range prior to enabling this feature. 

P8-07 

Load Profile Bandwidth 

0.1 

50.0 

1.0 

This parameter sets a bandwidth around the Load profile generated by P8-06. If P8-06 has been set to an appropriate value to 
detect an over /under load condition and the drive operates outside of the bandwidth set in P8-07 for a period longer than that 
defined by P8-08 then the drive will trip. Value entered in P8-07 is the value between the normal current and the trip level, hence 
total bandwidth for the function is 2 x P8-07. 

P8-08 

Load Monitor Trip Delay 

60 

This parameter sets a time limit for the Load profile generated by P8-06. If P8-06 has been set to an appropriate value to detect an 
over /under load condition and the drive operates outside of the bandwidth set in P8-07 for a period longer than that defined by 
P8-08 and then the drive will trip. 

P8-09 

Fire Mode Logic 

When Fire mode is assigned to a digital input on the drive then the logic configuration for the input is set by P8-09 to allow 
normally open or normally closed activation. Default behaviour is for Input logic off (0) to activate fire mode (Open activation). 
Input configuration for Fire mode is set by parameter P1-13 or can be user defined by the setting of P9-32. 
0 : Open Activation 
1 : Closed Activation
 

P8-10 

Fire Mode Speed 

-P1-01 

P1-01 

Hz 

When set to a non-zero value, this parameter sets an operational fixed frequency / speed used when Fire Mode is selected. The 
drive will maintain operation at this frequency until the fire mode signal is removed or the drive is no longer able to sustain 
operation. 
When P8-10 is zero, and fire mode is activated, the drive will continue to operate under the control of the selected speed 
reference, dependent on parameter settings and digital input selection. 

P8-11 

Bypass Mode on Fault 

Parameter configures the drive to switch to bypass mode automatically should a trip occur on the drive. When enabled the drive 
standard relays 1 and 2 are dedicated to bypass control and cannot be assigned other functions. 
0 : Disabled 
1 : Enabled 

Summary of Contents for eco OPTIDRIVE

Page 1: ...Optidrive Eco Advanced User Guide Revision 1 00 Optidrive Eco Parameter Set Overview 1 AC Variable Speed Drive 0 75kW 250kW 1HP 350HP 200 480 Volt 1 3 Phase Advanced User Guide Revision 1 00...

Page 2: ...e time of release This user guide must be read in conjunction with the Optidrive Eco User Guide included with each product and in particular all relevant safety information and warnings The informatio...

Page 3: ...5 Parameter Group 0 Monitoring Parameters Read Only 25 1 6 P6 28 Value Selection 29 2 Diagnostic and Fault Messages 30 3 Immunity Tests 31 3 1 Electrostatic Discharge ESD 31 3 2 Electrical Fast Trans...

Page 4: ...c Read Write Group 2 P2 01 to P2 40 Extended Parameters Extended Read Write Group 3 P3 01 to P3 18 PID Controller Extended Read Write Group 4 P4 01 to P4 14 Motor Control Extended Read Write Group 5 P...

Page 5: ...d nameplate voltage of the motor Volts The factory default setting of this parameter is drive model dependent as follows All kW HP models intended for 200 240 volt operation e g ODV 3 x2xxx xxF1x xN F...

Page 6: ...from the fieldbus option module interface 5 Slave Mode The drive acts as a Slave to a connected Optidrive operating in Master Mode 6 BACnet MSTP Control Control via BACnet bus connected to the RJ45 s...

Page 7: ...requency reference applied to the drive is within the band the Optidrive output frequency will remain at the upper or lower limit of the band P2 11 Analog Output 1 Terminal 8 Function Select 0 12 8 Di...

Page 8: ...ve and no fault exists 2 At Target Frequency Speed Logic 1 when the output frequency matches the setpoint frequency Hysterisis is applied defined by P6 04 3 Output Frequency 0 0 Hz Logic 1 when the dr...

Page 9: ...rror Limit Logic 1 when the PID Error exceeds the adjustable threshold 15 High or Low load detected Logic 1 when the output current falls outside of the load monitoring profile See P8 06 to P8 08 P2 1...

Page 10: ...e signal level falls below 3mA 4 to 20mA Signal In the event that the signal falls below 3mA the Optidrive will ramp operate at Preset Speed 4 20 to 4mA Signal the Optidrive will trip and show the fau...

Page 11: ...Speed 4 P2 04 4 Minimum Speed Terminal Start Following a stop and restart the drive will always initially run at the minimum speed P1 02 The drive starting is controlled from the digital inputs based...

Page 12: ...applied to the Analog Input 1 P3 10 PID Feedback Signal Source Select 0 5 0 0 Analog Input 2 1 Analog Input 1 2 Motor Current The feedback value is scaled such that 100 0 P1 08 3 DC bus voltage The fe...

Page 13: ...gain value for the speed controller when operating in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 Higher values provide better output frequency regulation and response Too high a va...

Page 14: ...put 1 status bit 1 indicates digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heatsink Temperature 0 to 100 0 to 100 C 5 User Register 1 6 User Register 2 7 P0 80...

Page 15: ...s option to be used P9 38 must be set to 1 and the PID User setpoint must not be utilised within any Function Block Code 2 User register 3 The value received by the drive in PDI 3 is transferred to Us...

Page 16: ...d into the drive to operate When set to 0 the Function Block Program will be disabled P6 11 Speed Holding Time on Enable 0 250 0 s Defines a time period for which the drive will run at Preset Speed 7...

Page 17: ...A higher value may cause a significant distortion in the motor current which may cause an aggressive rough motor behaviour P7 10 System Inertia Constant 0 600 10 System Load Inertia to Motor Inertia...

Page 18: ...arameter enables the Load Profile Monitoring Function load current monitoring which can be used to detect belt failure in belt driven fan applications or Dry Pump Pump Blockage or broken impeller in P...

Page 19: ...mber of assist pumps P8 14 1 or network slave drives P8 14 2 that are available in the Pump Staging application Setting the value to 0 disables Pump Staging P8 16 Pump Duty Switch Over Time 0 1000 0 H...

Page 20: ...ng on their state Parameters defined as logic sources have the following range of possible settings No Drive LED Display Drive OLED Display Function 0 Off Safe Function permanently disabled or where a...

Page 21: ...n Forward or Run Reverse commands are applied from external sources e g Fieldbus control signals or a Function Block Program Logic 1 Drive operation is allowed Logic 0 Drive stops using deceleration r...

Page 22: ...d restart P9 18 Speed Reference Select Bit 0 Logic Source P9 19 Speed Reference Select Bit 1 Logic Source P9 20 Speed Reference Select Bit 2 Logic Source Note The active speed setpoint source can be s...

Page 23: ...n Module Drive Tripped Relay 5 Cascade Option Module Drive Running 1 Relay Output 1 Function set by User Defined Source P9 42 Clean Trigger Input Edge Trigger 0 25 0 This parameter defines the source...

Page 24: ...for various internal protection and monitoring functions P0 17 Stator Resistance Rs Ohms Displays the measured motor stator resistance providing an auto tune has been successfully completed P0 19 Casc...

Page 25: ...ay shows user resettable time reset with P6 22 Second display shows none resettable time This is used for scheduled maintenance information P0 36 DC Bus Voltage Log 256ms Volts Diagnostic log for DC b...

Page 26: ...alue in use for output relay settings that use hysteresis defined by P6 04 P0 62 Fire Mode Total Acitvation Counter Specifies the total number of times that Fire Mode has been activated on the drive P...

Page 27: ...ltage Volts Displays the supply voltage measured between L2 and L3 terminals for indication to the user P0 76 L3 L1 Input Voltage Volts Displays the supply voltage measured between L3 and L1 terminals...

Page 28: ...a 123 Function Block Program Cycle Time R Data 32 User analog output 1 RW Data 124 Function Block Program ID R Data 33 User analog output 2 RW Data Reserved R 34 Reserved RW Data 130 kWh meter user re...

Page 29: ...s trip P LOSS 14 Input phase loss trip SC F05 54 BACnet comms loss trip h O I 15 Instantaneous over current on drive output SC F06 55 Reserved th Flt 16 Faulty thermistor on heatsink SC F07 56 Reserve...

Page 30: ...e as defined in EN 61000 4 4 2004 Test points Test Method Level Control Terminals Capacitive clamp 1kV at 5kHz Motor Power Terminals Capacitive clamp 2kV at 5kHz 1 PH Supply Power Terminals Coupling D...

Page 31: ...Time Four individual deceleration ramps 0 600 seconds 0 01s resolution Frame 2 3 0 6000 seconds 0 1s resolution Frame 4 above 4 1 3 Overload Capacity Overload Capacity 110 of rated current for 60 seco...

Page 32: ...5 Maximum non condensing 4 3 4 Vibration Levels Bump Test Testing in each of three mutually perpendicular axes in turn Reference standard IEC 60068 2 29 Severity 18g 6ms half sine No of bumps 600 100...

Page 33: ...Current P1 08 The accumulator value reduces towards zero The time required depends on the actual load current as explained further below Motor Current 100 P1 08 The accumulator value remains static M...