Invertek Drives eco OPTIDRIVE Advanced User'S Manual Download Page 13

Optidrive Eco Advanced User Guide Revision 1.00 

Opt

idr

ive 

Eco 

Par

am

et

er

 Set Ov

er

vi

ew

 

1

 

1.3.4.

 

Parameter Group 4 – High Performance Motor Control 

Par. 

Name 

Minimum 

Maximum 

Default 

Units 

 

Incorrect adjustment of parameters in menu group 4 can cause unexpected behaviour of the motor and any connected machinery. 

It is recommended that these parameters are only adjusted by experienced users. 

P4-01 

Motor Control Mode 

Selects the motor control method. An autotune should be performed for all modes but is mandatory for modes 2 - 5. 
0 : Eco Vector Speed Control (VT). Suitable for use with AC induction motors with a variable torque load such as centrifugal fans or 
pumps where the voltage to frequency characteristic follows a quadratic relationship. 
1 : Eco Vector Speed Control (CT). Suitable for use with AC induction motors with a constant torque load such as blowers or positive 
displacement pumps where the voltage to frequency characteristic follows a linear relationship.. 
2 : IM Vector Speed Control. 
 Similar to mode 1 but requires more accurate motor information including motor power factor P4-05. 
3 : PM Motor Vector Speed Control. Equivalent to setting 1, but intended for operation of Permanent Magnet motors.  
4 : BLDC Motor Speed Control. For operation of Brushless DC Motors. 
5 : SynRel Motor Speed Control. For operation of Synchronous Reluctance Motors. 

P4-02 

Motor Parameter Auto-tune Enable 

When set to 1, the drive immediately carries out an autotune to measure the motor parameters for optimum control and efficiency. 
Following completion of the autotune, the parameter automatically returns to 0. 

Note 

All motor nameplate data should be programmed into the drive, e.g. P1-07, P1-08, P1-09 and P4-05 prior to starting the autotune 

 

Whilst the autotune does not require the motor to rotate, it may still cause some movement of the motor shaft, 
thereby it is important to ensure that the motor and load are safe to operate prior to starting the autotune. 
The autotune does not require the load to be removed from the motor, however the motor brake should be 
released providing it is safe to do so. The motor must be stationary during the auto-tune procedure, if the motor 
is rotating then the auto-tune will fail or incorrect motor data will be measured by the drive.
 

P4-03 

Vector Speed Controller Proportional Gain 

0.1 

400.0 

50.0 

Sets the proportional gain value for the speed controller when operating in Vector Speed or Vector Torque motor control modes (P4-
01 = 0 or 1). Higher values provide better output frequency regulation and response. Too high a value can cause the speed to 
overshoot the setpoint during acceleration, and may also cause speed instability and possibly over current trips. For applications 
requiring best possible performance, the value should be adjusted to suit the connected load by gradually increasing the value and 
monitoring the actual output speed of the load until the required dynamic behaviour is achieved with little or no overshoot of the 
target speed during acceleration and deceleration. 
In general, higher friction loads can tolerate higher values of proportional gain, and high inertia, low friction loads may require the gain 
to be reduced. 

P4-04 

Vector Speed Controller Integral Time Constant 

0.010 

2.000 

0.050 

Seconds 

Sets the integral time for the speed controller. Smaller values provide a faster response in reaction to motor load changes, at the risk 
of introducing instability. For best dynamic performance, the value should be adjusted to suit the connected load. 

P4-05 

Motor Power Factor Cos Ø 

0.00 

0.99 

When operating in Vector Speed or Vector Torque motor control modes, this parameter must be set to the motor nameplate power 
factor before an autotune is carried out. 

P4-07 

Maximum Motoring Torque Limit 

P4-08 

150.0 

110.0 

This parameter defines the maximum torque limit (or current limit) of the drive 

P4-12 

Motor Thermal Memory Retention 

0 : Disabled. The present value of the motor overload accumulator is not stored during power off. 
1 : Enabled. 
The value of the motor thermal overload accumulator is stored during power off. 
Whilst the motor is being operated, the drive continuously monitors the output current over a time period, to determine the likely 
operating temperature of the motor. If the motor operates at high current for a period of time, the drive may trip to protect the motor 
and prevent damage. When this function is disabled (default setting), removing the power supply from the drive will result in the 
thermal overload value for the motor being reset to zero, hence the motor could potentially be operated and damaged. By enabling 
this parameter, even if the mains power is removed from the drive, the value is retained, and reused at the next power on, in order to 
avoid the risk of damage to the motor. 

P4-13 

Output Phase Sequence 

0 : U, V, W.  
1 : U, W, V. 
Direction of motor rotation when operating in a forward direction will be reversed. 

 
 

 

Summary of Contents for eco OPTIDRIVE

Page 1: ...Optidrive Eco Advanced User Guide Revision 1 00 Optidrive Eco Parameter Set Overview 1 AC Variable Speed Drive 0 75kW 250kW 1HP 350HP 200 480 Volt 1 3 Phase Advanced User Guide Revision 1 00...

Page 2: ...e time of release This user guide must be read in conjunction with the Optidrive Eco User Guide included with each product and in particular all relevant safety information and warnings The informatio...

Page 3: ...5 Parameter Group 0 Monitoring Parameters Read Only 25 1 6 P6 28 Value Selection 29 2 Diagnostic and Fault Messages 30 3 Immunity Tests 31 3 1 Electrostatic Discharge ESD 31 3 2 Electrical Fast Trans...

Page 4: ...c Read Write Group 2 P2 01 to P2 40 Extended Parameters Extended Read Write Group 3 P3 01 to P3 18 PID Controller Extended Read Write Group 4 P4 01 to P4 14 Motor Control Extended Read Write Group 5 P...

Page 5: ...d nameplate voltage of the motor Volts The factory default setting of this parameter is drive model dependent as follows All kW HP models intended for 200 240 volt operation e g ODV 3 x2xxx xxF1x xN F...

Page 6: ...from the fieldbus option module interface 5 Slave Mode The drive acts as a Slave to a connected Optidrive operating in Master Mode 6 BACnet MSTP Control Control via BACnet bus connected to the RJ45 s...

Page 7: ...requency reference applied to the drive is within the band the Optidrive output frequency will remain at the upper or lower limit of the band P2 11 Analog Output 1 Terminal 8 Function Select 0 12 8 Di...

Page 8: ...ve and no fault exists 2 At Target Frequency Speed Logic 1 when the output frequency matches the setpoint frequency Hysterisis is applied defined by P6 04 3 Output Frequency 0 0 Hz Logic 1 when the dr...

Page 9: ...rror Limit Logic 1 when the PID Error exceeds the adjustable threshold 15 High or Low load detected Logic 1 when the output current falls outside of the load monitoring profile See P8 06 to P8 08 P2 1...

Page 10: ...e signal level falls below 3mA 4 to 20mA Signal In the event that the signal falls below 3mA the Optidrive will ramp operate at Preset Speed 4 20 to 4mA Signal the Optidrive will trip and show the fau...

Page 11: ...Speed 4 P2 04 4 Minimum Speed Terminal Start Following a stop and restart the drive will always initially run at the minimum speed P1 02 The drive starting is controlled from the digital inputs based...

Page 12: ...applied to the Analog Input 1 P3 10 PID Feedback Signal Source Select 0 5 0 0 Analog Input 2 1 Analog Input 1 2 Motor Current The feedback value is scaled such that 100 0 P1 08 3 DC bus voltage The fe...

Page 13: ...gain value for the speed controller when operating in Vector Speed or Vector Torque motor control modes P4 01 0 or 1 Higher values provide better output frequency regulation and response Too high a va...

Page 14: ...put 1 status bit 1 indicates digital input 2 status etc 3 Analog Input 2 Signal Level 0 to 1000 0 to 100 0 4 Drive Heatsink Temperature 0 to 100 0 to 100 C 5 User Register 1 6 User Register 2 7 P0 80...

Page 15: ...s option to be used P9 38 must be set to 1 and the PID User setpoint must not be utilised within any Function Block Code 2 User register 3 The value received by the drive in PDI 3 is transferred to Us...

Page 16: ...d into the drive to operate When set to 0 the Function Block Program will be disabled P6 11 Speed Holding Time on Enable 0 250 0 s Defines a time period for which the drive will run at Preset Speed 7...

Page 17: ...A higher value may cause a significant distortion in the motor current which may cause an aggressive rough motor behaviour P7 10 System Inertia Constant 0 600 10 System Load Inertia to Motor Inertia...

Page 18: ...arameter enables the Load Profile Monitoring Function load current monitoring which can be used to detect belt failure in belt driven fan applications or Dry Pump Pump Blockage or broken impeller in P...

Page 19: ...mber of assist pumps P8 14 1 or network slave drives P8 14 2 that are available in the Pump Staging application Setting the value to 0 disables Pump Staging P8 16 Pump Duty Switch Over Time 0 1000 0 H...

Page 20: ...ng on their state Parameters defined as logic sources have the following range of possible settings No Drive LED Display Drive OLED Display Function 0 Off Safe Function permanently disabled or where a...

Page 21: ...n Forward or Run Reverse commands are applied from external sources e g Fieldbus control signals or a Function Block Program Logic 1 Drive operation is allowed Logic 0 Drive stops using deceleration r...

Page 22: ...d restart P9 18 Speed Reference Select Bit 0 Logic Source P9 19 Speed Reference Select Bit 1 Logic Source P9 20 Speed Reference Select Bit 2 Logic Source Note The active speed setpoint source can be s...

Page 23: ...n Module Drive Tripped Relay 5 Cascade Option Module Drive Running 1 Relay Output 1 Function set by User Defined Source P9 42 Clean Trigger Input Edge Trigger 0 25 0 This parameter defines the source...

Page 24: ...for various internal protection and monitoring functions P0 17 Stator Resistance Rs Ohms Displays the measured motor stator resistance providing an auto tune has been successfully completed P0 19 Casc...

Page 25: ...ay shows user resettable time reset with P6 22 Second display shows none resettable time This is used for scheduled maintenance information P0 36 DC Bus Voltage Log 256ms Volts Diagnostic log for DC b...

Page 26: ...alue in use for output relay settings that use hysteresis defined by P6 04 P0 62 Fire Mode Total Acitvation Counter Specifies the total number of times that Fire Mode has been activated on the drive P...

Page 27: ...ltage Volts Displays the supply voltage measured between L2 and L3 terminals for indication to the user P0 76 L3 L1 Input Voltage Volts Displays the supply voltage measured between L3 and L1 terminals...

Page 28: ...a 123 Function Block Program Cycle Time R Data 32 User analog output 1 RW Data 124 Function Block Program ID R Data 33 User analog output 2 RW Data Reserved R 34 Reserved RW Data 130 kWh meter user re...

Page 29: ...s trip P LOSS 14 Input phase loss trip SC F05 54 BACnet comms loss trip h O I 15 Instantaneous over current on drive output SC F06 55 Reserved th Flt 16 Faulty thermistor on heatsink SC F07 56 Reserve...

Page 30: ...e as defined in EN 61000 4 4 2004 Test points Test Method Level Control Terminals Capacitive clamp 1kV at 5kHz Motor Power Terminals Capacitive clamp 2kV at 5kHz 1 PH Supply Power Terminals Coupling D...

Page 31: ...Time Four individual deceleration ramps 0 600 seconds 0 01s resolution Frame 2 3 0 6000 seconds 0 1s resolution Frame 4 above 4 1 3 Overload Capacity Overload Capacity 110 of rated current for 60 seco...

Page 32: ...5 Maximum non condensing 4 3 4 Vibration Levels Bump Test Testing in each of three mutually perpendicular axes in turn Reference standard IEC 60068 2 29 Severity 18g 6ms half sine No of bumps 600 100...

Page 33: ...Current P1 08 The accumulator value reduces towards zero The time required depends on the actual load current as explained further below Motor Current 100 P1 08 The accumulator value remains static M...

Reviews: