27
EN
refrigerant contained in them.
-Cylinders shall be kept upright.
-Ensure that the refrigeration system is earthed prior to charging the system with
refrigerant.
-label the system when charging is complete (if not already)
-Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system is shall be pressure tested with OFN. The system shall be
leak tested on completion of charging but prior to commissioning. A follow up leak test
shall be carried out prior to leaving the site.
16. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants
are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall
be taken is case analysis is required prior to re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task is commenced.
a) become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that;
Mechanical handling equipment is available and being used correctly; the recovery process
is supervised at all times by a competent person; recovery equipment and cylinders
conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible , make a manifold so that refrigerant can be removed from
various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer’s
instructions.
h) Do not overfill cylinders. (No more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure
that the cylinders and the equipment are removed from site promptly and all isolation
valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it
has been cleaned and checked.
17. Labeling
Equipment shall be labeled stating that it has been de-commissioned and emptied of
refrigerant. The label shall be dated and signed. Ensure that there are labels on the
equipment stating the equipment contains flammable refrigerant.
18. Recovery
When removing refrigerant from a system, either for servicing or decommissioning,
it is recommended good practice that all refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed. Ensure that the correct number
of cylinders for holding the total system charge are available. All cylinders to be used
are designated for the recovered refrigerant and labeled for that refrigerant(i.e special
cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief
valve and associated shut-off valves in good working order. Empty recovery cylinders are
evacuated and , if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set with a set of instructions
concerning the equipment that is at hand and shall be suitable for the recovery of
flammable refrigerants.
Summary of Contents for ATM-25L
Page 2: ...LANGUAGES ENGLISH 3 31 ROMANA 59 DEUTSCH 85 FRAN AIS 113 ITALIANO 141 ESPA OL 169...
Page 30: ......
Page 32: ...32 GR 1 l 220 240V 50Hz l l l 30 l l l l l l l 8 l l l l l l l l l 3 l...
Page 33: ...33 GR l l l l l l l l l l l l l l l 24...
Page 34: ...34 GR 2 l l l l l l l l PCB T 3 15A 250V 350V 3 l 2002 96 EC 27 2003 l CO2 l A B...
Page 35: ...35 GR 4 R290 l l To R290 95g R290 l l R290 R290...
Page 36: ...36 GR 5 SN D2002255780115715200209 SN D2002255780115715200209 A SN...
Page 37: ...37 GR A 1 20cm 40cm 2 5 C 5 C 5 C 35 C 30 90 3 4 2 5...
Page 38: ...38 GR 6 HEPA...
Page 43: ...43 GR INDICATOR LIGHT CHILD LOCK Indicator Light 3 Child Lock WATER FULL WATER FULL WATER FULL...
Page 45: ...45 GR Lo 30 Lo 32 Hi 91 Hi 90 8 TIMER...
Page 46: ...46 GR 9 1 2...
Page 47: ...47 GR x...
Page 48: ...48 GR 15 10 l o l 2 l HEPA 30...
Page 49: ...49 GR 11 24 12 HEPA 45 55...
Page 50: ...50 GR Mode Dryer Cont Smart Dryer Cont Smart 5 C 41 F 24 2018...
Page 51: ...51 GR l l l l l l l l l l l l l l l l l l l l l l l...
Page 52: ...52 GR C1 C2 C8 3 C POWER 10 13 R290 1 2 3 4...
Page 53: ...53 GR CO2 5 6 7 8...
Page 54: ...54 GR 9 10 11 12 13 O LFL 25...
Page 55: ...55 GR 14 15 16...
Page 56: ...56 GR 80 17 18...
Page 57: ...57 GR 211 300 3300 www inventoraircondition gr media library 19 20 21 22...
Page 197: ......
Page 198: ...NOTES...
Page 199: ......
Page 200: ...v 1 1 DEHUMIDIFIER AIR PURIFIER...