The corresponding connection diagrams and assembly steps for installing the controller are not
part of this documentation! They can be found in the installation instructions for the respective
control unit. (sMove, MZ-Home, inVENTer Connect controller platform).
21
INSTALLATION AND ASSEMBLY
21
iV-Smart+ ventilation unit | Installation instructions
Principle sketches for cable laying
inVENTer Connect controller platform
sMove and MZ-Home controllers
System communication by radio:
Cable NYM-J, wire cross-section 1.5 mm²
Ventilation unit 1
Control unit:
Connect inner cover
House distributor
Ventilation unit n
Control unit:
Connect inner cover
Operating unit:
Easy Connect e16
System communication by cable:
RS485 data cable,
Cross-section 0.25 - 0.5 mm²,
Length max. 500 m
Cable NYM-J, wire cross-section 1.5 mm²
Ventilation unit n
Control unit:
Connect inner cover
Ventilation unit 1
Control unit:
Connect inner cover
House distributor
Operating unit:
Easy Connect e16
230 V AC
One after the other:
Star-shaped:
Cable type LiYY, 3-wire, wire cross-section 0.75 mm
2
,
length see
controller
Cable type LiYY, 3-wire,
wire cross-section 0.75 mm²,
length max. 33 m
Switching power
supply unit
Control unit:
sMove: Control unit
MZ-Home: Clust-Air module
Terminal
blocks
Ventilation units
Ventilation
units
Operated in pairs
Operated in pairs
Operated in
pairs
Operated in
pairs
Control unit:
sMove: Control unit
MZ-Home: Clust-Air module
Switching power
supply unit
6 – 16 V DC
230 V AC
6 – 16 V DC