59
10. Troubleshooting for single membrane controller
Error
Cause
Remedy
No display
-
Cable bridge (s. section 6.1) not
inserted
-
Plug in cable bridge
-
No 24 V voltage supply and
battery has discharged
-
Display cable is loose or
defective
-
Check AC switching power
mains supply; recharge battery
via internal charging switch. *
-
Check display cable or change
display
Battery operating mode
display
Note: After approx. 2 hours the
battery is discharged
-
Power failure
-
24 V switching power supply is
not connected
-
24 V switching power supply is
defective
-
Wait for power to come back on
-
Connect AC switching power
supply
-
Replace AC switching power
supply
Display after power failure
Note: Flashing LCD and audible
signal ON/OFF (1 sec / 1 sec
)
-
Display (for 30 sec) after power
failure of 24 V voltage supply
-
Check the number of failures in
status mode in a period, within
24 h for instance. If the number
increases and the reason is not a
general power failure, then the
power supply must be changed.
Display after power failure
Note: Flashing LCD and audible
signal ON/OFF (1 sec. / 1sec.
)
-
Display after power failure
during pump cycle
-
Check pumps in test menu. If
there is a power failure in test
mode, then check for defect in
respective pump or power
supply.
No water filters in the
filtration cycle
-
Incorrectly installed float switch
BRmin or Clmax or defective
-
Defective filtration pump
-
Check the position and function
of float switch and replace if
necessary
-
Check filtration pump in test
mode and replace if necessary
Low operating life of
membrane(s)
-
Backwash pump does not clean
the membrane regularly
-
Leakage clogs the membrane
fibres
-
Check backwash pump in test
mode (s. section 9.3) and
replace if necessary
-
Perform water-tight test (s.
section 9.1) and fix source of
leak if possible
Summary of Contents for AQUALOOP GW 10800
Page 12: ...11 Fig AQUALOOP System 1200 L day 317 GPD Fig AQUALOOP System 1800 L day 476 GPD...
Page 13: ...12 Fig AQUALOOP System 3600 L day 952GPD Fig AQUALOOP System 5400 L day 1428 GPD...
Page 37: ...36 Fig Electrical connection plan upper pump lower pump...
Page 39: ...38 Fig Control cabinet of multiple membrane station controller...
Page 42: ...41 7 1 3 Expansion membrane station controller Fig Control cabinet of expansion controller...
Page 89: ...88 Designed and provided by INTEWA GmbH or to be separately approved alternative...
Page 90: ...89 INTEWA GmbH Version 1 1 a Subject to technical changes...