IntesisBox
®
BACnet/IP Server - Modbus RTU Master
User’s Manual r14 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SL
URL
Email
tel
http://www.intesis.com
[email protected]
+34 938047134
18 / 27
Dev
Description
Device number to which belongs the point. Referenced to the list of devices
defined in
Connection Tab (
Values
From 1 to 254
Edit mode
Text edit or AutoEnumeration
Comments
This is not the slave number configured in the Modbus device itself, it is just
the order of the device (from top to bottom) in the devices list
Modbus
Code
Description
Modbus function code to be used by IntesisBox to read, to write or to
read/write the point in the slave device.
Values
0-
Communication Error
1-
Read digital outputs
2-
Read digital inputs
3-
Read analog registers
4-
Read analog inputs
5-
Write 1 digital output
6-
Write 1 analog register
7-
Write multiple digital output
8-
Write multiple analog registers
Restrictions
For
Read only
points function codes 1, 2, 3 or 4 can be used
For
write only points
, function codes 5, 6, 15 or 16 can be used
For
read/write points
, see section 5.1.3
Edit mode
Single / Multiple Values selection.
Comments
Consult documentation of Modbus device(s) to integrate for information about function codes
supported to read/write their internal points.
Format
Description
Modbus data format for the point.