IntesisBox
®
BACnet/IP Server - Modbus RTU Master
User’s Manual r14 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SL
URL
Email
tel
http://www.intesis.com
[email protected]
+34 938047134
15 / 27
Figure 5.2
Configuration: Connection Tab
BACnet/IP interface configuration parameters:
Figure 5.3
BACnet/IP interface Configuration
IP:
Enter the IP address for the gateway (supplied by the network administrator).
NetMask
: Enter the IP NetMask for the gateway (supplied by the network
administrator).
Gateway:
Enter the Default Gateway address (router address) in case the gateway
(IntesisBox) is in a different sub network than other BACnet devices (supplied by the
network administrator). Leave blank if there is no need of router address.
BACnet
Port:
Enter the BACnet port number used by the gateway (by default
47808, which is BAC0).