1.3 Capacity of IntesisBox
Element
Tiny
version
Basic
version
Extended
version
Notes
Type of BACnet
devices
Only those supporting BACnet/IP.
Number of BACnet
points
110
500
3000
Maximum number of points that can be
defined in the virtual BACnet device
inside the gateway.
Number of BACnet
subscribers
8
8
8
Maximum
number
of
BACnet
subscribers accepted by the gateway.
Number of BACnet
subscriptions
(COV) requests
220
1000
6000
Maximum
number
of
BACnet
subscriptions (COV) requests accepted
by the gateway.
Type of Modbus
slave devices
Those supporting Modbus
protocol
.
Communication over RS485 network
(2-Wire) or RS232 point to point.
Modbus
Slave devices
254
254
254
Maximum number of Modbus slave
devices allowed by IntesisBox.
There are different models of
IntesisBox BACnet/IP Server - Modbus RTU Master,
with
different capacity every one of them.
Tiny model supporting connection to up to 110 internal data points.
Ref.: IBOX-BAC-MBRTU-100.
Basic model supporting connection to up to 500 internal data points.
Ref.: IBOX-BAC-MBRTU-A.
Extended model supporting connection to up to 3000 internal data points.
Ref.: IBOX-BAC- MBRTU-B.