Description
Buttons to move the selected row (or rows) up or down inside the grid. To
move up or down inside the grid a single row or a group of consecutive
rows, just select the row or rows using the left button of the mouse and
push the desired up or down button.
Comments
This can be done also using the key combinations
ALT+arrow up
or
ALT+arrow down
instead of up or down buttons
Add
Description
Button that adds a row under the selected one.
Delete
Description
Buttons to delete the selected row (or rows).
Save
Description
Save the configuration (details in section 5.1.4)
Exit
Description
Exits the configuration window (details in section 5.1.4)
5.1.3 How to configure read/write points
First of all is important to take into account that different names for Modbusfunction codes,
are used in technical literature depending on the manufacturer of the Modbus device. The
following table shows the equivalence between nomenclature for function codes, used by
Intesis Software in IntesisBox and the used in Modbus protocol specification.
Function code
IntesisBox
Modbus protocol specification
01
Read digital outputs
Read Coils
02
Read digital inputs
Read Discrete Inputs
03
Read analog registers
Read Holding Registers
04
Read analog inputs
Read Input Registers
05
Write 1 digital output
Write Single Coil
06
Write 1 analog register
Write Single Register
15
Write multiple digital outputs
Write Multiple Coils
16
Write multiple analog registers
Write Multiple Registers
Given a point in a Modbus slave device, if this point allows to be read and written, different
Modbus function codes must be used for read and for write actions (consult the slave
documentation for details of what function codes must be used for read and for write). Use
the following criteria for configuration of this kind of points in IntesisBox: