background image

 

7

Water Connections continued- 
 

WARNING 

For protection against excessive temperatures and pressure, install 
temperature and pressure protective equipment required by local codes, 
but not less than a combination temperature and pressure relief valve 
certified by a nationally recognized testing laboratory that maintains 
periodic inspection of production of listed equipment or materials, as 
meeting the Requirements for 

Relief Valves and Automatic Gas Shutoff 

Devices for Hot Water Supply Systems, ANSI Z21.22

, and the Standard 

CAN1-4.4 Temperature, Pressure, Temperature and Pressure Relief 
Valves and Vacuum Relief Valves

.  The combination temperature and 

pressure relief valve shall be marked with a maximum set pressure, not to 
exceed the maximum working pressure of the water heater.  The 
combination temperature and pressure relief valve shall also have an 
hourly rated temperature steam BTU discharge capacity not less than the 
hourly input rating of the water heater. 
 
Install the combination temperature and pressure relief valve into the 
opening provided and marked for this purpose on the water heater 
 
Note:  Some models may already be equipped or supplied with a 
combination temperature and pressure relief valve.  Verify that the 
combination temperature and pressure relief valve complies with local 
codes.  If the combination temperature and pressure relief valve does not 
comply with local codes, replace it with one that does.  Follow the 
installation instructions above on this page. 
 
Install a discharge line so that water discharged from the combination 
temperature and pressure relief valve will exit within six (6) inches  

(15.3 cm)

 above, or any distance below the structural floor and cannot 

contact any live electrical part.  The discharge line is to be installed to 
allow for complete drainage of both the temperature and pressure relief 
valve and the discharge line.  The discharge opening must not be 
subjected to blockage or freezing.  

DO NOT

 thread, plug or cap the 

discharge line.  It is recommended that a minimum of four (4) inches  

(10.2 cm)

 be provided on the side of the water heater for servicing and 

maintenance of the combination temperature and pressure relief valve. 
 
Do not place a valve between the combination temperature and pressure 
relief valve and the tank.

 

Summary of Contents for TWO GALLON ELECTRIC WATER HEATER

Page 1: ...WITH THESE INSTRUCTIONS READ THESE INSTRUCTIONS THOROUGHLY BEFORE STARTING For your family s comfort safety and convenience we recommend this water heater be installed and serviced by a plumbing prof...

Page 2: ...enclosed warranty and refer to it when questions arise If you have any specific questions concerning your warranty please consult the plumbing professional from whom your water heater was purchased F...

Page 3: ...or the purpose of heating potable water The installation and use of this water heater for any purpose other than the heating of potable water may cause damage to the water heater and create a hazardou...

Page 4: ...these instructions After reading these installation and operating instructions select a location for the water heater where the floor is level and is easily accessible to a power supply and water conn...

Page 5: ...and the combination temperature and pressure relief valve will not result in damage to the area adjacent to the water heater or to lower floors of the structure When such locations cannot be avoided a...

Page 6: ...xpansion DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion Your water supplier or local plumbing inspector should be contacted on how to control...

Page 7: ...the opening provided and marked for this purpose on the water heater Note Some models may already be equipped or supplied with a combination temperature and pressure relief valve Verify that the comb...

Page 8: ...e available from your local plumbing supplier Please consult with a plumbing professional APPROXIMATE TIME TEMPERATURE RELATIONSHIPS IN SCALDS 120 F 49 C More than 5 minutes 125 F 52 C 1 to 2 minutes...

Page 9: ...free type and has been factory installed to interrupt all ungrounded power supply conductors in the event of thermostat failure Thermostats are factory set and wired in accordance with the wiring diag...

Page 10: ...liances require high temperature hot water such as dishwashers and automatic clothes washers TO FILL THE WATER HEATER 1 Open the cold water supply shut off valve 2 Open several hot water faucets to al...

Page 11: ...plastic terminal shield has not been displaced replace the access panel The water heater is now ready for operation and the main switch can be closed Figure 1 MAINTENANCE CAUTION Before adjusting the...

Page 12: ...the power supply to the water heater and contact the plumbing professional that installed this water heater or a qualified service technician 3 At least once a year check the combination temperature...

Page 13: ...e time interval for inspection and replacement of the anode rod Contact the plumbing professional who installed the water heater or the manufacturer listed on the rating plate for anode replacement in...

Page 14: ..._____ Supplier ______________________________________________________ Supplier Phone No ______________________________________________ Manufactured under one or more of the following U S Patents RE 34...

Page 15: ...15 NOTES...

Page 16: ...16 NOTES...

Reviews: