background image

11

Jøtul C 

550

 CB Rockland    139656_02     10/2/14

Chimney Connection Requirements

The insert must be connected to a code-approved 

masonry chimney or listed factory-built fireplace 

chimney with a direct (positive) flue connector into 

the first chimney liner section.  The chimney size 

should not be less than, nor more than, three times 

greater than the cross-sectional area of the flue 

collar.

The optional Jøtul Draw-Down Adaptor Kit 

156073 is available  to ease connection of the 

chimney liner with the flue collar.

A positive connection must be made between 

the fireplace insert and the chimney by one of the 

following approved methods. 

U.S. Only Requirements: 

1. 

The insert must be connected to a code-approved 

masonry chimney with a direct (positive) flue 

connector into the first chimney liner section. 

2. 

The cross-sectional area of the chimney flue may 

not be less than the cross-sectional area of the 

flue collar.. 

3.

  A sealed block-off plate must be installed at the 

damper area of the existing fireplace

, unless 

the liner is connected directly to the top of the 

chimney. See fig. 8. 

4.  For internal chimneys, 

(no sides of the chimney 

exposed to the outside below the roofline,) 

a positive connection into the first flue tile is 

acceptable provided the tile is no larger than 8” x 12”. 

5.  For external chimneys, 

(one or more sides are 

exposed to the outside below the roof line, 

including garages), a positive connection to the 

first flue tile is acceptable provided the tile is no 

larger than 8” x 8”. 

6.  A 6”, 7”,  or 8” stainless steel liner, extending the 

full height of the chimney, is required 

for those 

installations where the flue tile is greater than  

8” x 12” for internal chimneys, or  8” x 8” for 

external chimneys. In such cases, a damper block-

off plate is not required.

Canada Requirement: 

The insert must be installed with a continuous 

chimney liner of 6” (152 mm) diameter extending 

from the fireplace insert to the top of the chimney. 

The chimney liner must conform to the Class 3 

requirements of CAN/ULC-S635, Standard for Lining 

Systems for Existing Masonry or Factory-Built 

Chimneys and Vents, or CAN/ULC-S640, Standard for 

Lining Systems for New Masonry Chimneys.  

See fig. 9. 
Do not use aluminum or galvanized steel pipe for 

chimney connection components - these materials 

are not suitable for use with solid fuel.

Locking

Bracket

Damper

Frame

Adjustable

Sealing Plate

Flex

Connector

Flex 

Connector 

Pipe 

extends at 

least into 

the first 

flue tile 

Figure 8.  Positive Chimney Connection with an 

example of a damper block-off plate - U.S. only.

Attach Fireplace 

Conversion 

Notice Plate 

to Rear Wall of 

Fireplace

Summary of Contents for Jotul C 550 CB Rockland

Page 1: ...land 139656_02 10 2 14 J tul C 550 CB Rockland Fireplace Insert Keep these instructions for future reference Installation and Operating Instructions for the United States Canada V2 J tul C 550 CB Rock...

Page 2: ...6_02 10 2 14 NOTICE YOU SHOULD CONSULT THE AUTHORITY HAVING JURISDICTION IN YOUR LOCALE SUCH AS MUNICIPAL BUILDING DEPARTMENT FIRE DEPARTMENT FIRE PREVENTIOIN BUREAU ETC BEFORE INSTALLATION TO DETERMI...

Page 3: ...ntents Standards and Safety Notices Standards Codes 4 Safety Notices 5 Preparation 5 Unpacking the Firebox 5 Specifications J tul C 550 Rockland Fireplace Insert 6 Installation Masonry Fireplace Requi...

Page 4: ...tallation non appropri e de ce po le de chauffage ris que de provoquer un incendie Assurez votre s curit en respectant les directives d installation suivantes Consultez les autorit s locales du b time...

Page 5: ...ed appliance will not guarantee proper chimney performance Consult your local J tul authorized dealer regarding spe cific installation performance issues Installation Preparation We strongly urge you...

Page 6: ...550 CB Rockland Fireplace Insert meets U S EPA emission limits for wood heaters sold after July 1990 and is tested and listed to ANSI UL 1482 and CAN ULC S628 93 It is intended for installation in acc...

Page 7: ...fireplace with the following conditions The factory built fireplace must be listed per UL 127 or ULC S610 The factory built chimney system must be fully lined with listed chimney liner meeting type H...

Page 8: ...ossible in these instances A custom built surround panel system may be used provided it does not interfere with air circulation through the convection chamber louvers Air flow within and around the fa...

Page 9: ...such as drapes or doors that could swing into the area within 36 of the insert Mantel Clearances The installation must conform to the minimum mantel clearances specified in the chart below These clear...

Page 10: ...line as noted below A Hearth Protection width from centerline 18 1 2 470 mm B Hearth Protection forward from door opening US 16 CAN 20 508 mm C To Side Trim 1 max thickness from centerline 21 3 4 552...

Page 11: ...nto the first flue tile is acceptable provided the tile is no larger than 8 x 12 5 For external chimneys one or more sides are exposed to the outside below the roof line including garages a positive c...

Page 12: ...nts from the fireplace Alternatively you can wire the damper plate to lock it in the open position Thoroughly clean the firebox and smokeshelf area with a wire brush 2 If the fireplace has been modifi...

Page 13: ...IREPLACE 2 Insert the AC power receptacle lead through the ap propriate inlet in the side of the firebox See fig 10 Remove the 8 x 5 8 phillips screw already in place and engage the receptacle bracket...

Page 14: ...h 5 If appropriate attach the Extended Surround Pan el to the firebox See illustration on page 6 With the painted side facing out engage the hooked tabs on panel with the slots in the backside of the...

Page 15: ...arting or reviving the fire the control lever should be set at the far right position to allow the maximum amount of air into the stove See fig 15 After the fire is well established the lever should b...

Page 16: ...rol without waiting for the fire to be reestablished Creosote Formation This appliance is designed to burn wood cleanly and efficiently when operated as described in this manual However when wood is b...

Page 17: ...tion of creosote An exterior chimney whether masonry or prefabricated steel will be ex posed to cold outside temperatures and consequently will be more prone to creosote accumulation than an interior...

Page 18: ...tible materials pending final dis posal If the ashes are disposed of by burial in soil or otherwise dispersed they should be kept in the closed container until all coals and cinders have thoroughly co...

Page 19: ...for seal integrity The gaskets should be soft enough to be somewhat resilient to the touch Over time gaskets will com press and harden Replace worn out or hardened gaskets with the appropriate size ma...

Page 20: ...SA 24 127215 Blower Maintenance In order to ensure that the blower delivers many years of reliable performance you should inspect it regularly and clean it of any household dust and debris that may ha...

Page 21: ...21 J tul C 550 CB Rockland 139656_02 10 2 14 This page is intentionally blank...

Page 22: ...ine J tul replacement parts Do not substitute parts from any other manufacturer See your local Authorized J tul Dealer or contact us directly J tul North America 55 Hutcherson Dr Gorham Maine 04038 Fi...

Page 23: ...No Description Part Number 1 Rear Shroud 222027 2 Screw 8 x 1 2 Hex Slt 117917 3 Nut M6 Flange 117968 4 Right Baffle Plate 157045 5 Left Baffle Plate 157044 6 Secondary Air Tube Front 223262 7 Seconda...

Page 24: ...31 Total R R brick R mineral board 0 8 0 431 1 231 Step 3 Compare proposed system R 1 231 to specified R of 0 893 Since R is greater than required the system is acceptable Definitions Thermal conducta...

Page 25: ...red Over firing can also be identified by warped plates rust colored cast iron paint pig ment that has turned dusty white or bubbling cracking and discolor ation of the enamel finish Misuse includes w...

Page 26: ...26 J tul C 550 CB Rockland 139656_02 10 2 14 This page is intentionally blank...

Page 27: ...27 J tul C 550 CB Rockland 139656_02 10 2 14 This page is intentionally blank...

Page 28: ...lations It is important that the these instructions be carefully read and understood before beginning the instal lation J tul pursues a policy of continual product development Consequently products ma...

Reviews: