![Interra ITR901-001 Product Manual Download Page 23](http://html1.mh-extra.com/html/interra/itr901-001/itr901-001_product-manual_2080319023.webp)
KNX IP Router
Product Manual
23
@2019 INTERRA
PM190205012AEN
5.1.1) Access via Windows Network UPnP
When the UPnP network function is enabled, ITR901-001 Interra KNX IP Router appears in the Windows Network. A click
on the ITR901-001 network device opens the Web front-end with the standard web browser. If Interra KNX IP Router is not
visible as an UPnP network device a manual restart is recommended. After that, the device becomes visible in the list of
network devices.
5.1.2) Access via IP Address
When IP address and HTTP port (80 or 8080) are known, this information is sufficient to access the ITR901-001 Web front-
end by a web browser. The actual IP address is shown in the ETS list of Discovered Interfaces.
The above box shows how to enter the IP address and HTTP port in the URL bar.
Ex 1 : DHCP is not used. With the latest ETS download the IP address was set to 192.168.1.32 and HTTP port was set to
80. In the browser´s URL bar has to be entered “http://192.168.1.32:80/”.
Ex 2 : With the latest ETS download HTTP port was set to 8080 and DHCP was activated. The DHCP server assigned a free
IP address to MECip and ETS shows this IP address to be 192.168.1.201. In th
e browser´s URL bar has to be entered
“http://192.168.1.201:8080/”.
5.1.3) Access via MAC Address
When NetBIOS is installed (by default on Windows systems and Linux systems containing SAMBA) the MAC address that
is printed on a label on the side of the ITR901-001 housing can be used. Due to name resolution is mandatory to establish
communication by Host name, activation of NetBIOS is necessary.
Use the MAC address in the form of AA-BB-CC-XX-YY-ZZ and the pre-set HTTP
port to be entered in the browser´s URL
bar as described here (without brackets):
Ex :
On the housing side ITR901-001 is labelled with MAC address D0-72-59-55-44-66 and the pre-set HTTP port is 8080.
Then, in the web browser´s URL bar has to be entered
“http://knx
-iprt-
554466:8080/”
.
Note : The values to be entered in the browser bar are the values inside the quotation mark.