International comfort products R2H3 Series Installation Instructions Manual Download Page 4

INSTALLATION INSTRUCTIONS

R-22 Split System Heat Pump

4

428 01 5202 00

UNIT SUPPORT

NOTE:

 Unit must be level 

 2 degrees (

 inch rise or fall

per foot of run) or compressor may not function properly.

A. GROUND LEVEL INSTALLATION

The unit must be level and supported above grade by
beams, platform, or a pad. Platform or pad can be of open or
solid construction but should be of permanent materials
such as concrete, bricks, blocks, steel, or pressure- treated
timbers approved for ground contact. Soil conditions must
be considered so that the platform or pad does not shift or
settle and leave the unit partially supported. Minimum pad
dimensions are shown in Figure 2.

If beams or an open platform are used for support, it is
recommended that the soil be treated or area be graveled
to reduce the growth of grasses and weeds.

To minimize vibration or noise transmission, it is
recommended that supports not be in contact with the
building structure. However, slabs on grade constructions
with an extended pad are normally acceptable.

!

CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.

Top surface of platform must be above estimated snow‐
fall level to prevent snow blocking coil and to allow water
melt to drain from unit.

B. ROOF TOP INSTALLATION

This type of installation is not recommended on wood
frame structures where low noise levels are required.

Supporting structure or platform for the unit must be level.
If installation is on a flat roof, locate unit minimum 6 inches
above roof level.

Place the unit over one or more load bearing walls. If there
are several units, mount them on platforms that are
self-supporting and span several load bearing walls. These
suggestions are to minimize noise and vibration
transmission through the structure. If the structure is a home
or apartment, avoid locating the unit over bedrooms or study.

NOTE:

 When unit is to be installed on a bonded

guaranteed roof, a release must be obtained from the
building owner to free the installer from all liabilities.

C. FASTENING UNIT DOWN

If conditions or local codes require the unit be attached in
place, remove the knockouts in the base pan and install
tie down bolts through the holes (refer to Figure 2).

Contact local distributor for hurricane hold-down details and
the P.E. (Professional Engineer) certification, when required.

!

CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.

Inadequate unit support may cause excessive vibration,
noise, and/or stress on the refrigerant lines, leading to re‐
frigerant line failure.

Figure 2

Tie Down Knockouts

Base

Pan

Depth

C

B

A

Base Pan Width

” dia. Tie Down Knockouts

In Base Pan (2 places)

Representative View From Top

Product Family: R series

Base Pan

(Square)

Width x Depth

(inches)

Tie Down

Knockouts

Minimum

Mounting Pad

Dimensions

A

B

C

    

 

    

    

 

    

    

 

    

REFRIGERATION SYSTEM

A. COMPONENT MATCHES

Check to see that the proper system components are in
place, especially the indoor coil.

R-22 outdoor units can only be used with R-22 specific
indoor coils. If there is a refrigerant mis-match, consult
the indoor coil manufacturer to determine if a refrigerant
conversion kit is available for the indoor coil.

This outdoor unit is designed for use only with indoor coils
that utilize a TXV refrigerant metering device. If any other
type of metering device is installed on the indoor coil,
consult the indoor coil manufacturer to determine if a TXV
conversion kit is available.

!

CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product
damage.

Indoor coil and outdoor unit must be listed as a
certified combination (match) in the ARI Unitary
Directory of Certified Products.
Indoor coil must have R-22 specific, TXV refriger‐
ant metering device.

Summary of Contents for R2H3 Series

Page 1: ...manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or...

Page 2: ...so that water runoff will not enter the unit Locate unit away from areas where heat lint or exhaust fumes will be discharged onto unit as from dryer vents Locate unit away from recessed or confined a...

Page 3: ...ystem Heat Pump 428 01 5202 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service 24 S...

Page 4: ...the structure If the structure is a home or apartment avoid locating the unit over bedrooms or study NOTE When unit is to be installed on a bonded guaranteed roof a release must be obtained from the b...

Page 5: ...0 feet NOTE When the outdoor unit is lower than the indoor coil the vertical separation must not exceed 50 feet If it is necessary to add refrigerant line in the field use dehydrated or dry sealed deo...

Page 6: ...efrigerant Lines INSULATION SUCTION TUBE LIQUID TUBE OUTDOOR WALL INDOOR WALL LIQUID TUBE SUCTION TUBE INSULATION CAULK HANGER STRAP AROUND SUCTION TUBE ONLY JOIST 1 MIN THROUGH THE WALL SUSPENSION CA...

Page 7: ...valve 2 Check that piston size stamped on side of piston matches with number listed on unit rating plate Return piston to piston body of liquid service valve either direction Return retainer to piston...

Page 8: ...e capable of accurately measuring this vacuum level The deep vacuum method is the most positive way of assuring a system is free of air and water Watch the vacuum gauge as the system is pulling down T...

Page 9: ...main remote electrical disconnect device There may be more than one disconnect device Supply voltage must be 208 230 volts 197 volt minimum to 253 volts maximum 60 Hz single phase Outdoor units are ap...

Page 10: ...LLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE THERM...

Page 11: ...fan motor lead from OF2 on control board refer to Figure 12 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in heating...

Page 12: ...ill default to high speed fan for servicing Reconnect wire after servicing 2 Measure liquid service valve pressure by attaching an accurate gauge to service port 3 Measure liquid line temperature by a...

Page 13: ...heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermostat field installed option contacts close to complet...

Reviews: