SEQUENCE OF OPERATION

A. COOLING MODE

On a call for cooling, the thermostat makes circuits R-O,
R-Y, and R-G. Circuit R-O energizes reversing valve,
switching it to cooling position. Circuit R-Y energizes
contactor, starting outdoor fan motor and compressor.
Circuit R-G energizes indoor unit blower relay, starting
indoor blower motor.

When thermostat is satisfied, its contacts open,
de-energizing contactor and blower relay. Compressor
and motors stop.

NOTE:

 If indoor unit is equipped with a time-delay relay

circuit, the blower runs an additional length of time to
increase system efficiency. (Applies to both cooling and
heating modes.)

B. HEATING MODE

On a call for heating, the thermostat makes circuits R-Y
and R-G (circuit R-O is NOT made, and the reversing
valve stays in the de-energized, heating position). Circuit
R-Y energizes contactor, starting outdoor fan motor and
compressor. Circuit R-G energizes indoor blower relay,
starting blower motor. If the room temperature continues
to fall, circuit R-W2 is made through the second-stage
room thermostat bulb. Circuit R-W2 energizes a
sequencer, bringing on the first bank supplemental
electric heat and providing electrical potential to the
second heater sequencer (if used). If outdoor
temperature falls below the setting of the outdoor
thermostat (field-installed option), contacts close to
complete the circuit and bring on the second bank of
supplemental electric heat.

When the thermostat is satisfied, its contacts open,
de-energizing contactor, blower relay, and sequencer.
Compressor, motors, and heaters stop.

MAINTENANCE

Condensate Drain

During the cooling season, check monthly for free flow of
drainage and clean if necessary.

Cleanliness

These tips will help keep the air conditioner looking better
and working more efficiently:

1.

Free flow of air is essential. Keep fences, shrubs,
trash cans, and other obstructions at least 18
inches from all coil inlets.

2.

Keep the coil free of grass clippings, leaves,
weeds, and other debris.

NOTE:

 Coil may occasionally require cleaning with

a liquid solution. The coil must be cold when
cleaning. Use an alkaline based cleaner only.
Cleaning a hot coil or using an acid based cleaner
will remove the paint from the fins and may clog the
coil.

3.

Never use a weather cover over the outdoor unit
unless it is a ventilated type or made of breathable
fabric that will allow moisture to evaporate rapidly.
A cover that holds moisture in the unit will cause
more rust build-up and damage than normal
exposure to weather.

International Comfort Products, LLC

Lewisburg, TN 37091

Summary of Contents for R2H3 Series

Page 1: ...manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or...

Page 2: ...so that water runoff will not enter the unit Locate unit away from areas where heat lint or exhaust fumes will be discharged onto unit as from dryer vents Locate unit away from recessed or confined a...

Page 3: ...ystem Heat Pump 428 01 5202 00 3 Figure 1 Clearances various examples Wall 6 24 Service Wall Wall Wall 6 6 Post Wall Wall 18 18 18 18 6 6 6 18 18 18 18 24 Service 24 Service 24 Service 24 Service 24 S...

Page 4: ...the structure If the structure is a home or apartment avoid locating the unit over bedrooms or study NOTE When unit is to be installed on a bonded guaranteed roof a release must be obtained from the b...

Page 5: ...0 feet NOTE When the outdoor unit is lower than the indoor coil the vertical separation must not exceed 50 feet If it is necessary to add refrigerant line in the field use dehydrated or dry sealed deo...

Page 6: ...efrigerant Lines INSULATION SUCTION TUBE LIQUID TUBE OUTDOOR WALL INDOOR WALL LIQUID TUBE SUCTION TUBE INSULATION CAULK HANGER STRAP AROUND SUCTION TUBE ONLY JOIST 1 MIN THROUGH THE WALL SUSPENSION CA...

Page 7: ...valve 2 Check that piston size stamped on side of piston matches with number listed on unit rating plate Return piston to piston body of liquid service valve either direction Return retainer to piston...

Page 8: ...e capable of accurately measuring this vacuum level The deep vacuum method is the most positive way of assuring a system is free of air and water Watch the vacuum gauge as the system is pulling down T...

Page 9: ...main remote electrical disconnect device There may be more than one disconnect device Supply voltage must be 208 230 volts 197 volt minimum to 253 volts maximum 60 Hz single phase Outdoor units are ap...

Page 10: ...LLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2 C Y O R W 2 SUBBASE THERM...

Page 11: ...fan motor lead from OF2 on control board refer to Figure 12 Tape lead to prevent grounding 3 Restart unit in heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in heating...

Page 12: ...ill default to high speed fan for servicing Reconnect wire after servicing 2 Measure liquid service valve pressure by attaching an accurate gauge to service port 3 Measure liquid line temperature by a...

Page 13: ...heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermostat field installed option contacts close to complet...

Reviews: